Plan Review Details - Permit 02101893
Plan Review Stops For Permit 02101893
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-06-04 Cont ID  
Sent By btrobaug Date 2003-06-04 Time 10:05 Rev Time 0.50
Received By btrobaug Date 2003-06-04 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-06-03 Time 16:35 Rev Time 0.25
Received By dpalmer Date 2003-05-21 Time 07:05 Sent To B
Notes
2003-05-21 00:00:00************ UNSAT ******************
  
 1)NOTE; PLEASE CORRECT MAIN PANEL SHOW-
 ING10 CIERCUITS TO SUB PANEL.
 PLEASE SEE SUB PANEL, SHOWS 10 CIRCUITS
 AS 2P60A AND #6?
  
 2)NOTE: PLEASE CORRELATE AWG FOR FEEDERS
 ON RISER DIAGRAM. SHOWS #6`S TO 200A
 PANEL AND SHOWS 2/0`S TO 60A PANEL?
  
 3)NOTE: PLEASE SEE THAT SD IS STILL
 SHOWN IN KITCHEN. NOT PERMITTED UNDER
 NFPA-72 8-1.4.2.
  
 THESE ITEMS WERE REDLINED ON ORIG PLANS
 AND HAVE NOT BEEN ADDRESSED SINCE ORIG
 REVIEW. PLEASE SUBMIT THE ABOVE FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-07 Cont ID  
Sent By shernand Date 2003-05-20 Time 16:37 Rev Time 0.50
Received By dpalmer Date 2002-11-07 Time 16:22 Sent To B
Notes
2002-11-07 00:00:00************* NOTES **************
  
 NOTES REDLINED ON PLANS.
 SD NOT IN KITCHEN.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 16:34 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 16:34 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-20 Time 16:37 Rev Time 0.00
Received By shernand Date 2003-05-20 Time 16:37 Sent To E
Notes
2003-05-20 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-03 Cont ID  
Sent By btrobaug Date 2003-01-03 Time 16:32 Rev Time 0.00
Received By btrobaug Date 2003-01-03 Time 16:31 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 17:49 Rev Time 0.00
Received By btrobaug Date 2002-10-30 Time 17:47 Sent To Z
Notes
2002-10-30 00:00:00TO Z IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-24 Cont ID  
Sent By pkrauss Date 2002-12-24 Time 13:14 Rev Time 0.30
Received By pkrauss Date 2002-12-24 Time 13:14 Sent To  
Notes
2002-12-24 00:00:00MECHANICAL PERMIT 02101916

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By hmoser Date 2002-11-06 Time 18:51 Rev Time 0.50
Received By hmoser Date 2002-11-06 Time 18:51 Sent To E
Notes
2002-11-06 00:00:00PLAN DENIED
 1) EQUIPMENT SPECIFICATIONS ON MANUAL
 (J) NOT COMPLETE
 2) NEED FRESH AIR CALCULATIONS ON PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By sgraham Date 2002-11-04 Time 15:10 Rev Time 0.33
Received By jleech Date 2002-11-04 Time 17:21 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-02 Cont ID  
Sent By lhatten Date 2002-12-02 Time 18:15 Rev Time 2.50
Received By lhatten Date 2002-11-24 Time 18:15 Sent To  
Notes
2002-12-02 00:00:00REVIEW & STAMPED PLANS 11/24/2002
 CALC. FEES & PRINT CARD 12/02/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 17:49 Rev Time 0.03
Received By sgraham Date   Time   Sent To P
Notes
***NONE***