Plan Review Details - Permit 02102015
Plan Review Stops For Permit 02102015
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-18 Cont ID  
Sent By pkrauss Date 2002-11-18 Time 10:59 Rev Time 0.45
Received By pkrauss Date   Time   Sent To  
Notes
2002-11-18 00:00:00APPROVED BY N. MCCRAY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-01 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 09:45 Sent To  
Notes
2002-11-01 00:00:001) PLEASE PROVIDE SPEC'S ON TANKS FROM
 THE PRODUCT MANUFACTURE.
  
 2) WHAT IS THE DISTANCE BETWEEN THE
 TANKS AND ROADS
  
 3) HOW ARE THE TANKS PROTECTED FROM
 VEHICLE CRASHES.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 11:23 Rev Time 0.00
Received By btrobaug Date 2002-10-30 Time 11:22 Sent To FIRE
Notes
2002-10-31 00:00:00TO FIRE BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-18 Cont ID  
Sent By drunnels Date 2002-11-18 Time 11:02 Rev Time 0.00
Received By drunnels Date 2002-11-15 Time 16:46 Sent To  
Notes
2002-11-18 00:00:00PASSED PER PATTY. DATA ERROR. VJM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-04 Cont ID  
Sent By pkrauss Date 2002-11-04 Time 12:29 Rev Time 0.45
Received By pkrauss Date 2002-11-04 Time 12:16 Sent To  
Notes
2002-11-04 00:00:00DENIED:
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 PLEASE SUBMIT MANUFACTURER SUBMITTAL FOR
 ALL TANKS BEING INSTALLED.
  
 PROVIDE DISTANCES TO PROPERTY LINES &
 BUILDINGS AS PER NFPA 30 2.3.2.1.
  
 SEE ALSO COMMENTS FROM FIRE DEPT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.