Plan Review Details - Permit 02102198
Plan Review Stops For Permit 02102198
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-02-25 Cont ID  
Sent By rbrown Date 2005-02-25 Time 10:38 Rev Time 0.00
Received By rbrown Date 2005-02-25 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-03-04 Cont ID  
Sent By rbrown Date 2004-03-04 Time 09:02 Rev Time 0.00
Received By rbrown Date 2004-03-04 Time 09:02 Sent To  
Notes
2004-03-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 61G1-16.004FL. ADMIN. CODE.ADD, TO
 EACH ARCHITECTURAL SHEET, THE PRINTED
 NAME AND LICENSE NUMBER OF JORGE GARCIA
 AS THE ARCHITECT WHO SEALED THE PLANS.
 THIS MAY BE DONE BY STAMP OR HANDWRITTEN
  
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-09-30 Cont ID  
Sent By rbrown Date 2003-09-30 Time 19:31 Rev Time 0.00
Received By rbrown Date 2003-09-30 Time 19:31 Sent To  
Notes
2003-09-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/3/03:
  
 3) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 4) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 6) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, ON SHEET 1, COMPLETE THE
 PROJECT DETAILS INCLUDING NAME OF OWNER,
 PROJECT ADDRESS (4884 N. HAVERHILL RD),
 ZIP (33417) AND PERMIT NUMBER (02102198)
  
 7) PRODUCT APPROVALS.THE PRODUCT
 APPROVAL SHEETS SHALL BE MARKED, AS
 APPROPRIATE TO IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS/SIZES ARE TO BE USED,
 ALSO:
 (I) DRAWING SHEET 1 OF THE SUBMITTED PGT
 INDUSTRIES ALUMINUM FIXED WINDOW PRODUCT
 APPROVAL NOA# 01-0102.01 STATES THAT THE
 DESIGN PRESSURE RATING OF THE IMPACT
 WINDOWS, WITH HEAT STRENGTHENED
 LAMINATED GLASS, IS +60 PSF & -60 PSF.
 THIS IS EXCEEDED BY THE MAXIMUM NEGATIVE
 DESIGN PRESSURE (-76 PSF) STATED ON PLAN
 SHEETS A1-5.1 AND A1-5.2 (ELEVATIONS).
 SUBMIT A PRODUCT APPROVAL WITH THE
 APPROPRIATE DESIGN PRESSURE RATING.
 (J) SUBMIT A PRODUCT APPROVAL FOR THE
 GLAZED SLIDING DOORS TO THE GUARD HOUSE.
  
 --PROVISO--
 THE SUBMITTED ARCH ALUMINUM NARROW STILE
 DOOR PRODUCT APPROVAL NOA# 01-0910.09
 STATES THAT THESE DOORS ARE NOT IMPACT
 RESISTANT.SUBMIT A PRODUCT APPROVAL
 FOR HURRICANE MISSILE IMPACT PROTECTION
 SHUTTERS IF THESE DOORS ARE TO USED.
  
 --PROVISO--
 THE SUBMITTED ARCH ALUMINUM SERIES 4500
 STOREFRONT PRODUCT APPROVAL
 NOA# 00-1220.05 STATES THAT THIS SYSTEM
 IS NOT IMPACT RESISTANT.SUBMIT A
 PRODUCT APPROVAL FOR HURRICANE MISSILE
 IMPACT PROTECTION SHUTTERS IF THIS
 SYSTEM IS TO BE USED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-06-03 Cont ID  
Sent By rbrown Date 2003-06-03 Time 11:15 Rev Time 0.00
Received By rbrown Date 2003-06-03 Time 11:15 Sent To  
Notes
2003-06-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/8/03 AND 4/24/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4SITE SURVEY.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES).THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???).
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING AND THE BUS
 STOP.ACCEPTABILITY OF THIS PERMIT
 APPLICATION IS CONTINGENT UPON THE
 CIVIL/SITE PLANS, UNDER PERMIT 02102208,
 BEING PERMITTED.
  
