Plan Review Details - Permit 02102193
Plan Review Stops For Permit 02102193
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 10:54 Rev Time 0.50
Received By dpalmer Date 2003-02-07 Time 10:54 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-30 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 10:04 Rev Time 0.75
Received By dpalmer Date 2002-12-30 Time 07:24 Sent To B
Notes
2002-12-30 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY GROUPING OF MAINS
 PER 230-72. METER ONLY SHOWSONE MAIN
 NEXT TO IT.
  
 2)NOTE: PLEASE NOTE PANELS ARE SHOWN AS
 200MCBAND RISER SHOWS AS 150A MLO?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE MISSING FOOTER STEEL
 PER 250-50
  
 4)NOTE: PLEASE CLARIFY PADDLE FANS
 SHOWN OFF PANEL SCHEDULE.
  
 5)NOTE: PLEASE RE-CONFIGURE LOAD
 CALCULATIONS, PLEASE NOTE #`S DO NOT
 CORRELATE W/ SUBMITTED PANEL SCHEDULES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-28 Cont ID  
Sent By alange Date 2003-07-28 Time 11:04 Rev Time 0.00
Received By alange Date 2003-07-28 Time 11:04 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 10:04 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 10:04 Sent To E
Notes
2003-02-06 00:00:00TO DVP'`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2003-01-30 Time 14:06 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-14 Cont ID  
Sent By dpalmer Date 2002-11-14 Time 16:21 Rev Time 0.00
Received By dpalmer Date 2002-11-14 Time 16:21 Sent To Z
Notes
2002-11-14 00:00:00RESUBBED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 13:00 Rev Time 0.00
Received By dpalmer Date 2002-10-31 Time 13:00 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By jleech Date 2002-12-28 Time 11:14 Rev Time 0.50
Received By hmoser Date 2002-12-28 Time 13:12 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By alange Date 2003-07-28 Time 11:04 Rev Time 0.33
Received By jleech Date 2002-12-28 Time 11:14 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By jgomez Date 2003-02-07 Time 17:18 Rev Time 3.50
Received By jgomez Date 2003-02-07 Time 17:18 Sent To  
Notes
2003-02-07 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-PROVIDE COMPLETE DETAIL/SPECIFICATIONS
 FOR INSTALLATION OF CEILINGS AT FRONT
 & REAR PORCHES. SEE ASTM C926 AND ASTM
 C1063 FOR FASTENER SIZE & SPACING.
 SECTION 2504.2 FBC 2001.
 3-BEFORE INSTALLATION PROVIDE PRODUCT
 APPROVAL FOR: A)ENTRY DOORS PRODUCT
 APPROVAL NEED DRAWINGS W/ DADE COUNTY
 STAMP WITH NEW RENEWAL NUMBER. ALSO,
 FRONT PAGE REPORT NEEDS DADE COUNTY
 LOGO AT BOTTOM LEFT OF PAGE AS REQ'D
 BY DADE COUNTY FOR FINAL REPORTS.
 B)STOREFRONT SYSTEM AND FIXED WINDOWS
 SITE SPECIFIC ENGINEERING NEED TO BE
 SIGNED, SEALED AND DATED BY ARCHITECT
 (PROFESSIONAL OF RECORD) AS REQUIRED
 BY THE BUILDING OFFICIAL.
 **ALSO: MAKE SURE INSTALLATION MATCHES
 ARCHITECTURAL PLANS. EG: FIXED WINDOWS
 CALL FOR CONCRETE SILL BEAM, BUT THERE
 IS NOT CONCRETE SILL. SEE PLANS.
 **ALSO: ENGINEER TO REVISE ORIGINAL
 DRAWINGS AS REQUIRED. THERE ARE SOME
 REDLINES DRAWN ON STOREFRONT SYSTEM
 DRAWINGS WHICH INVALIDATES SUCH DWGS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2003-01-02 Cont ID  
Sent By jgomez Date 2002-12-31 Time 16:32 Rev Time 5.00
Received By jgomez Date 2002-12-31 Time 16:32 Sent To  
Notes
2002-12-31 00:00:00CHECKLIST:
 1-ARCHITECT TO PROVIDE ALL INFORMATION
 REQUIRED BY SECTION 1606.1.7 FBC 2001.
 (NOTE: NEED TO LIST ALL 5 ITEMS)
 2-PROVIDE AT LEAST ONE COMPLETE BATHROOM
 WITH A DOOR THAT ALLOWS 29" MIN. CLEAR
 OPENING. SEC. 11-11 FBC 2001.
 3-CLARIFY SIZE OF BEDROOM EGRESS WINDOWS
 WHAT IS A SH2853 AS CALLED ON FLOOR
 PLANS. CLARIFY/REVISE AS REQUIRED. SEE
 PLANS, RIGHT ELEVATION.
 4-SPECIFY IN PLANS ALL AREAS TO HAVE
 SAFETY GLASS AS REQUIRED BY SECTION
 2405.2 FBC 2001. ALSO, SAFETY GLASS TO
 PASS TEST REQUIREMENTS OF SECTION
 2405.1 FBC 2001.
 5-SIZE OF DOORS & WINDOWS CALLED ON PLAN
 DON'T MATCH SIZE SHOWN ON PLANS AND
 ELEVATIONS. EG: SEE SIZE SPECIFIED FOR
 SLIDING GLASS DOORS AT REAR ELEVATION.
 **NOTE: ALSO, SEE SITE SPECIFIC ENGINEE-
 RING INFORMATION FOR FIXED WINDOWS AND
 REVISE DRAWINGS AS REQUIRED TO MATCH
 THOSE. EG: HER BATH SHOWS BUTT GLAZING
 AND PRODUCT APPROVAL SHOWS STRUCTURAL
 MULLIONS. WHICH ONE IS CORRECT?
 6-REVISE DETAIL 11 OF SHEET A9 TO MATCH
 FIREPLACE CONSTRUCTION SHOWN ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 **NOTE: SPECIFY ON EXTERIOR ELEVATIONS
 THE MIN. CHIMNEY HEIGHTS REQUIRED BY
 SEC. 2804.2.4 FBC 2001.
 7-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305.1.4 FBC 2001.
 8-SPECIFY SUPPORTS FOR WWM IN CONCRETE
 SLAB AS REQUIRED BY SEC. 1090.3 FBC.
 9-PROVIDE COMPLETE DETAILS/SPECS FOR
 INSTALLATION OF CEILINGS AT FRONT AND
 REAR PORCHES. SPECIFY ALL FASTENERS &
 SPACING. SEE ASTM C926 AND ASTM C-1063
 AS REQUIRED BY SEC. 2504.2 FBC 2001.
 10-REVISE STRUCTURAL BUCK FOR SWING DOOR
 SEE SEC. 1707.4.4.2 FBC 2001.
 11-NEED RECORDED NOTICE OF COMMENCEMENT.
 12-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS ASSEMBLY AS SHOWN ON PLANS
 B)STOREFRONT GLAZING SYSTEM: ARCHITECT
 TO SIGN, SEAL & DATE SITE SPECIFIC
 FORM AS WELL. PROVIDE HIS INFORMATION
 AS REQUIRED BY CHAPTER 481 FL STATUTES
 AND IDENTIFY THE JOB SITE.
 **ALSO, PROVIDE THE PRODUCT APPROVAL #
 00-1220.5 FOR STOREFRONT SYSTEMS AS
 REFERENCED ON THIS FORM.
 C)SITE SPECIFIC FIXED WINDOWS PRODUCT
 APPROVAL NEEDS TO BE SIGNED, SEALED
 AND DATE BY ARCHITECT AS WELL. PROVIDE
 HIS INFORMATION AND IDENTIFY JOB SITE.
 D)GARAGE DOORS PRODUCT APPROVAL NEED
 LEGIBLE APPROVED DRAWINGS.
  
 13-PROVIDE COMPLETE INFO. FOR STORM SHU-
 TTERS OR APPLY FOR A SEPARATE PERMIT.
 CITY IMPLEMENTATION STANDARD FOR HURRI
 CANE MISSILE IMPACT PROTECTION.
 14-LIBRARY ROOM MAY BE USED AS SLEEPING
 ROOM. NEED TO PROVIDE EGRESS WINDOW OR
 AS PER CITY BUILDING OFFICIAL INTERPRE
 TATION CLEARLY WRITE ON PLANS THAT
 THIS ROOM SHALL NOT BE USED FOR
 SLEEPING PURPOSES.
 15-SEE PLANS FOR ADDITIONAL COMMENTS AND
 PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE TO THE ORIGINAL
 CAD DRAWINGS TO EXPEDITE THE REVIEW.
 ALSO, RETURN DWGS THAT ARE ALREADY
 STAMPED AND APPROVED TO AVOID SENDING
 DWGS BACK AND FORTH TO OTHER TRADES.

Review Stop Z ZONING
Rev No 3 Status P Date 2003-02-05 Cont ID  
Sent By sgraham Date 2003-02-05 Time 11:14 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-01-02 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2003-01-02 00:00:00DENIED, CHIMNEY FLUKE STILL OVER THE
 ALLOWED HEIGHT

Review Stop Z ZONING
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By dpalmer Date 2002-11-14 Time 16:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
2002-11-06 00:00:00DENIED MAX HEIGHT IS 30' & 10% TOTAL
 IS 33' NOT 36' OR 35'


Account Summary | Usage Policy | Privacy Policy