Plan Review Details - Permit 02102205
Plan Review Stops For Permit 02102205
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-09 Cont ID  
Sent By rbrown Date 2003-01-09 Time 16:48 Rev Time 0.00
Received By rbrown Date 2003-01-09 Time 16:48 Sent To  
Notes
2003-01-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 2) FL. ADMIN. CODE 61G15-23.002THE
 FOUNDATION PLAN SHEET SHALL BE SIGNED,
 SEALED AND DATED.
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING.
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 8) FBC* 104.2.1.2SUBMIT STRUCTURAL
 PLANS FOR THE SECOND FLOOR AND ROOF
 LAYOUT.
  
 9) FBC 311.2RESIDENTIAL OCCUPANCY
 CLASSIFICATION.DRAWING SHEET GN4-1
 STATES THE OCCUPANCY GROUP AS R3.IT IS
 ASSUMED THAT THIS DECISION IS BASED ON
 THE BUILDING ASSESSED AS 'ROOMING HOUSE
 (TRANSIENT)'.THIS IS NOT APPROPRIATE
 AS THE DEFINITION, IN SECTION 202, OF
 ROOMING HOUSE LIMITS THE BUILDING TO NOT
 MORE THAN FIVE GUEST ROOMS.THE CORRECT
 OCCUPANCY CLASSIFICATION WOULD BE R1.
  
 10) FBC 1004.2MINIMUM NUMBER OF EXITS.
 A MINIMUM OF TWO INDEPENDENT EXITS ARE
 REQUIRED FROM THE SECOND FLOOR BECAUSE
 THE BUILDING DOES NOT MEET THE
 CONDITIONS OF FBC 1026.1 (SINGLE EXIT),
 AND FBC 1026.1.2 DOES NOT APPLY (SEE
 PRECEDING COMMENT).AMEND THE PLANS TO
 SHOW TWO EXIT STAIRWAYS FROM THE SECOND
 FLOOR.
  
 11) FBC* 104.2.1.2SUBMIT A STAIRWAY
 LAYOUT DRAWING WITH DIMENSIONS/DETAILS
 OF THE STAIRS.
  
 12) SHEETS A4-2.1 AND A4-2.2.THE
 PARTITION LEGEND IS INCLUDED BUT NONE OF
 THE PARTITION TYPE REFERENCE MARKERS ARE
 SHOWN ON THE FLOOR LAYOUT.ALSO, THE
 'ARCHITECTURAL NOTES' AND 'DRAWING
 LEGEND' REFER TO SHEETS A4-10.1 AND
 A4-10.2 BUT THESE SHEETS ARE NOT
 INCLUDED WITH THE PLAN SET.
  
 13) FBC 2309.6SHEET A-11.02.ATTIC
 ACCESS PANELS APPEAR TO BE SHOWN ON THE
 PLAN, BUT THERE IS NO ANNOTATION TO
 CONFIRM THIS OR TO GIVE THE DIMENSIONS.
  
 14) FBC 11-4.9.4(2)SHEET A4-8.1, TYP.
 SIDE WALL RAILING DETAIL.THE HANDRAIL
 SHALL EXTEND AT LEAST 12" HORIZONTALLY
 BEYOND THE TOP RISER, AND SHALL
 CONTINUE TO SLOPE PAST THE BOTTOM RISER
 FOR A DISTANCE EQUAL TO THE WIDTH OF ONE
 TREAD AND THEN EXTEND A FURTHER 12"
 HORIZONTALLY AT THE BOTTOM.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2002-11-26 Time 16:26 Rev Time 2.00
Received By dpalmer Date 2002-11-26 Time 16:26 Sent To  
Notes
2002-11-26 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE MISSING ARC FAULT
 PROTECTION FOR BEDROOM RECEPTS.210-12
  
 2)NOTE: PLEASE NOTE, MISSING REQ`D
 SD`S PER NFPA-72 8-1
  
 3)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH PANEL SCHEDULES.
  
 4)NOTE: PLEASE NOTE BATH CIRCTUIT(S)
 PER 210-52D/210-11-C3
  
 5)NOTE: PLEASE NOTE KITCHEN COUNTERSPACE
 OUTLETS TO MEET SPACING PER 210-52C.
  
 6)NOTE: PLEASE NOTE, NO FIXTURE SCHEDULE
 SUBMITTED. PLEASE CLARIFY IF LTS REQ`D
 FOR EM ILLUMINATION MEET 700-16.
  