 6) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, THE ARCHITECT'S NAME AND
 REGISTRATION NUMBER SHALL BE ADDED ABOVE
 THOSE OF THE OTHER SYSTEM DESIGNERS.ON
 SHEET 1, COMPLETE THE PROJECT DETAILS
 INCLUDING NAME OF OWNER, PROJECT ADDRESS
 (4884 N. HAVERHILL RD), ZIP (33417)
 AND PERMIT NUMBER (02102198).
  
 7) PRODUCT APPROVALS.THE PRODUCT
 APPROVAL SHEETS SHALL BE MARKED, AS
 APPROPRIATE TO IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS ARE TO BE USED, ALSO:
 (A) THE SUBMITTED COPIES OF TIMBERLINE
 SELECT 40 ASPHALT SHINGLE PRODUCT
 APPROVAL NOA# 03-0219.08 IS MISSING
 SHEET 3 OF 3.ALSO, SHEET 2 IS A POOR
 COPY.SUBMIT TWO COPIES OF A COMPLETE
 AND LEGIBLE PRODUCT APPROVAL.
 (G) THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM NARROW STILE
 DOOR PRODUCT APPROVAL NOA# 01-0910.09
 ARE POORLY REPRODUCED.SUBMIT LEGIBLE
 COPIES.NOTE THAT THESE DOORS ARE NOT
 IMPACT RESISTANT, AND WILL REQUIRE THE
 INSTALLATION OF HURRICANE SHUTTERS.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (H) THE SUBMITTED ARCH ALUMINUM SERIES
 4500 STOREFRONT PRODUCT APPROVAL NOA#
 00-1220.05 IS FOR A NON-IMPACT RATED
 SYSTEM.THE INSTALLATION OF HURRICANE
 MISSILE IMPACT PROTECTION SHUTTERS WILL
 BE REQUIRED.THE PLANS SHALL IDENTIFY
 WHERE THIS SYSTEM IS TO BE USED AND A
 HURRICANE MISSILE IMPACT PROTECTION
 SHUTTER PRODUCT APPROVAL SHALL BE
 SUBMITTED.THE PRODUCT APPROVAL SHEETS
 SHALL BE MARKED, AS APPROPRIATE TO
 IDENTIFY WHICH PRODUCT OPTIONS/MATERIALS
 ARE TO BE USED.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-23 Cont ID  
Sent By rbrown Date 2003-04-23 Time 19:14 Rev Time 0.00
Received By rbrown Date 2003-04-23 Time 19:14 Sent To  
Notes
2003-04-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/8/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4SITE SURVEY.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES.). THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???).
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) THE GBS ARCHITECURE RESPONSE IS NOTED
 FBC 11-4.1.2 THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING AND BUS STOP
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED,
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) PRODUCT APPROVALS: DOOR, WINDOW, ROOF
 (A) ASPHALT SHINGLE PRODUCT APPROVAL
 NOA# 00-0105.02 EXPIRED ON 4/22/03.
 SUBMIT A VALID PRODUCT APPROVAL.
 (B) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. 98/99 RIM EXIT STEEL DOOR PRODUCT
 APPROVAL NOA# 01-1203.11 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (C) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. F, M FRAME STEEL DOOR PRODUCT
 APPROVAL NOA# 01-0129.12 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (D) NOT USED
 (E) THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM STOREFRONT DOOR
 PRODUCT APPR. NOA# 01-0919.02 ARE POORLY
 REPRODUCED.SUBMIT LEGIBLE COPIES.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (F) THE SUBMITTED 2 PAGE COPY EXTRACT OF
 THE 48 PAGE GAF MODIFIED BITUMEN ROOF
 PRODUCT APPROVAL NOA# 00-0331.09 DOES
 NOT INCLUDE A STATEMENT OF THE MAXIMUM
 DESIGN PRESSURE AND STATES THAT "ALL
 GENERAL AND SYSTEM LIMITATIONS SHALL
 APPLY".SUBMIT COPIES OF THE SHEETS
 WHICH STATE THE GENERAL AND SYSTEM
 LIMITATIONS AND THE MAX DESIGN PRESSURE.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
  
 9) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING.
 CONTRARY TO THE G.D. KLIEGER RESPONSE,
 THE ARCHITECTURAL PLANS SPECIFY PLYWOOD.
 DETAIL 6/A1-8.1 MAKES SPECIFIC REFERENCE
 TO "STRUCTURAL DRAWINGS FOR ATTACHMENT/
 NAILING PATTERN".AMEND THE THE NOTES
 AS DESCRIBED IN COMMENT #8 UNDER PERMIT#
 02102206 (FOR BUILDING 5, EDUCATIONAL).
  
