| Plan Review Stops For Permit 02101507 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2003-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-06-25 |
Time |
14:06 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2003-06-25 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2003-06-25 00:00:00 | REVISION # 7JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2003-06-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-06-23 |
Time |
11:30 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2003-06-23 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2003-06-23 00:00:00 | REVISION: 06/23/03 OK J WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-01-28 |
Time |
12:21 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2003-01-28 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2003-01-28 00:00:00 | | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 02101507 | | | ADDRESS: 700 S ROSEMARY # 118 | | | ARCH: HVC ARCHITECTS | | | TELL # (305)567-0602 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-12-31 |
Time |
16:30 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2002-12-31 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-11-14 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-11-14 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-11-06 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-11-06 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-11-06 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2002-11-06 00:00:00 | PLAN REVIEW ONLY NOT A PERMIT | | | APPLICATION. | | | | | | THE OCCUPANCY USE GROUP IS M, SEE FBC | | | 304.2.3. | | | | | | TWO EXITS ARE REQUIRED FROM THIS SPACE, | | | SEE FBC 1025.1 RE: 50' TRAVEL DISTANCE. | | | | | | SEE ALSO FBC 1004.2. | | | | | | EGRESS IS NOT PERMITTED THROUGH KITCHENS | | | OR SIMILAR AREAS.SEE FBC 1001.1.3. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2003-07-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-29 |
Time |
15:51 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-07-29 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2003-06-26 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-07-25 |
Time |
09:38 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-06-26 |
Time |
10:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-05-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-19 |
Time |
16:09 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-05-19 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-24 |
Time |
13:40 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-01-24 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-18 |
Time |
14:33 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2002-12-18 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2002-12-18 00:00:00 | ************* UNSAT ******************** | | | | | | 1)NOTE: PLEASE NOTE, "SHOW WINDOW" | | | RECEPTS WILL BE REQ`D PER 210-62 AND | | | ART 100 OF NEC. IT WAS NOTED THAT PLANS | | | SHOW A NOTE MENTIONONG THAT NO RECEPTS | | | ARE REQ`D. PLEASE NOTE, ALMOST ALL REST/ | | | FAST FOOD/FOOD SERVICE ETC HAVE A MEANS | | | TO ADVERTISE IN WINDOWS, THEREFORE MEET- | | | ING ART 100. SMALL WINDOW SIGNS ETC ARE | | | USED AND RECEPTS IN "SHOW" WINDOWS | | | PREVENT THE USED OF EXTENSION CORDS | | | BEING USED IN A MANOR THAT WOULD CREATE | | | A FIRE AND/OR LIFE SAFETY ISSUE. | | | | | | 2)NOTE: PLEASE SEE 450-13B FOR SIZING | | | OF PERMITTED TRANSFORMERS ABOVE CEILING. | | | PLEASE NOTE, UP TO 50 KVA ONLY. | | | PLEASE ADDRESS. | | | | | | 3)NOTE: PLEASE SEE 240-21 FOR TAPPED | | | CONDUCTORS FROM TRANSFORMER. EITHER | | | PRIMARY/PLUS SECONDARY OR 10'FT MAX. | | | | | | 4)NOTE: PLEASE NOTE NO CONTINUOUS | | | EQUIPMENT GROUND IS SHOWN FROM SECONDARY | | | SIDE OF TRANSFORMER TO PANEL? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-31 |
Time |
07:02 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-10-31 |
Time |
07:02 |
