Plan Review Details - Permit 02101617
Plan Review Stops For Permit 02101617
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-20 Cont ID  
Sent By hpiskura Date 2002-12-20 Time 09:50 Rev Time 0.00
Received By hpiskura Date 2002-12-20 Time 09:06 Sent To  
Notes
2002-12-20 00:00:00PROVISO:
 PLEASE PROVIDE A LIFE SAFETY PLAN,
 INCLUDING DIMESIONS, TRAVEL DISTANCES,
 ETC. IN ACCORDANCE WITH GOOD
 ARCHITECTURAL PRACTICES PRIOR TO FINAL
 INSPECTION.SEE FBC 104.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 13:26 Rev Time 0.00
Received By hpiskura Date 2002-12-10 Time 08:28 Sent To  
Notes
2002-12-10 00:00:00THE FIRE PROTECTION FOR THE NEW
 STRUCTURAL BEAMS IS NOT SHOWN ON THE
 PLANS AS WAS REQUESTED IN THE 11/05/02
 PLAN REVIEW COMMENTS.FBC TABLE 600
 REQUIRES 2 HR FIRE RESISTANT PROTECTION
 FOR BEAMS, GIRDERS AND ARCHES SUPPORTING
 ONE FLOOR AND FOR FLOOR CEILING
 ASSEMBLIES.
  
 THE 11TH FLOOR LIFE SAFETY DIAGRAM HAS
 NEITHER DIMENSIONS OR SCALE.IT
 APPEARS THAT THE COMMON PATH OF TRAVEL
 WILL EXCEED THE 75' ALLOWED BY FBC
 1004.1.3 AND 1004.1.2.PLEASE CLARIFY.
  
 PLEASE COLLATE THE PLANS INTO TWO
 CONCISE SETS AND REMOVE ANY VOID OR
 OBSOLETE PAGES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 15:23 Rev Time 0.00
Received By hpiskura Date 2002-11-05 Time 13:06 Sent To  
Notes
2002-11-05 00:00:00SHOW THE FIRE PROTECTION FOR THE STEEL
 BEAMS AS REQUIRED BY FBC TABLE 600
 (2HRS)
  
 SHOW A DETAIL OR SCHEDULE FOR THE
 CONCRETE SLAB REINFORCING.
  
 THE STRUCTURAL SHEET DECLARES DESIGN TO
 THE 1997 SBC.PLEASE REVISE AND ENSURE
 COMPLIANCE WITH FBC 2001
  
 PLEASE PROVIDE A LIFE SAFETY PLAN LAYOUT
 FOR THE 11TH AND 12TH FLOORS INDICATING
 THE EGRESS AND TENANT SEPARATIONS
 WHERE NECESSARY.FBC 104.2.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 15:23 Rev Time 0.00
Received By btrobaug Date   Time   Sent To B
Notes
2002-12-04 00:00:00TO HAROLD P./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-04 Cont ID  
Sent By nmccray Date 2002-12-04 Time 13:53 Rev Time 0.00
Received By nmccray Date 2002-12-04 Time 13:53 Sent To B
Notes
2002-12-04 00:00:001) THE TWO EXISTING BASE BUILDING
 EXIT STAIRS FROM EVERY FLOOR ARE TO
 REMAIN. ON EVERY FLOOR A MINIMUM OF
 AT LEAST TWO EXITS ARE TO BE PROVIDED.
 THESE EXITS ARE TO BE COMPRISED OF
 RATED EXIT STAIR ENCLOSURES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-08 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 07:46 Rev Time 0.00
Received By mcarsill Date 2002-11-08 Time 18:12 Sent To  
Notes
2002-11-08 00:00:001) PLEASE PROVIDE AN EXITING DIAGRAM
 FOR THE AREA OF WORK.
  
 2) PLEASE SEE BUILDING PLAN REVIEW
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-19 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 13:26 Rev Time 0.00
Received By btrobaug Date 2002-12-19 Time 13:26 Sent To B
Notes
2002-12-19 00:00:00TO HAROLD P./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-02 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 07:46 Rev Time 0.00
Received By btrobaug Date 2002-11-27 Time 07:46 Sent To FIRE
Notes
2002-12-02 00:00:00IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-12-20 Cont ID  
Sent By hpiskura Date 2002-12-20 Time 09:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-12-20 Cont ID  
Sent By hpiskura Date 2002-12-20 Time 09:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***