 10) INFORMATIVE:
 WOOD TRUSSES.G.D KLIEGER RESPONSE IS
 NOTED.THE COMMENT WAS ORIGINALLY MADE
 WHEN THE ARCHITECTURAL PLANS (NOTE 22 ON
 SHEETS A1-7.1, A1-9.1 AND 9.2) STILL
 MADE REFERENCE TO WOOD TRUSSES. ALL
 STRUCTURAL SHOP DRAWINGS SHALL BE
 REVIEWED AND STAMPED BY THE ENGINEER OF
 RECORD PRIOR TO SUBMITTAL TO WPB
 CONSTRUCTION SERVICES DEPT.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-08 Cont ID  
Sent By rbrown Date 2003-01-08 Time 16:15 Rev Time 0.00
Received By rbrown Date 2003-01-08 Time 16:15 Sent To  
Notes
2003-01-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 2) FL. ADMIN. CODE 61G1-16.003EACH
 ARCHITECTURAL PLAN SHEET SHALL BE SIGNED
 PERSONALLY, NOT SIGNATURE STAMPED.
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING.
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 8) FBC 1403.9ELEVATION SHEETS A1-5.1 &
 A1-5.2.4" VINYL SIDING IS SPECIFIED IN
 NOTE 2.RIGID VINYL SIDING IS LIMITED
 TO TYPE VI CONSTRUCTION.FROM TABLE 500
 THE AREA OF THIS BUILDING EXCEEDS THE
 ACCEPTANCE CRITERIA FOR TYPE VI
 CONSTRUCTION.
  
 9) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING.THE
 PERIMETER ZONE AT THE GABLE ENDS SHALL
 HAVE NAILS SPACED AT 4"O.C. MAXIMUM, TO
 A DISTANCE OF 5 FEET (NOT 24") FROM THE
 EDGE OF THE ROOF.
  
 10) STRUCTURAL NOTES, SHEET STR-GN, WOOD
 TRUSS NOTE 6.IT IS NOTED THAT THE
 TRUSS DESIGN ENGINEER IS TO PROVIDE THE
 WIND UPLIFT REACTIONS.THE PERMIT
 CANNOT BE ISSUED UNTIL THE REACTIONS ARE
 SPECIFIED ON THE PLANS FOR CROSS
 REFERENCE AGAINST THE PROPOSED TRUSS
 ANCHORS AND STRAPS.
  
 11) FBC 11-4.9.4(2)SHEET A1-8.1, TYP.
 SIDE WALL RAILING DETAIL (ALSO SHEET
 A1-9.1 STAIR 109/209 SECTION).THE
 HANDRAIL SHALL EXTEND AT LEAST 12"
 HORIZONTALLY BEYOND THE TOP RISER, AND
 SHALL CONTINUE TO SLOPE PAST THE BOTTOM
 RISER FOR A DISTANCE EQUAL TO THE WIDTH
 OF ONE TREAD AND THEN A FURTHER 12"
 HORIZONTALLY AT THE BOTTOM.
  
 12) FBC 11-4.13.6MANEUVERING CLEARANCE
 AT DOORS.THE LEADING EDGE OF DOOR 202B
 SHOULD BE NO LESS THAN 18" AWAY FROM THE
 CORRIDOR WALL ON THE PULL SIDE OF THE
 DOOR.
  
 13) FBC 11-4.16.3SHEET A1-2.41, DETAIL
 5A AND SHEET A1-4.1, DETAIL 2A, 2B, 4A.
 THE HEIGHT OF THE W.C. SEAT SHOULD BE
 17" TO 19", NOT 1'-3".
  
