Plan Review Details - Permit 02101578
Plan Review Stops For Permit 02101578
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-01-02 Cont ID  
Sent By jwitmer Date 2003-01-02 Time 10:02 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-12-23 Cont ID  
Sent By jwitmer Date 2002-12-23 Time 11:54 Rev Time 2.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-12-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02101578
 ADD: 477 S ROSEMARY/ 165
 CONT: RCC ASSOCIATES
 TEL: (954)429-3700
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET A1.2, SPECIFY THE CONNECTIONS
 FOR THE NEW STEEL COLUMNS TO THE STRUC-
 TURE ABOVE AND AT FLOOR SLAB. SPECIFY
 THE TYPE OF WELD(FILLET, SQUARE, BEVEL
 OR GROOVED) SIZE OF WELD, ETC?
 WHAT TYPE OF COMPONENT DOES THE TOP
 PLATE OF THE COLUMN FASTEN TO? WHAT TYPE
 OF FASTENERS? HAAS WIND AS WELL AS LARGE
 MISSLE IMPACT BEEN CONSIDERED? THE SAME
 INFORMATION REQUIRED FOR BOTTOM PLATE?
 IS IT FLUSH WITH THE FINISH SLAB? TYPE
 OF FASTENERS?
 VERTICAL STEEL STUD INFILL WALL, @
 STOREFRONT NO INFORMATION ON ATTACHMENT
 TO STRUCTURE ABOVE?
  
 3) THE HEAD DETAIL ON SHEET A1.2 CALLS O
 UT FOR PRECAST LINTELS. WHERE WILL THEY
 BE USED? IS THERE FILED CELLS @ THE ENDS
 OF THE NEW OPENINGS, IS OF VERT. REBAR?
 THERE IS A SECTION THROUGH A NEW STORE-
 FRONT WINDOW 1/A2.1 WHERE?
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 PLANS INDICATE THE USE OF STOREFRONT
 SYSTEMS, BUT NO PRODUCT APPROVALS HAVE
 BEEN SUPPLIED. FOR SITE SPECIFIC ENGIN-
 EERING ADDITIONAL INFORMATION REQUIRED:
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 6) SHEET A1.3 NOTES STUCCO CEILING ON
 METAL CHANNEL. PROVIDE SPECIFIC CONSTRUC
 TION DETAILS INCLUDING CONNECTIONS?
 UL LISTING, ETC?
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By hpiskura Date 2002-11-05 Time 15:35 Rev Time 0.00
Received By hpiskura Date 2002-11-05 Time 15:35 Sent To  
Notes
2002-11-05 00:00:00THE DOORS SHOWN AS (7) OBSTRUCT THE REAR
 EXIT.SEE FBC 1012.1.4.PLEASE REVISE
 AS NECESSARY.
  
 IS THE DEMISING WALL AT THE WEST END NEW
 OR EXISTING?
  
 SHEET A1.2, SPECIFY THE CONNECTIONS FOR
 THE NEW STEEL COLUMNS TO THE STRUCTURE
 ABOVE AND SPECIFY THE WELDS.SEE FBC
 104.2
  
 SHOW THE DESIGN PRESSURES FOR THE NEW
 STORE FRONT.SEE FBC 1607.1.7.
  
 A1.2 THE WALL SECTIONS SHOW USE OF
 PLYWOOD IN THE EXTERIOR WALL.THIS IS
 PROHIBITTED IN TYPE IV CONSTRUCTION,
 SEE FBC 606.
  
 THE "HEAD DETAIL" ON SHEET A1.2 CALLS
 OUT PRE-CAST LINTEL.WHERE WILL THIS
 BE USED?
  
 SHEET A1.3 NOTES A STUCCO CEILING ON
 METAL CHANNELS.PROVIDE A SPECIFIC
 CONSTRUCTION DETAIL INCLUDING
 CONNECTIONS.SEE FBC 104.2.
  
 WHERE WILL THE KITCHEN HOOD EXHAUST?
 SHAFT DETAILS?
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 DROPPED SOFFIT/BULKHEAD OVER THE
 KITCHEN AREA.
  
 THE DOOR SCHEDULE CALLS OUT A DEAD BOLT
 FOR DOOR #8.SEE FBC 1019.7.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-28 Cont ID  
Sent By dpalmer Date 2003-04-28 Time 07:26 Rev Time 0.50
Received By dpalmer Date 2003-04-28 Time 07:26 Sent To  
Notes
2003-04-28 00:00:00ELEC REV ONLY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-05 Cont ID  
Sent By shernand Date 2003-04-21 Time 15:26 Rev Time 1.00
Received By dpalmer Date 2002-12-05 Time 13:26 Sent To  
Notes
2002-12-05 00:00:00*********** NOTE:
 CONTRACTOR NEEDS TO COME IN AND TAKE OUT
 OLD SHEETS AND MAKE TWO COMPLETE SETS
 FOR REVIEW AND PERMITTING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By dpalmer Date 2002-11-05 Time 06:23 Rev Time 0.25
Received By dpalmer Date 2002-11-05 Time 06:17 Sent To  
Notes
2002-11-05 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE ADD SHOW WINDOW RECEPTS
 FOR OTHER WINDOWS ALONG SIDE. 210-62
  
 2)NOTE: PLEASE CORRELATE PANEL "B" ON
 RISER AND PANEL DETAIL. ONE SHOWS MCB
 (REQ`D) AND OTHER SHOWN AS MLO.
  
 3)NOTE: PLEASE SHOW CONDUCTORS ON SECOND
 -ARY SIDE OF TRANSFORMER.
  
 4)NOTE: PLEASE PROVIDE LOAD CALCULATION
 ON EXSITING 100A MAIN FEEDING SPACE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.(215-5) IF THERE ARE ANY QUESTION
 -S, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-12 Cont ID  
Sent By mcarsill Date 2002-12-12 Time 11:12 Rev Time 0.00
Received By mcarsill Date 2002-12-12 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-15 Cont ID  
Sent By mcarsill Date 2002-11-15 Time 10:11 Rev Time 0.00
Received By mcarsill Date 2002-11-15 Time 10:11 Sent To  
Notes
2002-11-15 00:00:00PLEASE SEE BUILDING PLAN REVIEW NOTES.
 THIS OFFICE AGREES WITH THEIR NOTES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 15:25 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 15:25 Sent To E
Notes
2003-04-21 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-24 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2002-12-24 Time 10:33 Sent To  
Notes
2002-12-24 00:00:00TO COMM BOARD #22.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 10:12 Rev Time 0.00
Received By btrobaug Date 2002-11-25 Time 10:13 Sent To  
Notes
2002-11-26 00:00:00TO COMM BOARD # 23./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-15 Cont ID  
Sent By pkrauss Date 2002-11-15 Time 07:29 Rev Time 0.40
Received By pkrauss Date 2002-11-15 Time 07:03 Sent To  
Notes
2002-11-15 00:00:00PROVISO:
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRESUPRESSION, AND WALK-IN COOLER.
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 & INSTALLATION INSTRUCTIONS WITH PERMIT
 APPLICATION.
  
 HOOD SUBMITTAL - PROVIDE DETAIL OF
 GREASE DUCT (TERMINATION, SLOPE, ACCESS
 DOORS, ETC).SHOW COMPLIANCE WITH 2001
 FBC(M) SECTION 507 & 507 AS WELL AS
 NFPA 96.PROVIDE AIR BALANCE.INDICATE
 AIR MAKE-UP FOR HOOD.
  
 PLEASE NOTE AHU PIPING DETAIL DIAGRAM -
 BULL-HEADING TEE IS NOT ALLOWED.
 2001 FBC(M) 1206.1.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-06 Cont ID  
Sent By kstevens Date 2003-01-06 Time 09:07 Rev Time 0.00
Received By kstevens Date 2003-01-06 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-14 Cont ID  
Sent By kstevens Date 2002-12-14 Time 14:08 Rev Time 1.25
Received By kstevens Date 2002-12-14 Time 14:07 Sent To  
Notes
2002-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 *****FROM PREVIOUS REVIEW
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ********NEW COMMENT
 1) PLEASE VERIFY WITH GAS PROVIDER THE
 DELIVERY PRESSURE. THEY DO NOT USEA
 1LB METER AND IF IT IS A 1LB SYSTEM THEN
 ALL REGULATORS SHALL BE SHOWN ON GAS
 RISER DIAGRAM. MANUFACTURE CUT SHEETS
 FOR REGULATORS WILL BE REQUIRED, AND
 A SHUT OFF VALVE AND UNION SHALL BE
 SHOWN ON RISER.
 2) PLANS SHALL BE SUBMITTED AS COMPLETE
 SETS. ALL OLD SHEETS SHALL BE REMOVED,
 AND NEW SHEETS INSERTED. SUBMIT ON SET
 OF OLD SHEETS TAKEN OUT FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By kstevens Date 2002-11-07 Time 16:50 Rev Time 3.00
Received By kstevens Date 2002-11-07 Time 16:50 Sent To  
Notes
2002-11-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL CODE
 FBC-2001 CHAPTER 11
  
 1) SHT A1.0 PLEASE SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLE 403.1.
 INDICATE IF SEATING IS FIXED, NOT FIXED,
 OR BOTH. NUMBER OF BOOTH SEATING. SEE
 TABLE 1003.1 FBC-2001 BUILDING.
 2) SHT A2.0 SUBMIT MANUFACTURE INFORMAT-
 ION FOR WATER FILTER FOR ICE MACHINE.
 FILTER SHALL BE NSF APPROVED.
 3) SHT A4.1 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFICTIVE RANGE" NOT
 AT TOP OF DROPS PER MANUFACTURE INSTALL-
 ATION AND PDI-WH 201.
 4) SHT A4.1 GAS RISER, FOLLOWING INFOR-
 MATION REQUIRED FOR GAS PERMIT APPLICAT-
 ION. (SEPARATE GAS PERMIT REQUIRED)
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE SEC
 502 THRU 506.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, & FBC-2001
 FUEL GAS CODE SEC. 402.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377