| Plan Review Stops For Permit 02101617 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-12-20 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-12-20 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2002-12-20 00:00:00 | PROVISO: | | | PLEASE PROVIDE A LIFE SAFETY PLAN, | | | INCLUDING DIMESIONS, TRAVEL DISTANCES, | | | ETC. IN ACCORDANCE WITH GOOD | | | ARCHITECTURAL PRACTICES PRIOR TO FINAL | | | INSPECTION.SEE FBC 104.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-12-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-19 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-12-10 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2002-12-10 00:00:00 | THE FIRE PROTECTION FOR THE NEW | | | STRUCTURAL BEAMS IS NOT SHOWN ON THE | | | PLANS AS WAS REQUESTED IN THE 11/05/02 | | | PLAN REVIEW COMMENTS.FBC TABLE 600 | | | REQUIRES 2 HR FIRE RESISTANT PROTECTION | | | FOR BEAMS, GIRDERS AND ARCHES SUPPORTING | | | ONE FLOOR AND FOR FLOOR CEILING | | | ASSEMBLIES. | | | | | | THE 11TH FLOOR LIFE SAFETY DIAGRAM HAS | | | NEITHER DIMENSIONS OR SCALE.IT | | | APPEARS THAT THE COMMON PATH OF TRAVEL | | | WILL EXCEED THE 75' ALLOWED BY FBC | | | 1004.1.3 AND 1004.1.2.PLEASE CLARIFY. | | | | | | PLEASE COLLATE THE PLANS INTO TWO | | | CONCISE SETS AND REMOVE ANY VOID OR | | | OBSOLETE PAGES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-11-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-04 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-11-05 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2002-11-05 00:00:00 | SHOW THE FIRE PROTECTION FOR THE STEEL | | | BEAMS AS REQUIRED BY FBC TABLE 600 | | | (2HRS) | | | | | | SHOW A DETAIL OR SCHEDULE FOR THE | | | CONCRETE SLAB REINFORCING. | | | | | | THE STRUCTURAL SHEET DECLARES DESIGN TO | | | THE 1997 SBC.PLEASE REVISE AND ENSURE | | | COMPLIANCE WITH FBC 2001 | | | | | | PLEASE PROVIDE A LIFE SAFETY PLAN LAYOUT | | | FOR THE 11TH AND 12TH FLOORS INDICATING | | | THE EGRESS AND TENANT SEPARATIONS | | | WHERE NECESSARY.FBC 104.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2002-12-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-04 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
| 2002-12-04 00:00:00 | TO HAROLD P./WRT. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-12-04 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2002-12-04 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2002-12-04 |
Time |
13:53 |
Sent To |
B |
|
| Notes |
| 2002-12-04 00:00:00 | 1) THE TWO EXISTING BASE BUILDING | | | EXIT STAIRS FROM EVERY FLOOR ARE TO | | | REMAIN. ON EVERY FLOOR A MINIMUM OF | | | AT LEAST TWO EXITS ARE TO BE PROVIDED. | | | THESE EXITS ARE TO BE COMPRISED OF | | | RATED EXIT STAIR ENCLOSURES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-11-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-02 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-08 |
Time |
18:12 |
Sent To |
|
|
| Notes |
| 2002-11-08 00:00:00 | 1) PLEASE PROVIDE AN EXITING DIAGRAM | | | FOR THE AREA OF WORK. | | | | | | 2) PLEASE SEE BUILDING PLAN REVIEW | | | COMMENTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-19 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-19 |
Time |
13:26 |
Sent To |
B |
|
| Notes |
| 2002-12-19 00:00:00 | TO HAROLD P./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-02 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-27 |
Time |
07:46 |
Sent To |
FIRE |
|
| Notes |
| 2002-12-02 00:00:00 | IN BOX./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-12-20 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-12-20 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|