 14) FBC 2405.2THE GLAZED PANEL AT HR
 RECEPTION IS WITHIN 24" OF DOOR 103.
 THIS IS A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-02-28 Cont ID  
Sent By dpalmer Date 2005-02-28 Time 06:31 Rev Time 0.20
Received By dpalmer Date 2005-02-28 Time 06:23 Sent To  
Notes
2005-02-28 00:00:00****** PROVISO *********
  
  
  
 PURSUANT TO DECISION BY THE AHJ AND
 BUILDING OFFICAL, ALL ELECTRICAL WORK TO
 BE PERFORMED UNDER THE 2002 NEC.
 PLANS ARE TO BE REVISED BEFORE ROUGH FOR
 ANY CHANGES AFFECTING DESIGN.
  
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-03-02 Cont ID  
Sent By dpalmer Date 2004-03-02 Time 08:40 Rev Time 0.50
Received By dpalmer Date 2004-03-02 Time 08:40 Sent To  
Notes
2004-03-02 00:00:00** UNSAT **
  
 1)NOTE: PLEASE INCLUDE NAME, LICENSE#
 AND CERTIFICATE OF AUTHORIZATION # ON
 TITLE BLOCK(S). THIS IS REQ'D ON ALL
 SHEETS AND FOR ALL TRADES.
 PLEASE SEE FAC 61G15-23.002, FS 471.023
 THIS MAY BE HAND WRITTEN ON ALL SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-02 Cont ID  
Sent By dpalmer Date 2003-10-02 Time 18:07 Rev Time 0.50
Received By dpalmer Date 2003-10-02 Time 18:07 Sent To  
Notes
2003-10-02 00:00:00PLANS OK AND STAMPED 5-15-03
 NO RESUBMITTIAL SHEET FOUND TO SIGN OFF.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-15 Cont ID  
Sent By dpalmer Date 2003-05-15 Time 08:39 Rev Time 1.00
Received By dpalmer Date 2003-05-15 Time 08:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-27 Cont ID  
Sent By dpalmer Date 2003-03-27 Time 16:37 Rev Time 2.00
Received By dpalmer Date 2003-03-27 Time 16:37 Sent To  
Notes
2003-03-27 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM. IT IS NOTED ON RISER THAT
 GROUNDIGN ELECTRODE DETAIL IS ON SHEET
 E3.01? PLEASE NOTE, NO SHEET 3.01 WAS
 SUBMITTED FOR REVIEW.?
 PLEASE ALSO SHOW GROUNDING DETAIL OR
 NOTED WHERE TRANSFORMERS WILL BE
 ATTACHED? BLDG STEEL/FOOTER? 250-30
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2002-11-26 Time 05:47 Rev Time 2.00
Received By dpalmer Date 2002-11-25 Time 16:47 Sent To  
Notes
2002-11-26 00:00:00****************UNSAT **************
  
 1)NOTE: PLEASE SHOW LOCATION OF SERVICE/
 1MDP.SHOWN ON RISER IN RM 126??
 PLEASE NOTE, THIS IS CLARIFY DISTANCE
 FROM MDP TO PRIMARY SIDE OF TRANSFORMERS
 PLANS/LINE DIAGRAM DOES NOT SHOW HOW FAR
 AWAY.? TAPPED CONDUCTORS 240-21
  
 2)NOTE: PLEASE CLARIFY PANEL SCHEDULE
 FOR 1L/B? PLEASE NOTE THERE IS ANOTHER
 PANEL SCHEDULE SHOWN. MISPRINT?
  
 3)NOTE: PLEASE NOTE, RISER DIAGRAM SHOWS
 THE "GUARDHOUSE" PANEL AS 120/240V AND
 BEING FROM MDP WHICH IS 277/480V?
 PLEASE CLARIFY.
  
 4)NOTE: PLEASE SHOW GROUNDING ATTHE
 DEATCHED "GH". PER 250-32
  
 5)NOTE: PLEASE SHOW LOCATIONS FOR
 GROUNDING OF TRANSFORMERS PER 250-30.
  
 6)NOTE: PLEASE SEE NOTE GROUNDING
 ELECTRODE SYSTEM BELOW MDP, NOTE MENTION
 -S, "SEE GROUNDING DETAIL THIS SHEET"??
 PLEASE CLARIFY WHERE THIS DEATIL CAN BE
 FOUND. ALSO MENTIONS "ALL SERVICES TO
 BE BONDED TOGETHER? PLEASE NOTE, ONLY
 ONE SERVICE IS SHOWN. ??
  
 7)NOTE: PLEASE CLARIFY THE MDP HAS
 A MCB THE MEETS 230-76 AND 230-79.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-06-25 Cont ID  
Sent By mamini Date 2003-06-25 Time 10:39 Rev Time 1.00
Received By mamini Date 2003-06-25 Time 10:39 Sent To  
Notes
2003-06-25 00:00:00PASSED :
 1. SEE PERMIT # 02102208 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-03-17 Cont ID  
Sent By mamini Date 2003-03-17 Time 10:37 Rev Time 1.00
Received By mamini Date 2003-03-17 Time 10:36 Sent To  
Notes
2003-03-17 00:00:00FAILED:
 1. SEE REVIEW COMMENTS, PERMIT #02102208
 DATED 03-17-03.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By mamini Date 2002-11-06 Time 15:28 Rev Time 0.00
Received By mamini Date 2002-11-06 Time 15:28 Sent To  
Notes
2002-11-06 00:00:00FAILED:
 1. SEE REVIEW COMMENTS FOR PLAN REVIEW #
 02102208.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-11-03 Cont ID  
Sent By nmccray Date 2003-11-03 Time 10:31 Rev Time 0.00
Received By nmccray Date 2003-11-03 Time 10:31 Sent To  
Notes
2003-11-03 00:00:00PLANS OK APPROVED ON 04-24-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By nmccray Date 2003-04-24 Time 11:07 Rev Time 0.00
Received By nmccray Date 2003-04-24 Time 11:07 Sent To  
Notes
2003-04-24 00:00:00***********PROVISO**********************
 1) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-04 Cont ID  
Sent By mcarsill Date 2002-12-04 Time 17:38 Rev Time 0.00
Received By mcarsill Date 2002-12-04 Time 17:38 Sent To  
Notes
2002-12-04 00:00:001) BUILDING ADDRESS REQUIRED.
  
 2) ELEVATOR ROOM DOOR APPEARS TO
 SWING TOO FAR INTO CORRIDOR 149.
  
 3) AGAIN WILL GUARD HOUSE BE STAFFED
 FULL TIME.
  
 4) ALL SHAFTWAYS IN WHICH ARE LARGE
 ENOUGH FOR PERSONS TO FALL INTO
 MUST BE MARKED SHAFTWAY MUST BE MARKED
 SHAFTWAY IN SIX INCH HIGH LETTERS WITH
 A WHITE BACKGROUND.
  
 5) PLEASE PROVIDE THIS OFFICE WITH
 A LIFE SAFETY PLAN INDICATING OCCUPANT
 LOADS, TRAVEL DISTANCES, ETC.
  
 6) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-24 Cont ID  
Sent By rbrown Date 2005-02-03 Time 08:48 Rev Time 0.00
Received By rbrown Date 2005-02-03 Time 08:48 Sent To  
Notes
2005-02-24 00:00:00PLANS ON RACK (COMMERCIAL BOARD #17)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:54 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 15:54 Sent To  
Notes
2004-02-06 00:00:00TO COMM BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:33 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 09:08 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #12,PLANS NEXT TO CONF ROOM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 08:51 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 08:51 Sent To  
Notes
2003-03-14 00:00:00COMM BOARD #46
 PLANS ON RACK, 1ST & 2ND SHELF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-10 Cont ID  
Sent By pkrauss Date 2003-05-10 Time 12:05 Rev Time 0.35
Received By pkrauss Date 2003-05-10 Time 11:40 Sent To  
Notes
2003-05-10 00:00:00MECHANICAL PERMIT 03050133

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-04-03 Cont ID  
Sent By pkrauss Date 2003-04-03 Time 13:04 Rev Time 0.45
Received By pkrauss Date 2003-04-03 Time 13:02 Sent To  
Notes
2003-04-03 00:00:00PLEASE CLARIFY "SHAFTWAY" INDICATED ON
 PLAN SHEET A1-2.21.DOES THIS HAVE
 A "RATING"?PLEASE NOTE, EXHAUST DUCT
 IN "SHAFTWAY" SHALL COMPLY WITH 2001
 FBC(M) 607.1.2 #1 OR 2.
  
 PLEASE PROVIDE OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By pkrauss Date 2002-12-03 Time 14:33 Rev Time 1.00
Received By pkrauss Date 2002-12-03 Time 14:33 Sent To  
Notes
2002-12-03 00:00:00ADMINISTRATION BUILDING #1
 DENIED:
  
 1) PLAN SHEET M1-2.02 HVAC KEYNOTES #6,
 "ROUTE 3/4" CONDENSATE DRAIN TERMINATE
 AT RAIN LEADER."CONDENSATE SHALL BE
 TO A DEDICATED LINE & TERMINATE INTO
 STORM OUTSIDE OF BUILDING.PLEASE
 CLARIFY.
  
 2) FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS OR A SUPER-
 VISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.NFPA 90A 4-4.4.3 & 4-4.4.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-07 Cont ID  
Sent By kstevens Date 2003-06-07 Time 14:31 Rev Time 0.33
Received By kstevens Date 2003-06-07 Time 14:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-28 Cont ID  
Sent By kstevens Date 2003-03-28 Time 15:31 Rev Time 0.50
Received By kstevens Date 2003-03-28 Time 15:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By kstevens Date 2002-12-03 Time 10:54 Rev Time 3.50
Received By kstevens Date 2002-12-02 Time 18:52 Sent To  
Notes
2002-12-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1-4.1 DETAIL #1 SHOWS 5'2" WIDTH
 FOR TOILET ROOM AND STALL. MINIMUM 5'3"
 IS REQUIRED FOR BOTH.
 2) SHT A1-4.2 DETAIL #10A BREAK ROOM
 SINK SHALL COMPLY WITH SECTION 11-4.24,
 AND ALL SUBSECTIONS. PLEASE SHOW ON DE-
 TAIL KNEE CLEARANCE, CLEAR FLOOR SPACE,
 ECT.
 3) SHT A1-4.3 DETAILS #5 & 9, PLEASE
 SHOW CLEAR FLOOR SPACE. IF FRONTAL APP-
 ROACH SHOW DETAILS FOR COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. IF
 PARALLEL APPROACH, SHOW ON PLANS. SINK
 TO BE CENTERED ON 48".
 4) SHTS P1-2.02 & P1-3.01 ICE MAKER
 DRAIN, 2ND FLOOR PLUMBING PLAN AND SANT.
 RISER DIAGRAM, ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOOR SINK. SEC 802.3
 5) SHT P1-3.02 BACKFLOW REQUIRED ON
 WATER SERVICE TO ADMIN. BLDG.
 6) SHT P1-3.02 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS REQUIRED BY SEC.
 604.9 SHALL BE LOCATED NEAR FIXTURES IN
 AN "EFFECTIVE RANGE" NOT AT TOP OF DROP
 AS SHOWN FOR 1ST FLOOR. PER PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS.
 7) SHT P1-4.01 WATER HEATER DETAIL/WATER
 HEATER SCHEDULE. W/H DETAIL SHOWN P/T &
 PAN DRAIN DRAINING TO JANITOR SINK, BUT
 W/H SCHEDULE SHOWS P/T & PAN DRAIN DRAIN
 ING INTO FLOOR DRAIN. (NOT APPROVED)
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-06 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:33 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By sgraham Date 2003-01-13 Time 11:25 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-13 00:00:00DENIED, NEED MINOR AMENDMENT AND THE
 PLAT NEED TO BE RECORDED