Plan Review Details - Permit 02101817
Plan Review Stops For Permit 02101817
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-18 Cont ID  
Sent By pkrauss Date 2002-11-12 Time 10:28 Rev Time 2.00
Received By jwitmer Date 2002-11-18 Time 11:11 Sent To  
Notes
2002-11-18 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02101817
 ADD: 322 PURITAN RD
 CONT: H CARO CONSTRUCTION
 TEL: (561)791-8763
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FBC 1804.6.3.1 VENTILATION, CRAWL
 SPACES UNDER BUILDINGS, INDICATE COMPLI-
 ANCE WITH SEC 1-3.
  
 2)1804.6.2.3 CRAWL SPACE ACCESS UNDER
 BUILDINGS WITHOUT ABSSEMENTS SHALL PRO-
 VIDE ONE OPENING NOT LESS THAN 18X24"
  
 3)2304.3.4 WOOD JOIST SHALL HAVE 18"
 CLEARENCE FROM THE BOTTOM OF JOIST TO
 EARTH OR ELSE BE PRESSURE TREATED WOOD
  
 4) FBC 1007.3.1. TREADS & RISERS, SHALL
 NOT HAVE RISERS OVER 7 3/4", 2(R)+1(T)=
 24"-25".
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 10:09 Rev Time 0.50
Received By btrobaug Date 2002-10-30 Time 09:15 Sent To P
Notes
2002-10-30 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 1} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 2} SMOKE DETECTORS ARE REQUIRED INSIDE &
 OUTSIDE OF BEDROOMS PER 8-1.4.1.6 NFPA-
 72.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2002-10-30 00:00:00TO ELEC. IN BOX./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By sgraham Date 2002-10-29 Time 10:03 Rev Time 0.00
Received By btrobaug Date 2002-10-28 Time 07:55 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-12 Cont ID  
Sent By kstevens Date 2002-11-09 Time 05:51 Rev Time 0.25
Received By pkrauss Date 2002-11-12 Time 10:13 Sent To B
Notes
2002-11-12 00:00:00DENIED:
  
 PLEASE PROVIDE INFORMATION ON THE
 EXISTING A/C EQUIPMENT (MAKE, MODEL,
 BTU'S & SEER OF CONDENSER).
  
 INDICATE DUCT SIZE FOR THE SUPPLY &
 RETURN DUCTS FOR THE ADDITION.
  
 INDICATE SIZE, MATERIAL & TERMINATION OF
 THE DRYER EXHAUST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-09 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 10:09 Rev Time 0.50
Received By kstevens Date 2002-11-09 Time 05:36 Sent To M
Notes
2002-11-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE.
 2) NO DRY HORIZONTAL VENTS ALLOWED SEC.
 905.3. (SEE VENT AFTER WATER CLOSET.
 3) SHOWER NOT VENTED.
 4) WATER CLOSET DOUBLE TRAPPED. TRAP
 UNDER SLAB NOT REQUIRED. W/C HAS INTER-
 NAL TRAP. SEC 1002.1
 5) WASH MACHINE SHALL NOT DRAIN INTO WET
 VENT FOR BATHROOM GROUP. SECTIONS 909.1,
 AND 909.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-29 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To I
Notes
***NONE***