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE RISER DIAGRAM NEEDS | | | MORE INFORMATION FOR COMPLETE REVIEW. | | | PLEASE NOTE MISSING WIRE AND CONDUIT | | | FROM X-FORMER TO PANEL "A". | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS IN CONDUITS TO AND | | | FROM TRANSFORMER. PLEASE CLARIFY METHOD | | | OF EQUIPMENT GROUND BETWEENGUTTER AND | | | PANEL "H". SIZE PER 250-122, PER 250-24 | | | | | | 3)NOTE: PLEASE CLARIFY 75KVA TRANSFORMER | | | BELOW CEILING. PER 450-13 | | | | | | 4)NOTE: PLEASE CLARIFY NEW/EXISTING | | | SHOW WINDOW RECEPTS PER 210-62 | | | | | | 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER | | | 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2003-08-06 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-08-06 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-08-06 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2003-08-06 00:00:00 | REVISION DATED 7-14-03 OK |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-07-07 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-07-07 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2003-07-07 00:00:00 | REVISION 6-24-03 NAM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2003-06-12 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-06-12 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-06-12 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2003-06-12 00:00:00 | REVISION # 4 SUBMITTED 5-16-03 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-01-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-01-23 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-01-23 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-12-18 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-12-18 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-11-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-11-22 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-22 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2002-11-22 00:00:00 | 1) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND | | | CEILINGS. | | | | | | 2) COULD NOT LOCATE ANY FIRE ALARM | | | EQUIPMENT ON FLOOR PLAN. DID LOCATE | | | FIRE ALARM RISER DIAGRAM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-07-25 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-07-25 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2003-07-25 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2003-07-25 00:00:00 | TO DP DESK | | | TO COMM BD # 10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-06-24 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-24 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-24 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2003-06-24 00:00:00 | COMM BOARD #28 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-05-19 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-19 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-19 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2003-05-19 00:00:00 | COMM BOARD #3 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-05-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-14 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-14 |
Time |
11:14 |
Sent To |
P |
|
| Notes |
| 2003-05-14 00:00:00 | KSTEVENS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-17 |
Time |
18:26 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-01-16 |
Time |
18:26 |
Sent To |
|
|
| Notes |
| 2003-01-17 00:00:00 | COMM.BOARD#27./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-10 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-10 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2002-12-10 00:00:00 | COMM BOARD #42./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-07-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-28 |
Time |
13:37 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-07-28 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-18 |
Time |
12:30 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-12-18 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-11-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-26 |
Time |
13:33 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-11-26 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2002-11-26 00:00:00 | DENIED: | | | | | | PLEASE CLARIFY THE FOLLOWING: | | | | | | 1.DRAIN PAN WITH OVERFLOW PROTECTION | | | REQUIRED AS PER 2001 FBC(M) 307.2.3. | | | | | | 2.PLEASE IDENTIFY CONDENSATE DRAIN | | | (LINE SIZE & MATERIAL). INDICATE | | | TERMINATION (EXISTING?) | | | | | | 3.CONDENSER UNIT STANDS SHALL COMPLY | | | WITH 2001 FBC TABLE 1511.7 (SEE | | | ATTACHED). | | | | | | PLEASE NOTE ADEQUATE ACCESS REQUIRED FOR | | | INSPECTION, SERVICE & REPLACEMENT OF THE | | | AHU. | | | | | | ADDITIONAL PERMIT REQUIRED FOR WALK-IN | | | COOLERS/FREEZERS.PLEASE PROVIDE | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
N |
Date |
2003-07-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-05 |
Time |
13:41 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-07-05 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2003-07-05 00:00:00 | NO PLUMBING REVISIONS SHOWN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2003-06-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-16 |