 7)NOTE: PLEASE NOTE, PANELS AND LOAD
 CALCULATIONS NEED TO BE DONE FOR A
 REVIEW TO BE DONE. PLEASE COMPLETE
 E4-4.01
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE, THERE MAY BE OTHER
 COMMENTS WHEN PLANS ARE COMPLETED FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-06-25 Cont ID  
Sent By mamini Date 2003-06-25 Time 10:31 Rev Time 1.00
Received By mamini Date 2003-06-25 Time 10:30 Sent To  
Notes
2003-06-25 00:00:00PASSED:
 1. SEE PERMIT # 02102208 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-7623
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-03-17 Cont ID  
Sent By mamini Date 2003-03-17 Time 10:23 Rev Time 1.00
Received By mamini Date 2003-03-17 Time 10:22 Sent To  
Notes
2003-03-17 00:00:00FAILED:
 1. SEE REVIEW COMMENTS PERMIT # 02102208
 DATED 03-17-03.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By mamini Date 2002-11-06 Time 10:30 Rev Time 0.00
Received By mamini Date 2002-11-06 Time 10:29 Sent To  
Notes
2003-01-10 00:00:00FAILED:
 1. SEE REVIEW COMMENTS FOR PLAN REVIEW #
 02102208.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-04 Cont ID  
Sent By mcarsill Date 2002-12-04 Time 17:07 Rev Time 0.00
Received By mcarsill Date 2002-12-04 Time 17:06 Sent To  
Notes
2002-12-04 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
  
 2) WHAT PROVISIONS WILL BE MADE FOR
 FIRE AND PARAMEDICAL ACCESS THRU THE
 SECURITY GATES. IF THE SECURITY GATES
 ARE ELECTRIC,WHAT PROVISIONS WILL BE
 MADE IN THE EVENT OF LOSS OF POWER.
  
 3) KNOX-BOXES WILL BE REQUIRED ON ALL
 THE BUILDINGS.
  
 4) THE MINIMUM WIDTH FOR FIRE RESCUE
 ACCESS SHALL BE AT LEAST 20 FEET IN
 CLEAR WIDTH.
  
 5) WILL THE GUARD HOUSE BE STAFFED FULL
 TIME.
  
 6) HOW IS FIRE AND PARAMEDICAL ACCESS
 ACHEIVED FOR COTTAGES 8,9,12,13.
  
 7) PLEASE EXPLAIN SINGLE STAIRWAY
 THEORY FROM SECOND FLOOR.
  
 8) BUILDING ADDRESS REQUIRED ON
 BUILDING.
  
 9) PLEASE SHOW EMERGENCY LIGHTING FOR
 CORRIDORS ON ELECTRICAL PAGES.
  
 10) PLEASE INDICATE THE LOCATIONS OF
 SMOKE DETECTORS WITHIN THE RESIDENTIAL
 AREAS, MORE SPECIFICALLY THE SLEEPING
 ROOMS ON THE PLANS.
  
 11) PLANS APPEAR TO BE INCOMPLETE.
 PLEASE REVISE PLANS AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By pkrauss Date 2002-12-02 Time 16:36 Rev Time 1.45
Received By pkrauss Date 2002-12-02 Time 16:31 Sent To  
Notes
2002-12-02 00:00:00BUILDING #4 - VISTATION
 DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3, FOR ALL
 AREAS, RESIDENTIAL & COMMON.
 INDICATE DUCT SIZE, MATERIAL, LAYOUT
 AND INTAKE LOCATION ON PLAN.
  
 2.RETURN AIR REQUIRED FROM THE BEDROOM
 AREA IN THE RESIDENTIAL SPACES.
 2001 FBC(M) 601.4.
  
 3.PROVIDE INFORMATION ON THE DRYER
 VENT.DUCT SIZE, MATERIAL, &
 TERMINATION.
  
 4.PROVIDE DETAIL FOR TOILET EXHAUST.
  
 5.PLAN SHEET M4-2.01, EXHAUST FOR THE
 BATHROOMS, JANITOR, AND ELECTRICAL
 ROOMS NO DETAILS GIVEN AS TO SIZE,
 MATERIAL OR TERMINATION.WILL DUCT
 BE ENCLOSED IN A SHAFT THROUGH THE
 ROOF OR OUT THE SIDE?PLEASE
 CLARIFY.
  
 6.VAV BOXES ARE IDENTIFIED ON PLAN
 SHEET M4-2.01 BUT ARE NOT IDENTIFIED
 ON THE SCHEDULE SHOWN ON M4-6.01.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-14 Cont ID  
Sent By kstevens Date 2002-12-14 Time 18:57 Rev Time 0.75
Received By kstevens Date 2002-12-14 Time 18:57 Sent To  
Notes
2002-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A4-2.1 KITCHEN/BREAK ROOM, SINK
 SHALL COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. PLEASE PROVIDE DETAIL
 2) SHT P-4.201 RPZ BACK FLOW REQUIRED ON
 WATER SERVICE.
 3) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM. SHOW ALL
 PIPE SIZES, ECT. ON SANT. RISER.
 SHOW ALL PIPE SIZES AND WATER HAMMER
 ARRESTORS REQUIRED FOR ALL QUICK CLOSING
 VALVES PER 604.9. (WASH MACHINE, DISH
 WASHER, ICE MACHINE). LOCATE NEAR FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT IN
 CEILING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By sgraham Date 2003-01-13 Time 10:27 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-13 00:00:00DENIED, NEED MINOR AMENDMENT AND THE
 PLAT NEED TO BE RECORDED


Account Summary | Usage Policy | Privacy Policy