| 2003-01-09 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC* 104.2.4A SIGNED AND SEALED |
| | SURVEY DRAWING IS REQUIRED. |
| | |
| | 2) FL. ADMIN. CODE 61G15-23.002THE |
| | FOUNDATION PLAN SHEET SHALL BE SIGNED, |
| | SEALED AND DATED. |
| | |
| | 3) INFORMATIVE: |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 4) INFORMATIVE: |
| | IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY, THE PLANS STAMPED BY THEM AND A |
| | COPY OF THE RECEIPT SUBMITTED TO THE |
| | CITY OF WEST PALM BEACH CONSTRUCTION |
| | SERVICES DEPARTMENT BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5) FBC 11-4.1.2THE BUILDING SHALL BE |
| | SERVED BY AT LEAST ONE ACCESSIBLE ROUTE |
| | FROM THE ACCESSIBLE PARKING. |
| | ACCEPTABILITY OF THESE PLANS IS |
| | CONTINGENT UPON THE CIVIL/SITE PLANS, |
| | PERMIT# 02102208, BEING PERMITTED. |
| | |
| | 6) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE |
| | ROOFING, EXTERIOR DOORS AND WINDOWS. |
| | |
| | 8) FBC* 104.2.1.2SUBMIT STRUCTURAL |
| | PLANS FOR THE SECOND FLOOR AND ROOF |
| | LAYOUT. |
| | |
| | 9) FBC 311.2RESIDENTIAL OCCUPANCY |
| | CLASSIFICATION.DRAWING SHEET GN4-1 |
| | STATES THE OCCUPANCY GROUP AS R3.IT IS |
| | ASSUMED THAT THIS DECISION IS BASED ON |
| | THE BUILDING ASSESSED AS 'ROOMING HOUSE |
| | (TRANSIENT)'.THIS IS NOT APPROPRIATE |
| | AS THE DEFINITION, IN SECTION 202, OF |
| | ROOMING HOUSE LIMITS THE BUILDING TO NOT |
| | MORE THAN FIVE GUEST ROOMS.THE CORRECT |
| | OCCUPANCY CLASSIFICATION WOULD BE R1. |
| | |
| | 10) FBC 1004.2MINIMUM NUMBER OF EXITS. |
| | A MINIMUM OF TWO INDEPENDENT EXITS ARE |
| | REQUIRED FROM THE SECOND FLOOR BECAUSE |
| | THE BUILDING DOES NOT MEET THE |
| | CONDITIONS OF FBC 1026.1 (SINGLE EXIT), |
| | AND FBC 1026.1.2 DOES NOT APPLY (SEE |
| | PRECEDING COMMENT).AMEND THE PLANS TO |
| | SHOW TWO EXIT STAIRWAYS FROM THE SECOND |
| | FLOOR. |
| | |
| | 11) FBC* 104.2.1.2SUBMIT A STAIRWAY |
| | LAYOUT DRAWING WITH DIMENSIONS/DETAILS |
| | OF THE STAIRS. |
| | |
| | 12) SHEETS A4-2.1 AND A4-2.2.THE |
| | PARTITION LEGEND IS INCLUDED BUT NONE OF |
| | THE PARTITION TYPE REFERENCE MARKERS ARE |
| | SHOWN ON THE FLOOR LAYOUT.ALSO, THE |
| | 'ARCHITECTURAL NOTES' AND 'DRAWING |
| | LEGEND' REFER TO SHEETS A4-10.1 AND |
| | A4-10.2 BUT THESE SHEETS ARE NOT |
| | INCLUDED WITH THE PLAN SET. |
| | |
| | 13) FBC 2309.6SHEET A-11.02.ATTIC |
| | ACCESS PANELS APPEAR TO BE SHOWN ON THE |
| | PLAN, BUT THERE IS NO ANNOTATION TO |
| | CONFIRM THIS OR TO GIVE THE DIMENSIONS. |
| | |
| | 14) FBC 11-4.9.4(2)SHEET A4-8.1, TYP. |
| | SIDE WALL RAILING DETAIL.THE HANDRAIL |
| | SHALL EXTEND AT LEAST 12" HORIZONTALLY |
| | BEYOND THE TOP RISER, AND SHALL |
| | CONTINUE TO SLOPE PAST THE BOTTOM RISER |
| | FOR A DISTANCE EQUAL TO THE WIDTH OF ONE |
| | TREAD AND THEN EXTEND A FURTHER 12" |
| | HORIZONTALLY AT THE BOTTOM. |
| | |
| | 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |