Plan Review Details - Permit 02102203
Plan Review Stops For Permit 02102203
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-10-27 Cont ID  
Sent By rbrown Date 2003-10-27 Time 17:23 Rev Time 0.00
Received By rbrown Date 2003-10-27 Time 17:22 Sent To  
Notes
2003-10-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/04/03:
  
 1) FBC* 105.13.1SPECIAL INSPECTOR.
 THIS COMMENT HAS NOT BEEN ADDRESSED.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING PURPOSES
  
 4) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 5) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 7) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, ON SHEET 1, COMPLETE THE
 PROJECT DETAILS INCLUDING NAME OF OWNER,
 PROJECT ADDRESS (4878 N. HAVERHILL RD),
 ZIP (33417) AND PERMIT NUMBER (02102203)
  
 8) THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.
 (I) DRAWING SHEET 1 OF THE SUBMITTED PGT
 INDUSTRIES ALUMINUM FIXED WINDOW PRODUCT
 APPROVAL NOA# 01-0102.01 STATES THAT THE
 DESIGN PRESSURE RATING OF THE IMPACT
 WINDOWS, WITH HEAT STRENGTHENED
 LAMINATED GLASS, IS +60 PSF & -60 PSF.
 THIS IS EXCEEDED BY THE MAXIMUM NEGATIVE
 DESIGN PRESSURE (-72 PSF) STATED ON PLAN
 SHEETS A1-5.1 AND A1-5.2 (ELEVATIONS).
 SUBMIT A PRODUCT APPROVAL WITH THE
 APPROPRIATE DESIGN PRESSURE RATING.
  
 --PROVISO--
 THE SUBMITTED ARCH ALUMINUM NARROW STILE
 DOOR PRODUCT APPROVAL NOA# 01-0910.09
 STATES THAT THESE DOORS ARE NOT IMPACT
 RESISTANT.SUBMIT A PRODUCT APPROVAL
 FOR HURRICANE MISSILE IMPACT PROTECTION
 SHUTTERS IF THESE DOORS ARE TO USED.
  
 --PROVISO--
 THE SUBMITTED ARCH ALUMINUM SERIES 4500
 STOREFRONT PRODUCT APPROVAL
 NOA# 00-1220.05 STATES THAT THIS SYSTEM
 IS NOT IMPACT RESISTANT.SUBMIT A
 PRODUCT APPROVAL FOR HURRICANE MISSILE
 IMPACT PROTECTION SHUTTERS IF THIS
 SYSTEM IS TO BE USED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-06-04 Cont ID  
Sent By rbrown Date 2003-06-04 Time 14:22 Rev Time 0.00
Received By rbrown Date 2003-06-04 Time 14:22 Sent To  
Notes
2003-06-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/13/03 AND 4/23/03:
  
 1) FBC* 105.13.1SPECIAL INSPECTOR.
 THIS COMMENT HAS NOT BEEN ADDRESSED.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.
  
 2) THIS COMMENT HAS NOT BEEN ADDRESSED
 FBC* 104.2.4SITE SURVEY.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES.). THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???).
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 5) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 6) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING AND BUS STOP
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 7) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, THE ARCHITECT'S NAME AND
 REGISTRATION NUMBER SHALL BE ADDED ABOVE
 THOSE OF THE OTHER SYSTEM DESIGNERS.ON
 SHEET 1, COMPLETE THE PROJECT DETAILS
 INCLUDING NAME OF OWNER, PROJECT ADDRESS
 (4878 N. HAVERHILL RD), ZIP (33417)
 AND PERMIT NUMBER (02102203).
  
 8) PRODUCT APPROVALS.THE PRODUCT
 APPROVAL SHEETS SHALL BE MARKED, AS
 APPROPRIATE TO IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS ARE TO BE USED, ALSO:
 (A) THE SUBMITTED COPIES OF TIMBERLINE
 SELECT 40 ASPHALT SHINGLE PRODUCT
 APPROVAL NOA# 03-0219.08 IS MISSING
 SHEET 3 OF 3.ALSO, SHEET 2 IS A POOR
 COPY.SUBMIT TWO COPIES OF A COMPLETE
 AND LEGIBLE PRODUCT APPROVAL.
 (H) THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM NARROW STILE
 DOOR PRODUCT APPROVAL NOA# 01-0910.09
 ARE POORLY REPRODUCED.SUBMIT LEGIBLE
 COPIES.NOTE THAT THESE DOORS ARE NOT
 IMPACT RESISTANT, AND WILL REQUIRE THE
 INSTALLATION OF HURRICANE SHUTTERS.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (J) THE SUBMITTED ARCH ALUMINUM SERIES
 4500 STOREFRONT PRODUCT APPROVAL NOA#
 00-1220.05 IS FOR A NON-IMPACT RATED
 SYSTEM.THE INSTALLATION OF HURRICANE
 MISSILE IMPACT PROTECTION SHUTTERS WILL
 BE REQUIRED.THE PLANS SHALL IDENTIFY
 WHERE THIS SYSTEM IS TO BE USED AND A
 HURRICANE MISSILE IMPACT PROTECTION
 SHUTTER PRODUCT APPROVAL SHALL BE
 SUBMITTED.
  
 14) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-05-05 Time 08:57 Rev Time 0.00
Received By rbrown Date 2003-04-23 Time 14:05 Sent To  
Notes
2003-04-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/13/03:
  
 1) FBC* 105.13.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.
  
 2) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4SITE SURVEY.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES.). THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???).
  
 4) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 5) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 6) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING AND BUS STOP
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 7) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 8) PRODUCT APPROVALS: DOOR, WINDOW, ROOF
 (A) ASPHALT SHINGLE PRODUCT APPROVAL
 NOA# 00-0105.02 EXPIRED ON 4/22/03.
 SUBMIT A VALID PRODUCT APPROVAL.
 (B) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. 98/99 RIM EXIT STEEL DOOR PRODUCT
 APPROVAL NOA# 01-1203.11 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (C) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. F, M FRAME STEEL DOOR PRODUCT
 APPROVAL NOA# 01-0129.12 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (D) NOT USED
 (E) THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM STOREFRONT DOOR
 PRODUCT APPR. NOA# 01-0919.02 ARE POORLY
 REPRODUCED.SUBMIT LEGIBLE COPIES.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (F) THE SUBMITTED 2 PAGE COPY EXTRACT OF
 THE 48 PAGE GAF MODIFIED BITUMEN ROOF
 PRODUCT APPROVAL NOA# 00-0331.09 DOES
 NOT INCLUDE A STATEMENT OF THE MAXIMUM
 DESIGN PRESSURE AND STATES THAT "ALL
 GENERAL AND SYSTEM LIMITATIONS SHALL
 APPLY".SUBMIT COPIES OF THE SHEETS
 WHICH STATE THE GENERAL AND SYSTEM
 LIMITATIONS AND THE MAX DESIGN PRESSURE.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (G) SHEET A2-5.1, WEST ELEVATION.DOORS
 108A AND 108B INCORPORATE GLAZED LITES
 ABOVE, GIVING AN OVERALL HEIGHT IN
 EXCESS OF 10 FT.THE DOOR SCHEDULE
 (SHEET A2-10.1) DOES NOT REFLECT THIS.
 ALSO THE OVERALL HEIGHT IS OUTSIDE THE
 SCOPE OF THE SUBMITTED ARCH ALUMINUM
 STOREFRONT DOOR PRODUCT APPROVAL
 NOA# 01-0919.02.SUBMIT AN APPROPRIATE
 DOOR PRODUCT APPROVAL OR A STRUCTURAL
 MULLION PRODCT APPROVAL.
  
 9) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.FBC 1403.9 LIMITS RIGID
 VINYL SIDING TO BUILDINGS OF TYPE VI
 CONSTRUCTION ONLY.THIS BUILDING
 CANNOT BE TYPE VI AS THE OCCUPANCY CLASS
 AND AREA ARE OUTSIDE THE ACCEPTANCE
 CRITERIA (SEE COMMENT 13, BELOW).AN
 ALTERNATIVE TYPE OF SIDING THAT WOULD BE
 ACCEPTABLE IS FIBER-CEMENT SIDING
 (HARDIPLANK OR SIMILAR).AMEND NOTE 2
 ON ELEVATION SHEETS A2-5.1 AND A2-5.2.
  
 10) INFORMATIVE:
 STEEL ROOF TRUSS ANCHORING.G.D KLIEGER
 RESPONSE IS NOTED.ALL STRUCTURAL SHOP
 DRAWINGS SHALL BE REVIEWED AND STAMPED
 BY THE ENGINEER OF RECORD PRIOR TO
 SUBMITTAL TO WPB CONSTRUCTION SVCS DEPT.
  
 13) FBC TABLE 500FROM GBS ARCHITECTURE
 COMMENT RESPONSE LETTER DATED 3-13-03,
 IT IS NOTED THAT THE OCCUPANCY LOAD HAS
 INCREASED AND THE PROPOSED CONSTRUCTION
 TYPE AND OCCUPANCY CLASS WERE REVISED TO
 TYPE VI CONSTRUCTION AND A-1 LARGE
 ASSEMBLY OCCUPANCY RESPECTIVELY. TYPE VI
 (WOOD) CONSTRUCTION FOR LARGE ASSEMBLY
 OCCUPANCY IS NOT PERMITTED BY TABLE 500.
 THE "MAX. NUMBER OF STORIES" FOR THAT
 COMBINATION IS SHOWN IN THE TABLE AS "0"
 IF THERE WERE NO RESTRICTIONS, AS STATED
 IN THE COMMENT RESPONSE LETTER, THE
 TABLE ENTRY WOULD BE NL (I.E. NO LIMIT).
 AMEND SHEET GN2-1.
  
 14) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By rbrown Date 2003-01-13 Time 16:34 Rev Time 0.00
Received By rbrown Date 2003-01-13 Time 16:34 Sent To FIRE
Notes
2003-01-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 105.13.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.
  
 2) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 3) FL. ADMIN. CODE 61G1-16.003EACH
 ARCHITECTURAL PLAN SHEET SHALL BE SIGNED
 PERSONALLY, NOT SIGNATURE STAMPED.
  
 4) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 5) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 6) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING.
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 7 ) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 9) FBC 1403.9ELEVATION SHEETS A2-5.1 &
 A2-5.2.VINYL SIDING IS SPECIFIED IN
 NOTE 2.THE CODE LIMITS RIGID VINYL
 SIDING TO TYPE VI CONSTRUCTION ONLY.
 FROM TABLE 500, THE AREA OF THIS
 BUILDING EXCEEDS THE ACCEPTANCE CRITERIA
 FOR TYPE VI CONSTRUCTION.
  
 10) STRUCTURAL NOTES, SHEET STR-GN,
 STEEL ROOF JOISTS AND TRUSSES.SECTIONS
 A, B, H AND K ON SHEET S-2.03 STATE
 "...(SEE NOTES)" OR "...BY TRUSS
 ENGINEER"FOR ANCHORAGE TO THE CONCRETE
 TIE BEAM.THE PERMIT CANNOT BE ISSUED
 UNTIL THE REACTIONS ARE SPECIFIED ON THE
 PLANS FOR CROSS REFERENCE AGAINST THE
 PROPOSED ANCHORAGE.
  
 11) SHEET S-2.02NOTES 1 AND 2 ARE
 PRINTED IN A SMALL FONT SIZE AND ARE NOT
 LEGIBLE.
  
 12) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-10-02 Cont ID  
Sent By dpalmer Date 2003-10-02 Time 18:43 Rev Time 1.00
Received By dpalmer Date 2003-10-02 Time 18:43 Sent To  
Notes
2003-10-02 00:00:00************ UNSAT ******************
  
 THIS IS RESPONSE TO RESPONSE LETTER
 DATED 6/26/03
  
 PANEL 2LS/A HAS NOW BEEN CORRECTED.
 1)NOTE: PLEASE SEE CONDUCTORS SHOWN ON
 RISER DIAGRAM COMING FROM TRANSFORMER
 TO PANEL 2LS/A 4-1#8 ETC, CLARIFY SIZES
 INTO A 40A BRKR.
  
 2)NOTE: IT IS NOTED AND KNOWN THAT
 GENERATOR IS NOT IN A SEPARATE BLDG.
 THE NOTE AND CODES REFERENCE WAS FOR
 MEANS OF DISCONNECTING POWER COMING FROM
 GENERATOR TO THIS ACTIVITY BLDG.225.31
 PLEASE SEE THAT ATS APPEARS TO NOW SHOW
 A 400A MCB FOR THE MEANS OF DSIC.
 PLEASE SEE THAT THIS IS ON SECOND FLOOR
 AND NEEDS TO HAVE DISCONNECTING MEANS
 "GROUPED" WITH 2MDP.
 SHEET 3.01 IS NOW SUBMITTED AND THIS
 SHEET REFERENCES WHAT APPEARS TO BE
 TWO "SHUNT TRIP'S". PLEASE SEE THAT
 SHUNT TRIPS ARE NOT CONSIDERED TO BE
 "RATED" FOR THE LOAD SERVED. 230.76 AND
 230.79.
  
 3)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B). PLEASE SEE THAT WITH
 RESPECT TO DESIGN PROFESSIONAL(S) A
 4X FEE WILL BE ACCESSED FOR THE PORTION
 ATTRIBUTED TO PLAN REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-05-14 Cont ID  
Sent By dpalmer Date 2003-05-14 Time 07:29 Rev Time 3.00
Received By dpalmer Date 2003-05-14 Time 07:29 Sent To  
Notes
2003-05-14 00:00:00************* UNSAT **************
  
 **PLEASE NOTE, THIS IS THE THIRD REVIEW
 WITH SOME OF THE SAME COMMENTS NOT
 ADDRESSED? LETTER WAS ATTACHED IN REF.
 TO FS 553.80(2)(B) WITH RESPECT TO
 DESIGNERS OF RECORD.
  
 A RESPONSE LETTER FROM OCI DATED
 4TH FEBUARY 2003WAS FOUND IN SUBMITTAL
 PACKAGE. AN ELECTRICAL REVIEW WAS ALSO
 DONE ON 3/27/03 AND NOTES MENTIONS THAT
 NOTES FROM FIRST REVIEW DATED 11/26/02
 WERE NOT ADDRESSED.
 PLEASE SEE THE FOLLOWING AND NOTE, SOMES
 NOTES HAVE NOT BEEN ADDRESSED.
  
 1)NOTE: PLEASE SEE PANEL 2LS/A, SHOWN
 AS 277/480V? HOW IS THIS THE LOADSIDE
 OF A STEPDOWN TRANSFORMER BEING FED
 FROM 277/480V/120/208V?
  
 2)NOTE: PLEASE SEE RESPONSE FOR MEANS
 OF DISCONNECTING POWER FROM A ONE BLDG
 FEEDING TO ANOTHER. 225-31 A SHUNT TRIP
 HAS BEEN ADDED AT GENERATOR? THIS IS NOT
 A MEANS OF DISC FOR FEEDERS COMING TO
 MAIN BLDG? 225-31/230-76/230-79
 A RELATED NOTE: MEANS OF DISC FOR EM PWR
 FROM GENERATOR AT MAIN BLDG, NOT SHOWN.
 GROUPING OF DISC`S PER 230-72, RATING
 OF DISC FOR LOAD SERVED AND MANUAL MEANS
 REQ`D UNDER 230-76/230-79.
  
 3)NOTE: PLEASE SEE RESPONSE LETTER,
 A COUPLE OF THE RESPONSES MENTION TO
 SEE E-3.01 FOR DETAIL? PLEASE CLARIFY?
 THIS SHEET IS NOT IN SETS?
  
 PLEAS SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS FOR
 COMPLETE SETS FOR STAMPING AND REVIEW.
 ONCE AGAIN, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-27 Cont ID  
Sent By dpalmer Date 2003-03-27 Time 14:07 Rev Time 2.00
Received By dpalmer Date 2003-03-27 Time 14:07 Sent To  
Notes
2003-03-27 00:00:00************** UNSAT ****************
  
 1)NOTE: ORIG NOTES ASKED TO SHOW
 GROUNDING FOR TRANSFORMERS PER 250-30
 PLEASE CLARIFY WHERE THIS IS SHOWN?
 THERE IS ONLY A NOTE MENTIONING GROUND
 PER 250?
  
 2)NOTE: PLEASE CLARIFY GROUNDING ELEC-
 -TRODE SYSTEM, NOTE AT SERVICE SAYS TO
 SEE DETAIL ON E-3.01, PLEASE SEE THAT
 THIS SHEET WAS NOT SUBMITTED IN SET FOR
 REVIEW?
  
 3)NOTE: PLEASE SEE 230-76 AND 230-79 FOR
 MEANS OF DISC REQ`D. SHUNT TRIPS ARE NOT
 RATED FOR LOAD SERVED AND DO NOT COMPLY
 W/ 230-72. PLEASE HAVE A DISC MEANS FOR
 FEEDERS COMING TO BLDG/SEPARATE STUCTURE
 225-31 AND GROUPED PER 230-72/ 225-32
  
 4)NOTE: PLEASE SUBMIT/CLARIFY INFORMAT-
 ION REQUESTED ON PREVIOUS REVIEW FOR
 GENERATOR. SIZE /SPECS ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE MANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2002-11-26 Time 13:19 Rev Time 2.00
Received By dpalmer Date 2002-11-26 Time 13:19 Sent To  
Notes
2002-11-26 00:00:00****************** UNSAT **************
  
 PLEASE NOTE, THERE ARE MANY ITEMS ON
 RISER DIAGRAM AND PANEL SCHEDULES THAT
 ARE MISSING AND/OR DO NOT CORRELATE.
 PLEASE NOTE, A COMPLETE REVIEW CAN NOT
 BE ACCURATE AT THIS TIME.
  
 1)NOTE: PLEASE SEE 2MDP. SHOWN AS 100A
 MLO?
  
 2)NOTE: PLEASE NOTE, RISER DOES NOT
 SHOW HOW PANELS, 2EMF/A,2HLS/A,2EDP,
 ARE BEING FED FROM ON NORMAL POWER????
 RISER SHOWS THESE PANELS AND TRANSFOMER
 BEING ENERGIZED WHEN GENERATOR IS
 RUNNING> 215-5
  
 3)NOTE: PLEASE SHOW ALL GROUNDING FOR
 TRANSFORMERS PER 250-30.
  
 4)NOTE: PLEASE NOTE, MEANS OF DISC OF
 POWER COMING FROM GENERATOR TO BLDG.PER
 225-31. PLEASE NOTE, MEANS OF DISC TO
 BE GROUPED, 230-72,LABELED 230-2, RATING
 -S PER 230-76 AND 230-79.210-70 LOCAL
 AMENDMENTS.
  
 5)NOTE: PLEASE NOTE TAPPED CONDUCTORS
 FOR 2EMH/A AND 2KP. PLEASE NOTE BOTH
 PANELS HAVE NO MAINS. PLEASE ALSO SEE
 384-16 FOR LT AND APPL PANELS REQ`D TO
 HAVE MAINS.240-21
 PLEASE SEE PANEL SCHEDULE 2HLS/A NO
 LISTING FOR FEEDING TRANSFORMER TO
 2LS/A??
  
 6) NOTE: PLEASE NOTE, NO POWER SHOWN
 ON "NORMAL" LINE FOR ATS>
  
 7)NOTE: PLEASE NOTE, PLAN NOTE MENTIONS
 SEE GROUNDING DETAIL THIS SHEET?? PLEASE
 NOTE, NO DETAIL SHOWN.?? ALSO MENTIONS,
 TO BOND ALL SERVICES? PLEASE NOTE, ONLY
 ONE SHOWN??
  
 8)NOTE: PLEASE CLARIFY THAT MAIN IN
 2MDP MEETS 230-76/230-79.
  
 9)NOTE: PLEASE SUBMIT INFORMATION ON
 GENERATOR.SPECS ETC.
  
 10)NOTE: PLEASE NOTE LOADS SHOWN ON
 2MDP AND 2EDP DO NOT SEEM TO CALCULATED
 LOADS SHOWN ON PANEL SCHEDULE LOAD
 CALCS? PLEASE CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-06-25 Cont ID  
Sent By mamini Date 2003-06-25 Time 10:42 Rev Time 1.00
Received By mamini Date 2003-06-25 Time 10:42 Sent To  
Notes
2003-06-25 00:00:00PASSED:
 1. SEE PERMIT # 02102208 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-03-17 Cont ID  
Sent By mamini Date 2003-03-17 Time 10:44 Rev Time 1.00
Received By mamini Date 2003-03-17 Time 10:44 Sent To  
Notes
2003-03-17 00:00:00FAILED:
 1. SEE REVIEW COMMENTS, PERMIT #02102208
 DATED 03-17-03.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By mamini Date 2003-01-13 Time 09:05 Rev Time 0.00
Received By mamini Date 2003-01-13 Time 09:05 Sent To  
Notes
2003-01-13 00:00:00FAILED:
 1. SEE REVIEW COMMENTS FOR PLAN REVIEW #
 02102208.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-11-03 Cont ID  
Sent By nmccray Date 2003-11-03 Time 10:37 Rev Time 0.00
Received By nmccray Date 2003-11-03 Time 10:37 Sent To  
Notes
2003-11-03 00:00:00PLANS OK APPROVED ON 06-04-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-06-04 Cont ID  
Sent By nmccray Date 2003-06-04 Time 10:55 Rev Time 0.00
Received By nmccray Date 2003-06-04 Time 10:55 Sent To  
Notes
2003-06-04 00:00:00***************PROVISO******************
 SEPARATE PLANS AND PERMITS APPLICATION
 REQUIRED FOR HOOD SUPPRESSION SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-03-21 Cont ID  
Sent By mcarsill Date 2003-03-21 Time 10:27 Rev Time 0.00
Received By mcarsill Date 2003-03-21 Time 10:27 Sent To  
Notes
2003-03-21 00:00:001) EXITS PROVIDED FOR DINING ROOM 123
 DO NOT APPEAR TO BE PROPERLY
 SEPARATED FROM ONE ANOTHER.
  
 2) PLEASE EXPLAIN OPEN STAIR # 1.
  
 3) LIFE SAFETY PLAN DOES NOT INDICATE
 ANY EMERGENCY LIGHTS IN THE GALLERY,
 BATHROOMS,MEZZANINE LEVEL,STORAGE ROOM,
 AND DINING ROOM. THE ELECTRICAL PLAN
 SHOWS DIFFERENT INFORMATION. ARE NIGHT
 LIGHTS SHOWN ON THE ELECTRICAL PLAN
 THE SAME AS EMERGENCY LIGHTS.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD, DUCT AND EXTINGUISHING
 SYSTEMS PLANNED FOR INSTALLATION.
  
 5) REQUIRED DUCT SMOKE DETECTORS ARE
 TO BE CONNECTED TO THE BUILDING'S FIRE
 ALARM SYSTEM.
  
 6) IT APPEARS THAT SECURITY DEVICES ARE
 PRESENT ON EXIT DOORS. PLEASE REVIEW
 SPECIAL LOCKING ARRANGEMENTS OF THE 2000
 LIFE SAFETY CODE, SECTION 7. PLEASE
 PROVIDE APPROPRIATE CODE SECTIONS ON THE
 PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-23 Cont ID  
Sent By rbrown Date 2003-01-13 Time 17:18 Rev Time 0.00
Received By mcarsill Date 2003-01-23 Time 10:16 Sent To  
Notes
2003-01-23 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3) PLEASE PROVIDE A LIFE SAFETY PLAN
 FOR THE BUILDING.
  
 4) WHAT WILL THE MEZZANINE BE USED FOR.
  
 5) WHY IS STAIR # 1 OPEN.
  
 6) BUILDING ADDRESS REQUIRED.
  
 7) A KNOX-BOX WILL BE REQUIRED.
  
 8) PLEASE INDICATE HANDICAPPED SEATING.
  
 9) ONLY THREE LABELED FIRE DOORS ARE
 SHOWN ON DOOR SCHEDULE. PLEASE VERIFY
 THIS.
  
 10) COULD NOT LOCATE ANY EMERGENCY EXIT
 LIGHTS ON MEZZANINE LEVEL.
  
 11) NO SMOKE DETECTOR IN ELECTRICAL ROOM
 113, WHERE THE FACP IS LOCATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 11:29 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 11:29 Sent To  
Notes
2003-09-12 00:00:00COMM BD#42/PLANS ON RACK SHELF 4

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-05 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:33 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 09:04 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #12,PLANS NEXT TO CONF ROOM

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 08:57 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 08:57 Sent To B
Notes
2003-05-05 00:00:00RBROWN DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-01 Cont ID  
Sent By sthyng Date 2003-04-01 Time 10:54 Rev Time 0.00
Received By sthyng Date 2003-03-28 Time 10:54 Sent To P
Notes
2003-04-01 00:00:00HEALTH DEPT APPROVED PAGES - SENT
 TO KS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 08:48 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 08:48 Sent To  
Notes
2003-03-14 00:00:00COMM BOARD #46
 RACK, 1ST & 2ND SHELF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-10 Cont ID  
Sent By pkrauss Date 2003-05-10 Time 11:33 Rev Time 0.35
Received By pkrauss Date 2003-05-10 Time 11:33 Sent To  
Notes
2003-05-10 00:00:00MECHANICAL PERMIT 03050390
 REPLACED SHHET M2-2.01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-04 Cont ID  
Sent By pkrauss Date 2003-04-04 Time 09:41 Rev Time 2.00
Received By pkrauss Date 2003-04-04 Time 09:41 Sent To  
Notes
2003-04-04 00:00:00ADDITIONAL PERMITS REQUIRED:
  
 HOOD - PLAN SUBMITTED W/BUILDING PERMIT
 FIRE SUPPRESSION - PLANS SUBMITTED
 W/BUILDING PERMIT
 WALK-IN COOLER/FREEZER - PROVIDE
 MANUFACTURER SUBMITTAL DATA W/PERMIT
 APPLICATION.
  
 GREASE DUCT:
 1. MATERIALS SHALL COMPLY W/2001 FBC(M)
 506.3.3.
 2. 1/4" PER FT SLOPE PER FBC(M) 506.3.9.
 3. CLEARANCE TO COMBUSTIBLES SHALL BE NO
 LESS THAN 18" PER FBC(M) 507.9.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By pkrauss Date 2002-12-03 Time 10:17 Rev Time 3.45
Received By pkrauss Date 2002-12-03 Time 10:17 Sent To  
Notes
2002-12-03 00:00:00ACTIVITIES BUILDING #2
 DENIED:
  
 1) PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 2001 FBC(M) 501.4.
  
 2) PLANS ARE VAGUE AS TO ACCESS FOR THE
 EQUIPMENT LOCATED ON THE ROOF.PLAN
 SHEETS A2-7.1, A2-9.1, & ID-1 SHOW
 ACCESS TO THE EQUIPMENT LOCATED ON THE
 ROOF ABOVE THEKITCHEN/DINING AREA.
 CLARIFY ACCESS TO THE REST OF EQUIPMENT
 LOCATED ON THE OTHER ROOF AREAS.PLEASE
 NOTE, ACCESS TO EQUIPMENT LOCATED ON THE
 ROOF SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30".
  
 3) PLEASE NOTE, PLAN SHEET M2-5.01
 DETAIL #7, "COND. DRAINS SLOPE TO ROOF
 DRAIN OR DISCHARGE ON ROOF" - CONDENSATE
 SHALL NOT DISCHARGE ONTO THE ROOF.
  
 4) ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION & WALK-IN COOLER/FREEZER
  
 A) PROVIDE MANUFACTURER SUBMITTAL AND
 INSTALLATION INSTRUCTIONS FOR THE WALK
 IN COOLER & FREEZER WITH PERMIT THE
 PERMIT APPLICATION.
  
 B) PROVIDE SUBMITTAL DATA ON ANY FIRE
 WRAP OR SHAFTS (IF APPLICABLE) WITH
 PERMIT APPLICATION.
  
 C) AS PER NFPA 96 4-8.2.1 (E), A
 HINGED UPBLAST FAN WITH FLEXIBLE
 WEATHER PROOF ELECTRICAL CABLE SHALL
 BE USED. PLAN SHEET M2-5.02 INDICATES
 HIGNED FAN AS AN OPTION.
  
 D) AIR VELOCITY WITHIN THE DUCT SYSTEM
 SHALL BE NOT LESS THAN 1,500 FPM & NOT
 GREATER THAN 2,500 FPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-10-15 Cont ID  
Sent By kstevens Date 2003-10-15 Time 18:28 Rev Time 0.50
Received By kstevens Date 2003-10-15 Time 18:28 Sent To  
Notes
2003-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FLORIDA ADMIN. CODE
  
 1) PLANS STAMPED BY THE HEALTH DEPART-
 MENT SHALL BE SIGNED AND SEALED AND
 PLACED IN EACH SET OF PLANS IN THEIR
 PROPER ORDER. SECTION 104.2.2
 2) PREVIOUS COMMENT NOT ADDRESSED.
 CORRELATE PLANS FOR ROOF DRAINS AND
 ASSOCIATED PIPING. SHT P2-2.02 SHOWS ALL
 ROOF DRAINS AS 6". SHT P203.01 SHOWS 4"
 ROOF DRAIN AND 4" PIPING. SHT P2-4.3
 SHOWS A 4" ROOF DRAIN AND 6" PIPING.
 PLEASE CLAIRFY.
 3) ALL THREE SETS OF PLANS SHALL HAVE
 ALL SHEETS IN ORDER SIGNED, SEALED, DAT-
 ED, AND HAVE ALL INFORMATION REQUIRED IN
 TITLE BLOCK. SEE ATTACHED SHEETS FOR THE
 ARCHITECT AND ENGINEER. SECTIONS
 61G-15.002 AND 61G1-16.003/004
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-06-07 Cont ID  
Sent By kstevens Date 2003-06-07 Time 14:09 Rev Time 1.50
Received By kstevens Date 2003-06-07 Time 14:08 Sent To  
Notes
2003-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 ADMIN. CODE CHAPTER
 ONE & AMENDMENTS.
  