Time |
15:39 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2003-06-11 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2003-06-16 00:00:00 | PASSED - PROVISO - FLOOR SINKS SHALL BE | | | LOCATED UNDER FIXTURES SO AS NOT TO PRE- | | | SENT A TRIPPING HAZARD. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2003-05-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-22 |
Time |
07:01 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2003-05-21 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2003-05-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) FLOOR SINKS ARE REQUIRED FOR ALL | | | SINKS IN THE FOOD PREP AREAS. | | | 2) ALL FLOOR SINKS THAT HAVE INDIRECT | | | WASTE SHALL BE LOCATED SO AS NOT TO BE A | | | TRIPPING HAZARD. | | | 3) FLOOR DRAINS REQUIRED FOR GENERAL | | | CLEAN UP AREAS. (TO CLEAN FLOOR) | | | 4) ALL FILTERS SHALL BE NSF APPROVED. | | | MANUF. INFO REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-01-23 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-14 |
Time |
11:14 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-01-23 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2003-01-23 00:00:00 | PASSED PROVISO - CHECK VALVE TO BE DE- | | | LETED OR EXPANSION TANK MOVED TO HOT | | | SIDE OF SYSTEM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-12-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-27 |
Time |
15:56 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-12-27 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2002-12-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) ACKNOWELEGED RESPONSE TO COMMENT #1, | | | STAMPED PLAN BY HOTEL AND RESTURANT DIV | | | REQUIRED WILL STILL BE REQUIRED FOR | | | PUBLIC RECORD AND ON JOBSITE AS SOON AS | | | POSSIBLE. | | | 2) FROM PREVIOUS REVIEW: ALL INDIRECT | | | WASTE SHALL DRAIN INTO A FLOOR SINK, | | | ITEMS #3 (2) AND # 15.1 STILL DRAIN INTO | | | A TROUGH. | | | 3) FROM PREVIOUS REVIEW: EXPANSION CON- | | | TROL FOR WATER HEATER IS NOT ACCOMPLISH- | | | ED BY USE OF A PRESSURE REDUCING VALVE. | | | AN EXPANSION TANK IS REQUIRED AT WATER | | | HEATER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-11-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-13 |
Time |
11:37 |
Rev Time |
3.50 |
| Received By |
kstevens |
Date |
2002-11-12 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2002-11-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PLEASE ROUTE PLANS TO DEPT. OF BUSIN- | | | ESS REGULATION HOTEL AND RESTURAND DIV. | | | (954) 956-5692 FOR REVIEW PRIOR TO RE- | | | SUBMITTING TO CITY FOR REVIEW. | | | 2) SHT D-1 DEMO NOTES #4 & 5, ALL CAPPED | | | LINES (WATER & SANT.) SHALL BE INSPECTED | | | PRIOR TO COVERING. | | | 3) SHT EQ-1 EQUIPMENT SCHEDULE, ITEMS | | | #7, 19, 21, 37, 43, 47, 49, & 50 DO NOT | | | SHOW EITHER WATER SUPPLY, WASTE, (DIRECT | | | OR INDIRECT), OR BOTH. PLEASE CLAIRFY. | | | 4) SHT A-1 TABLE 403.1 REQUIRES A DRINK- | | | ING FOUNTAIN. | | | 5) SHTS P-1/P-2 (SANT RISER) ALL IN- | | | DIRECT WASTE SHALL BE DISCHARGED INTO A | | | FLOOR SINK. FLOOR DRAINS, & TROUGH DRAIN | | | IS NOT AN APPROVED INDIRECT WASTE RE- | | | CEPTOR. SEC 802.3 - PLEASE PROVIDE FLOOR | | | SINKS FOR ALL INDIRECT WASTES AND LOCATE | | | THEM SO THEY WILL NOT BE TRIPPING HAZARD | | | 6) SHT P-1 BIG DIPPER GREASE TRAP IS NOT | | | APPROVED FOR THIS SPACE. A GREASE LINE | | | IS AVAILABLE FOR USE IN 700 S ROSEMARY | | | BLDG. PLEASE CHECK WITH CITY PLACE MAN- | | | AGEMENT. | | | 7) SHT P-1 AN RPZ BACKFLOW IS REQUIRED | | | FOR THIS SPACE. MAXIMUM HEIGHT A.F.F. IS | | | 4' FOR SERVICING AND TESTING. | | | 8) SHT P-1 DISHWASHER, ITEM #8 SHALL | | | DISCHARGE INTO THE SANITARY SYSTEM, NOT | | | THE GREASE WASTE SYSTEM AS SHOWN. PER | | | UTILITY DEPT. (ALSO SHOW ON SANITARY/ | | | GREASE RISERS SHT P-2) | | | 9) SHT P-1 ALL FOOD HANDLING EQUIPMENT | | | AND CLEAR WASTE WATER SHALL DISCHARGE | | | THROUGH AN INDIRECT WASTE PIPE AS SPECI- | | | FIED IN SECTIONS 802.1.1 THROUGH 802.1.4 | | | 10) SHTS P-1/P-2WATER HEATER PAN DRAIN | | | AND RELIEF LINE SHALL DRAIN INTO A FLOOR | | | SINK NOT FLOOR DRAIN AS SHOWN ON FLOOR | | | PLAN AND HEATER DETAIL. | | | 11) SHT P-2 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL IS REQUIRED PER 607.3 | | | AND 607.3.2. PLEASE SHOW ON DETAIL. | | | 12) SHT P-2 PLEASE SUBMIT CALCULATIONS | | | FOR WATER SUPPLY FOR FIXTURES. 3/4" FOR | | | ALL FIXTURES. | | | 13) SHT P-3 "NOTE" STATES ALL INDIRECT | | | WASTE TO FLOOR DRAINS, PLEASE SHOW ALL | | | INDIRECT TO FLOOR SINKS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|