Plan Review Details - Permit 02102015
| Plan Review Stops For Permit 02102015 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-11-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-18 |
Time |
10:59 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-11-18 00:00:00 | APPROVED BY N. MCCRAY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-11-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-31 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-31 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2002-11-01 00:00:00 | 1) PLEASE PROVIDE SPEC'S ON TANKS FROM | | | THE PRODUCT MANUFACTURE. | | | | | | 2) WHAT IS THE DISTANCE BETWEEN THE | | | TANKS AND ROADS | | | | | | 3) HOW ARE THE TANKS PROTECTED FROM | | | VEHICLE CRASHES. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT. 8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-31 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-10-30 |
Time |
11:22 |
Sent To |
FIRE |
|
| Notes |
| 2002-10-31 00:00:00 | TO FIRE BOX./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-11-18 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2002-11-18 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
2002-11-15 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2002-11-18 00:00:00 | PASSED PER PATTY. DATA ERROR. VJM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-11-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-04 |
Time |
12:29 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-11-04 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2002-11-04 00:00:00 | DENIED: | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | PLEASE SUBMIT MANUFACTURER SUBMITTAL FOR | | | ALL TANKS BEING INSTALLED. | | | | | | PROVIDE DISTANCES TO PROPERTY LINES & | | | BUILDINGS AS PER NFPA 30 2.3.2.1. | | | | | | SEE ALSO COMMENTS FROM FIRE DEPT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|