 1) PLANS NOT STAMPED BY THE PALM BEACH
 COUNTY DEPT.SEE PREVIOUS REVIEW COMMENTS
 2) SHT P2-02 SHOWS 6" RD.
 SHT P2-3.01 SHOWS 4" RD & 4" PIPING.
 SHT P2-4.03 SHOWS 6" RD & 6" PIPING.
 PLEASE CLAIRFY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-01 Cont ID  
Sent By sthyng Date 2003-04-01 Time 10:54 Rev Time 3.00
Received By kstevens Date 2003-03-28 Time 18:13 Sent To  
Notes
2003-03-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS FROM THE PALM BEACH CTY
 HEALTH DEPT ARE NOT SIGNED AND SEALED.
 PLEASE SIGN AND SEAL PLANS AND STAMP FOR
 HEALTH DEPT APPROVAL ONLY OR MAKE ALL
 CORRECTIONS REQUIRED FROM ALL PLAN
 REVIEWS AND INSERT THOSE SHEETS INTO
 EACH SET FOR REVIEW.
 2) SHT A2-2.2 ROOF CALCULATIONS, GUTTERS
 FOR ALL ROOFS. PLEASE PROVIDE HORIZONTAL
 DETAIL FOR GUTTER. SHOW SLOPE FOR EACH
 SECTION, (MIN. 2% PER TABLE 1106.6), AND
 SHOW HOW MUCH OF THE GUTTER IS DRAINED
 TO EACH DOWNSPOUT.
 3) SHT A2-2.2 PLEASE PROVIDE CALCULATION
 FOR LOWER ROOF NOT ADDRESSED. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING THE
 PARAPET WALLS. SHOW AREA FROM ROOF "B"
 THAT DRAINS ONTO LOWER ROOF IN CALCULAT-
 IONS. INDICATE HOW THE 2 SCUPPERS WILL
 DRAIN THE ROOF IN AN EMERGENCY.
 4) SHT P2-2.01 FROM PREVIOUS REVIEW,
 RESPONSE, (#6) INDICATES THAT A FLOOR
 SINK WAS PROVIDED, BUT THE DRAIN WAS
 DELETED ON REVISED SHEET P2-2.01. PLEASE
 CLAIRFY.
 5) EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. MANUAL AND
 UNION SHALL ALSO BE LOCATED BELOW CEIL-
 ING. MANUAL VALVE AND UNION SHALL BE
 BELOW CEILING ALSO
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-11 Cont ID  
Sent By kstevens Date 2002-12-11 Time 16:00 Rev Time 12.00
Received By kstevens Date 2002-12-11 Time 15:57 Sent To  
Notes
2002-12-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA ST W.P.B (561) 355-
 3018 PRIOR TO RESUBMITTING FOR PLAN RE-
 VIEW.
 2) PLEASE CONTACT RODNEY COMPO, ENVIRON-
 MENTAL COMPLIANCE @ (561) 837-4074 FOR
 SIZING OF GREASE TRAPS. WASTE ORDINANCE
 #2938-96
 3) SHT A2-2.2 ALL ROOF AREAS THAT HAVE
 PARAPET WALLS ON ALL SIDES SHALL HAVE A
 PRIMARY AND SECONDARY ROOF DRAIN. PLEASE
 SUBMIT CALCULATIONS FOR ALL ROOFS AND
 ALL PRIMARY AND SECONDARY DRAINS.
 3A) PLEASE SUBMIT DETAILS FOR ALL ROOF
 SCUPPERS, GIVE HEIGHT & WIDTH. SHOW DE-
 TAILS FOR ALL GUTTERS PER TABLE 1106.6,
 GIVE SIZE OF ALL GUTTERS.
 4) SHT K1.1 EQUIPMENT SCHEDULE, PLEASE
 SUBMIT MANUF. INFO. FOR WATER FILTER,
 ITEM #K6. SHALL BE "NSF" COMPLIANT.
 5) SHT KP1.4 PLUMBING LEGEND, ITEM P-11,
 SAFE WASTE NOT APPROVED. ALL INDIRECT
 WASTE TO DRAIN INTO A FLOOR SINK. SECT.
 802.3
 6) SHT P2-2.01 3" FUNNEL DRAIN NOT APP-
 ROVED. FLOOR SINK REQUIRED. (DINNING
 AREA)
 7) SHT P2-3.01 DETAIL B/P2-301, RAIN
 WATER RUNS FROM 8" TO 6" THEN BACK TO
 8" PIPE. PLEASE CLAIRFY.
 8) SHT P2-4.01 GREASE LINE (RISER), SAFE
 WASTE NOT APPROVED AT JANITOR SINK -
 FLOOR DRAIN. PLEASE TIE FLOOR DRAIN
 DOWN STREAM OF JANITOR SINK.
 9) SHT P2-4.01 GREASE LINE (RISER), FUN-
 NEL DRAIN NOT APPROVED, FLOOR SINK REQ-
 UIRED FOR ALL INDIRECT WASTE. 802.3
 10) SHT P2-4.01 AND SHT P2-2.01, DRAIN
 FROM THE DISHWASHER SHALL NOT DRAIN INTO
 GREASE LINE. PER UTILITY DEPT ALL DISH-
 WASHERS SHALL DRAIN TO SANITARY.
 11) SHT P2-4.02 WATER RISER DIAGRAM,
 BACKFLOW REQUIRED ON WATER SERVICE.
 ALL WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT AT THE TOP OF DROPS. PER
 PDI-WH 201 AND MANUFACTURE INSTRUCTIONS.
 12 FOLLOWING ARE COMMENTS RELATING TO
 THE GAS SYSTEM.
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 D) SOLENOID VALVE SHALL BE APPROVED FOR
 OUTDOOR USE. PLEASE SUBMIT MANUFACTURE
 INFORMATION AND INSTALLATION INSTRUCTION
 A SHUT OFF VALVE AND UNION ARE REQUIRED
 UPSTREAM OF THE SOLENOID VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-06 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:33 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By sgraham Date 2003-01-13 Time 10:26 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-13 00:00:00DENIED, NEED MINOR AMENDMENT AND THE
 PLAT NEED TO BE RECORDED


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved