Plan Review Details - Permit 02101660
Plan Review Stops For Permit 02101660
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-02-05 Cont ID  
Sent By btrobaug Date 2004-02-05 Time 14:53 Rev Time 0.50
Received By btrobaug Date 2004-02-05 Time 13:05 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-16 Cont ID  
Sent By csiegber Date 2004-02-05 Time 12:25 Rev Time 0.75
Received By btrobaug Date 2003-04-16 Time 15:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-10 Cont ID  
Sent By shernand Date 2003-04-14 Time 16:50 Rev Time 1.00
Received By btrobaug Date 2003-03-10 Time 07:58 Sent To P
Notes
2003-03-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE NECESSARY CHANGES TO SHOW
 CODE COMPLIANCE ON PLANS.
  
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.ON PANEL SCHEDULE
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE,PER 210-12.
  
 3} GROUNDING ELECTRODE SYSTEM TO INCLUDE
 250-50(C).
  
 4} THE EQUIPMENT GROUND FROM THE METER
 TO THE FIRST MEANS OF DISCONNECT
 CREATES A PARALLEL GROUND PATH WITH THE
 NEUTRAL AND MUST BE REMOVED.
  
 5} THE OCP FOR THE 12KW. RANGE IS
 INCORRECT.
  
 6} PLEASE SHOW THE RECEPTACLES SERVING
 THE KICHEN COUNTERTOPS IN COMPLIANCE
 WITH 210-8(A)(6) AND 210-52(C)
  
 IF THERE ARE ANY QUESTION PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 10:03 Rev Time 0.00
Received By btrobaug Date 2002-11-20 Time 10:19 Sent To R
Notes
2002-11-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARYCHANGES
 TO PLANS,AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,ON THE PANEL
 SCHEDULE.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 4} SHOW METER MAIN LOCATION ON PLANS.
  
 5} GEC SYSTEM TO INCLUDE
 250-50(C).PLEASE INDICATE SAME ON RISER
 DIAGRAM.
  
 6} THE CONDUIT FROM THE MAIN DISCONNECT
 TO THE PANEL MUST COMPLY WITH 250-110(EQ
 GND.).
  
 7} THE #10 CONDUCTOR FOR THE RANGE IS
 INCORRECT FOR THE LOAD SERVED AND THE
 OCP.
  
 8} A WP. GFI IS REQUIRED IN THE FRONT OF
 THE RESIDENCE PER 210-52(E).
  
 9} IF THE RECEPTACLE SYMBOLS AT EACH
 COMPRESSER LOCATION ARE MEANT TO
 REPRESENT DISCONNECTS,NOTE THAT THEY
 MUST COMPLY WITH 110-26.
  
 10} PLEASE NOTE THAT THE RECEPTACLES
 SERVING KITCHEN COUNTERTOPS MUST COMPLY
 WITH 210-8(A)(6) AND 210-52(C).
  
 11} THE BATH RECEPTACLE LOCATION MUST
 COMPLY WITH 210-52(D).NOTE BATHS OFF
 BR'S 2 & 5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 12:25 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 12:25 Sent To E
Notes
2004-02-05 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-14 Time 16:49 Rev Time 0.00
Received By shernand Date 2003-04-14 Time 16:49 Sent To E
Notes
2003-04-14 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 10:03 Rev Time 0.00
Received By dpalmer Date 2003-02-26 Time 10:02 Sent To E
Notes
2003-02-26 00:00:00TO BILL T. DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2002-11-07 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2002-11-07 Time 18:45 Sent To  
Notes
2002-11-12 00:00:00TO RES RACK 11/7/02 WRT/DVP.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-11 Cont ID  
Sent By pkrauss Date 2003-03-11 Time 16:50 Rev Time 0.45
Received By pkrauss Date 2003-03-11 Time 16:50 Sent To B
Notes
2003-03-11 00:00:00PROVISO:
  
 1.FRESH AIR CALCULATIONS (NATURAL -
 2001 FBC(M) 402.2 OR MECHANICAL TABLE
 403.3). PROVIDE CALCS AT ROUGH
 INSPECTION.
  
 2.RETURN AIR REQUIRED FROM BEDROOM
 AREAS AS PER 2001 FBC(M) 601.4.
  
 3.FAN SHUTDOWN REQUIRED AT FINAL
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-11-14 Cont ID  
Sent By jleech Date 2003-03-10 Time 16:19 Rev Time 0.33
Received By hmoser Date 2002-11-14 Time 17:46 Sent To R
Notes
2002-11-14 00:00:00 
 AIRCONDITIONING CONTRACTOR MUST SUPPLY
 PLANS,ENERGY CALCULATIONS,MANUAL(J)
 WITH APPLICATION.
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-10 Cont ID  
Sent By jleech Date 2003-03-10 Time 16:18 Rev Time 0.33
Received By jleech Date 2003-03-10 Time 16:18 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-13 Cont ID  
Sent By btrobaug Date 2003-03-10 Time 08:46 Rev Time 0.33
Received By jleech Date 2002-11-13 Time 18:16 Sent To  
Notes
2002-11-13 00:00:00DENIED;
 RISER DIAGRAM HAS SEVERAL CODE
 VIOLATIONS. STACKS TO SECOND FLOOR SHALL
 NOT DUMP INTO VENT STACKS OF FIRST FLOOR
 FIXTURES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2004-02-05 Cont ID  
Sent By rmcdouga Date 2004-02-05 Time 16:22 Rev Time 1.00
Received By rmcdouga Date 2004-02-05 Time 16:22 Sent To  
Notes
2004-02-05 00:00:00REVISION TO SHEETS A1 AND A2 ARE OK

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2003-04-18 Cont ID  
Sent By lmartine Date 2003-04-18 Time 14:53 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-04-18 00:00:00IMPACT FEEPAIDLM

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2003-04-17 Cont ID  
Sent By rmcdouga Date 2003-04-17 Time 13:44 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-04-17 00:00:00DENIED UNTIL IMPACT FEES ARE PAID.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2003-04-17 Cont ID  
Sent By rmcdouga Date 2003-04-17 Time 13:00 Rev Time 4.00
Received By rmcdouga Date 2003-04-17 Time 13:00 Sent To  
Notes
2003-04-17 00:00:00PROVISO
  
 STORM PANELS WILL REQUIRE A SEPARATE
 PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2003-03-13 Cont ID  
Sent By rmcdouga Date 2003-03-13 Time 08:15 Rev Time 4.00
Received By rmcdouga Date 2003-03-13 Time 08:15 Sent To  
Notes
2003-03-13 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE PLANS HAVE BEEN WHITED OUT AND
 CHANGES HAVE BEEN RED LINED. THE
 ARCHITECT IS REQUIRED TO INITIAL AND
 DATE ALL THE CHANGES THAT HAVE BEEN
 WRITTEN ON THE PLANS.
  
 4) THE WRONG FORM WAS SUBMITTED FOR THE
 ENERGY CALCULATIONS. THE CORRECT FORM
 FOR THE RESIDENTIAL WHOLE BUILDING
 METHOD IS 600A. NOTE: THE FORM IS
 REQUIRED TO BE SIGNED BY THE OWNER/AGENT
  
 5) INDICATE THE STAIR RISER HEIGHT ON
 THE PLANS. NOTE: THE SUM OF TWO RISERS
 AND A TREAD EXCLUSIVE OF THE NOSING MUST
 BE BETWEEN 24 AND 25 INCHES.FBC 1007.3
  
 6) THE MINIMUM HEIGHT OF A GUARDRAIL ON
 THE OPEN SIDE OF STAIRS IS 36" PER FBC
 1015 AND 1026.5.1. THE INTERMEDIATE
 RAILS ARE REQUIRED TO REJECT THE PASSAGE
 OF A 4" SPHERE PER FBC 1015.3. PLEASE
 REVISE THE STAIR DETAIL ON A2.
  
 7) CIRCULAR STAIRS ARE REQUIRED TO HAVE
 A MINIMUM TREAD DEPTH OF 9" WITH 1" OF
 NOSING PER FBC 1007.8.3. DRAWINGS APPEAR
 TO SHOW TREADS NARROWER THAN THIS AT THE
 SMALLER RADIUS OF THE STAIR. PLEASE
 INDICATE THIS ON THE PLANS.
  
 8) FBC 2305.2.2 REQUIRES THE FLOOR/
 CEILING ASSEMBLY TO BE DIVIDED INTO
 AREAS OF NO MORE THAN 500 SQ FT BY
 DRAFTSTOPPING. INDICATE ON THE PLANS
 THE LOCATIONS OF THESE DIVISIONS AND THE
 MATERIAL THAT WILL BE USED FOR DRAFTSTOP
  
 9) SHEET A1 SHOWS THE DRYER BEING VENTED
 INTO THE GARAGE. THE FBC MECHANICAL CODE
 504.4 REQUIRES THE DRYER VENT TO
 TERMINATE ON THE OUTSIDE OF THE BUILDING
  
 10) THE WALL SECTION AT THE STUDY IS
 MISMARKED. THE SECTION IS SHOWN ON SHEET
 A4. THE SECTION ON A4 IS ALSO MISMARKED
 AS A3. PLEASE CORRECT.
  
 11) PROVIDE BUCK DETAILS FOR THE
 EXTERIOR WINDOWS, DOORS AND OVERHEAD
 GARAGE DOORS.
  
 12) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. IF NOT
 PROVIDED AT THIS TIME A SEPARATE PERMIT
 AND ADDITIONAL FEES WILL BE REQUIRED.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - 16' WIDE GARAGE DOOR
 - 9' WIDE GARAGE DOOR (THE ONE THAT WAS
 SUBMITTED IS ILLEGIBLE)
 - THE SINGLE OUTSWING/INSWING DOOR IS
 MISSING THE 6 PAGES OF DRAWINGS
 - THE INFORMATION SUBMITTED FOR THE
 NORANDEX PRODUCTS (HORIZONTAL SLIDING
 WINDOWS, FIXED WINDOWS AND SLIDING GLASS
 DOOR ARE NOT ACCEPTABLE WITHOUT SITE
 SPECIFIC ENGINEERING. SEE ATTACHED
 PRODUCT APPROVAL FORM. IT MUST BE FILLED
 OUT AND SIGNED, SEALED AND DATED BY THE
 ENGINEER FOR THE PRODUCT AND SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE PER BUILDING
 OFFICIAL. SEE FBC 103.7 ALTERNATE
 MATERIALS AND METHODS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 12:19 Rev Time 6.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-02 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE INTERNAL PRESSURE
 COEFFICIENT, WHICH IS + OR - 0.18 FOR AN
 ENCLOSED STRUCTURE. PLEASE CORRECT THE
 IMPORTANCE FACTOR, WHICH SHOULD BE 1.00.
  
 4) PLEASE REVISE GENERAL NOTES 3,8 & 10
 ON C1 TO REFERENCE THE FLORIDA BUILDING
 CODE AND 140 MPH WIND ZONE.
  
 5) PROVIDE ENERGY CALCULATIONS, REQUIRED
 BY CHAPTER 13 OF THE FBC.
  
 6) PROVIDE FLOOR AND ROOF FRAMING PLANS.
 PROVIDE A CONNECTOR SCHEDULE AND
 INDICATE THE LOADS TO BE RESISTED.
  
 7) PROVIDE DETAILS OF THE STAIRS, HAND-
 RAILS AND GUARDRAILS WHICH COMPLY WITH
 FBC SECTIONS 1007, 1007.5 AND 1015.
  
 8) PROVIDE DETAILS FOR THE GUARDRAILS AT
 THE EXTERIOR BALCONY WHICH SHOW
 COMPLIANCE WITH FBC SECTIONS 1015 AND
 1608.2.2. INDICATE HEIGHT, INTERMEDIATE
 RAIL SPACING, MATERIAL, CONNECTIONS TO
 STRUCTURE, ETC.
  
 9) INDICATE THE LOCATIONS AND MATERIALS
 THAT WILL BE USED FOR DRAFTSTOPPING THE
 FLOOR/CEILING ASSEMBLY INTO 500 SQFT
 AREAS AS REQUIRED BY FBC 2305.2.2.
  
 10) PROVIDE CONSTRUCTION DETAILS FOR THE
 SECOND FLOOR EXTERIOR BALCONY.
  
 11)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36". REQUIRED FOR
 ALL ATTIC SPACES WITH 24" CLEAR HEIGHT.
  
 12) SPECIFY THE SIZE AND SPACING OF THE
 ATTIC VENTS ON A4. THE RATIO OF NET FREE
 VENTILATING AREA TO THE AREA OF THE
 CEILING SHALL BE MINIMUM OF 1/150. SEE
 FBC 2309.7.
  
 13) CLARIFY THE FOOTINGS FOR THE 16"
 DIAMETER CONCRETE FILLED BLOCK COLUMNS
 AT THE FRONT PORCH.
  
 14) SPECIFY THE CONNECTION OF THE SECOND
 FLOOR EXTERIOR WOOD FRAME BEARING WALL
 TO THE WOOD GIRDER TRUSS. SEE A2.
  
 15) SPECIFY THE BOLT TYPE, LENGTH AND
 EMBEDDMENT FOR THE HD2A/ADS2 CONNECTORS
 INDICATED IN DETAIL 8/A8.
  
 16) SPECIFY THE COLUMN SUPPORTING THE
 GIRDER TRUSS AT THE LIVING ROOM AND THE
 BUILT-UP WOOD COLUMNS SHOWN ON A3.
 SPECIFY THE CONNECTORS AT THE TOPS AND
 BOTTOMS OF THESE COLUMNS. PLEASE CLARIFY
 WHICH ONE OF THE TWO COLUMNS SHOWN IN
 DETAIL 8/A8 IS TO BE USED AT EACH
 LOCATION.
  
 17) PLEASE CLARIFY THE SECTION AT THE
 STUDY WALL ON A3 THAT IS MARKED 4/A3.
 THERE IS NO SECTION OR DETAIL 4 ON SHEET
 A3.
  
 18) THE CITY OF WPB AMENDMENTS TO THE
 FBC 2111.1.9 REQUIRES A 1-1/2" RECESS IN
 MONOLITHIC FOUNDATIONS FOR A WATERSTOP.
 PLEASE REVISE SECTIONS ON A4.
  
 19) THE FBC SECTION 1909.3 REQUIRES THAT
 WELDED WIRE MESH USED IN THE SLAB BE
 SUPPORTED ON APPROVED MATERIALS AT
 SPACINGS NOT TO EXCEED 3 FEET.
  
 20)FBC 905.2.2 REQUIRES A SMOKE DETECTOR
 ON THE FIRST FLOOR IN CLOSE PROXIMITY TO
 THE STAIRWAY LEADING TO THE FLOOR ABOVE.
  
 21)INDICATE FIREBLOCKING WHERE CONCEALED
 SPACES OF WALLS AND FLOORS OR CEILINGS
 MEET. IT IS ALSO REQUIRED AT CONCEALED
 SPCACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF RUNS. SEE FBC 2305.1.
  
 22) REVISE THE CONCRETE TILE NAILING
 INFORMATION ON A4 TO REFERENCE THE FBC.
  
 23) SPECIFY THE SPECIAL ROOF SHEATHING
 NAILING REQUIREMENTS PER THE CITY OF WPB
 AMENDMENTS TO THE FBC TABLE 2306.1.
  
 24) SPECIFY THE TYPE, DIAMETER AND
 EMBEDMENT DEPTH FOR THE BOLTS USED TO
 ATTACH THE LEDGERS SUPPORTING THE FLOOR
 TRUSSES SHOWN IN THE SECTION ON A4.
  
 25) ALL THE IDENTIFING MARKS FOR THE
 SECTIONS AND THE SECTIONS GIVEN ON A4
 ARE INCORRECTLY LABELED AS A3. PLEASE
 CORRECT.
  
 26) PROVIDE BUCK ATTACHMENT DETAILS FOR
 WINDOWS, DOORS AND OVERHEAD GARAGE DOORS
  
 27) SAFETY GLASS IS REQUIRED WITHIN 3
 FEET OF A TUB OR SHOWER PER FBC 2405.2.
 PLEASE INDICATE TEMPERED GLASS AT THESE
 WINDOWS ON THE PLANS.
  
 28)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 29) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - HORIZONTAL SLIDING WINDOWS
 - HORIZONTAL AND VERTICAL STRUCTURAL
 MULLIONS
 - FIXED GLASS WINDOWS (RECTANGULAR AND
 ARCHED)
 - 4 PANEL SLIDING GLASS DOOR
 - OVERHEAD GARAGE DOORS
 - WOOD OR METAL OUTSWING DOOR AT GARAGE
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-07 Cont ID  
Sent By sgraham Date 2002-11-07 Time 14:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
***NONE***