Plan Review Details - Permit 02101507
Plan Review Stops For Permit 02101507
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-06-25 Cont ID  
Sent By jwitmer Date 2003-06-25 Time 14:06 Rev Time 1.25
Received By jwitmer Date 2003-06-25 Time 14:06 Sent To  
Notes
2003-06-25 00:00:00REVISION # 7JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-06-23 Cont ID  
Sent By jwitmer Date 2003-06-23 Time 11:30 Rev Time 0.50
Received By jwitmer Date 2003-06-23 Time 11:30 Sent To  
Notes
2003-06-23 00:00:00REVISION: 06/23/03 OK J WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-01-28 Cont ID  
Sent By jwitmer Date 2003-01-28 Time 12:21 Rev Time 1.25
Received By jwitmer Date 2003-01-28 Time 11:22 Sent To  
Notes
2003-01-28 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02101507
 ADDRESS: 700 S ROSEMARY # 118
 ARCH: HVC ARCHITECTS
 TELL # (305)567-0602
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-31 Cont ID  
Sent By jwitmer Date 2002-12-31 Time 16:30 Rev Time 0.75
Received By jwitmer Date 2002-12-31 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-14 Cont ID  
Sent By hpiskura Date 2002-11-14 Time 10:18 Rev Time 0.00
Received By hpiskura Date 2002-11-14 Time 10:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By hpiskura Date 2002-11-06 Time 11:52 Rev Time 0.00
Received By hpiskura Date 2002-11-06 Time 08:13 Sent To  
Notes
2002-11-06 00:00:00PLAN REVIEW ONLY NOT A PERMIT
 APPLICATION.
  
 THE OCCUPANCY USE GROUP IS M, SEE FBC
 304.2.3.
  
 TWO EXITS ARE REQUIRED FROM THIS SPACE,
 SEE FBC 1025.1 RE: 50' TRAVEL DISTANCE.
  
 SEE ALSO FBC 1004.2.
  
 EGRESS IS NOT PERMITTED THROUGH KITCHENS
 OR SIMILAR AREAS.SEE FBC 1001.1.3.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-07-29 Cont ID  
Sent By dpalmer Date 2003-07-29 Time 15:51 Rev Time 0.33
Received By dpalmer Date 2003-07-29 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-06-26 Cont ID  
Sent By alange Date 2003-07-25 Time 09:38 Rev Time 0.50
Received By dpalmer Date 2003-06-26 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-05-19 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 16:09 Rev Time 0.33
Received By dpalmer Date 2003-05-19 Time 15:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 13:40 Rev Time 0.50
Received By dpalmer Date 2003-01-24 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-12-18 Cont ID  
Sent By dpalmer Date 2002-12-18 Time 14:33 Rev Time 1.00
Received By dpalmer Date 2002-12-18 Time 14:33 Sent To  
Notes
2002-12-18 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE NOTE, "SHOW WINDOW"
 RECEPTS WILL BE REQ`D PER 210-62 AND
 ART 100 OF NEC. IT WAS NOTED THAT PLANS
 SHOW A NOTE MENTIONONG THAT NO RECEPTS
 ARE REQ`D. PLEASE NOTE, ALMOST ALL REST/
 FAST FOOD/FOOD SERVICE ETC HAVE A MEANS
 TO ADVERTISE IN WINDOWS, THEREFORE MEET-
 ING ART 100. SMALL WINDOW SIGNS ETC ARE
 USED AND RECEPTS IN "SHOW" WINDOWS
 PREVENT THE USED OF EXTENSION CORDS
 BEING USED IN A MANOR THAT WOULD CREATE
 A FIRE AND/OR LIFE SAFETY ISSUE.
  
 2)NOTE: PLEASE SEE 450-13B FOR SIZING
 OF PERMITTED TRANSFORMERS ABOVE CEILING.
 PLEASE NOTE, UP TO 50 KVA ONLY.
 PLEASE ADDRESS.
  
 3)NOTE: PLEASE SEE 240-21 FOR TAPPED
 CONDUCTORS FROM TRANSFORMER. EITHER
 PRIMARY/PLUS SECONDARY OR 10'FT MAX.
  
 4)NOTE: PLEASE NOTE NO CONTINUOUS
 EQUIPMENT GROUND IS SHOWN FROM SECONDARY
 SIDE OF TRANSFORMER TO PANEL?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 07:02 Rev Time 0.50
Received By dpalmer Date 2002-10-31 Time 07:02 Sent To  
Notes
2002-10-31 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE NOTE RISER DIAGRAM NEEDS
 MORE INFORMATION FOR COMPLETE REVIEW.
 PLEASE NOTE MISSING WIRE AND CONDUIT
 FROM X-FORMER TO PANEL "A".
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS IN CONDUITS TO AND
 FROM TRANSFORMER. PLEASE CLARIFY METHOD
 OF EQUIPMENT GROUND BETWEENGUTTER AND
 PANEL "H". SIZE PER 250-122, PER 250-24
  
 3)NOTE: PLEASE CLARIFY 75KVA TRANSFORMER
 BELOW CEILING. PER 450-13
  
 4)NOTE: PLEASE CLARIFY NEW/EXISTING
 SHOW WINDOW RECEPTS PER 210-62
  
 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER
 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2003-08-06 Cont ID  
Sent By nmccray Date 2003-08-06 Time 11:50 Rev Time 0.00
Received By nmccray Date 2003-08-06 Time 11:49 Sent To  
Notes
2003-08-06 00:00:00REVISION DATED 7-14-03 OK

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-07-07 Cont ID  
Sent By nmccray Date 2003-07-07 Time 14:17 Rev Time 0.00
Received By nmccray Date 2003-07-07 Time 14:17 Sent To  
Notes
2003-07-07 00:00:00REVISION 6-24-03 NAM

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-06-12 Cont ID  
Sent By nmccray Date 2003-06-12 Time 15:40 Rev Time 0.00
Received By nmccray Date 2003-06-12 Time 15:40 Sent To  
Notes
2003-06-12 00:00:00REVISION # 4 SUBMITTED 5-16-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-01-23 Cont ID  
Sent By mcarsill Date 2003-01-23 Time 15:51 Rev Time 0.00
Received By mcarsill Date 2003-01-23 Time 15:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 09:59 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 10:08 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 10:08 Sent To  
Notes
2002-11-22 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 2) COULD NOT LOCATE ANY FIRE ALARM
 EQUIPMENT ON FLOOR PLAN. DID LOCATE
 FIRE ALARM RISER DIAGRAM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-25 Cont ID  
Sent By alange Date 2003-07-25 Time 09:37 Rev Time 0.00
Received By alange Date 2003-07-25 Time 09:37 Sent To  
Notes
2003-07-25 00:00:00TO DP DESK
 TO COMM BD # 10

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-24 Cont ID  
Sent By shernand Date 2003-06-24 Time 10:06 Rev Time 0.00
Received By shernand Date 2003-06-24 Time 10:06 Sent To  
Notes
2003-06-24 00:00:00COMM BOARD #28

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-19 Time 09:59 Rev Time 0.00
Received By shernand Date 2003-05-19 Time 09:59 Sent To  
Notes
2003-05-19 00:00:00COMM BOARD #3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 11:14 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 11:14 Sent To P
Notes
2003-05-14 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:26 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 18:26 Sent To  
Notes
2003-01-17 00:00:00COMM.BOARD#27./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 18:00 Rev Time 0.00
Received By btrobaug Date 2002-12-10 Time 18:00 Sent To  
Notes
2002-12-10 00:00:00COMM BOARD #42./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-28 Cont ID  
Sent By pkrauss Date 2003-07-28 Time 13:37 Rev Time 0.35
Received By pkrauss Date 2003-07-28 Time 13:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By pkrauss Date 2002-12-18 Time 12:30 Rev Time 0.35
Received By pkrauss Date 2002-12-18 Time 11:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By pkrauss Date 2002-11-26 Time 13:33 Rev Time 0.45
Received By pkrauss Date 2002-11-26 Time 13:18 Sent To  
Notes
2002-11-26 00:00:00DENIED:
  
 PLEASE CLARIFY THE FOLLOWING:
  
 1.DRAIN PAN WITH OVERFLOW PROTECTION
 REQUIRED AS PER 2001 FBC(M) 307.2.3.
  
 2.PLEASE IDENTIFY CONDENSATE DRAIN
 (LINE SIZE & MATERIAL). INDICATE
 TERMINATION (EXISTING?)
  
 3.CONDENSER UNIT STANDS SHALL COMPLY
 WITH 2001 FBC TABLE 1511.7 (SEE
 ATTACHED).
  
 PLEASE NOTE ADEQUATE ACCESS REQUIRED FOR
 INSPECTION, SERVICE & REPLACEMENT OF THE
 AHU.
  
 ADDITIONAL PERMIT REQUIRED FOR WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 6 Status N Date 2003-07-05 Cont ID  
Sent By kstevens Date 2003-07-05 Time 13:41 Rev Time 0.33
Received By kstevens Date 2003-07-05 Time 13:41 Sent To  
Notes
2003-07-05 00:00:00NO PLUMBING REVISIONS SHOWN

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-06-16 Cont ID  
Sent By kstevens Date 2003-06-16 Time 15:39 Rev Time 2.00
Received By kstevens Date 2003-06-11 Time 16:01 Sent To  
Notes
2003-06-16 00:00:00PASSED - PROVISO - FLOOR SINKS SHALL BE
 LOCATED UNDER FIXTURES SO AS NOT TO PRE-
 SENT A TRIPPING HAZARD.

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-05-22 Cont ID  
Sent By kstevens Date 2003-05-22 Time 07:01 Rev Time 1.50
Received By kstevens Date 2003-05-21 Time 18:50 Sent To  
Notes
2003-05-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FLOOR SINKS ARE REQUIRED FOR ALL
 SINKS IN THE FOOD PREP AREAS.
 2) ALL FLOOR SINKS THAT HAVE INDIRECT
 WASTE SHALL BE LOCATED SO AS NOT TO BE A
 TRIPPING HAZARD.
 3) FLOOR DRAINS REQUIRED FOR GENERAL
 CLEAN UP AREAS. (TO CLEAN FLOOR)
 4) ALL FILTERS SHALL BE NSF APPROVED.
 MANUF. INFO REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-23 Cont ID  
Sent By shernand Date 2003-05-14 Time 11:14 Rev Time 0.50
Received By kstevens Date 2003-01-23 Time 09:23 Sent To  
Notes
2003-01-23 00:00:00PASSED PROVISO - CHECK VALVE TO BE DE-
 LETED OR EXPANSION TANK MOVED TO HOT
 SIDE OF SYSTEM.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-27 Cont ID  
Sent By kstevens Date 2002-12-27 Time 15:56 Rev Time 1.50
Received By kstevens Date 2002-12-27 Time 15:00 Sent To  
Notes
2002-12-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) ACKNOWELEGED RESPONSE TO COMMENT #1,
 STAMPED PLAN BY HOTEL AND RESTURANT DIV
 REQUIRED WILL STILL BE REQUIRED FOR
 PUBLIC RECORD AND ON JOBSITE AS SOON AS
 POSSIBLE.
 2) FROM PREVIOUS REVIEW: ALL INDIRECT
 WASTE SHALL DRAIN INTO A FLOOR SINK,
 ITEMS #3 (2) AND # 15.1 STILL DRAIN INTO
 A TROUGH.
 3) FROM PREVIOUS REVIEW: EXPANSION CON-
 TROL FOR WATER HEATER IS NOT ACCOMPLISH-
 ED BY USE OF A PRESSURE REDUCING VALVE.
 AN EXPANSION TANK IS REQUIRED AT WATER
 HEATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-13 Cont ID  
Sent By kstevens Date 2002-11-13 Time 11:37 Rev Time 3.50
Received By kstevens Date 2002-11-12 Time 18:50 Sent To  
Notes
2002-11-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE ROUTE PLANS TO DEPT. OF BUSIN-
 ESS REGULATION HOTEL AND RESTURAND DIV.
 (954) 956-5692 FOR REVIEW PRIOR TO RE-
 SUBMITTING TO CITY FOR REVIEW.
 2) SHT D-1 DEMO NOTES #4 & 5, ALL CAPPED
 LINES (WATER & SANT.) SHALL BE INSPECTED
 PRIOR TO COVERING.
 3) SHT EQ-1 EQUIPMENT SCHEDULE, ITEMS
 #7, 19, 21, 37, 43, 47, 49, & 50 DO NOT
 SHOW EITHER WATER SUPPLY, WASTE, (DIRECT
 OR INDIRECT), OR BOTH. PLEASE CLAIRFY.
 4) SHT A-1 TABLE 403.1 REQUIRES A DRINK-
 ING FOUNTAIN.
 5) SHTS P-1/P-2 (SANT RISER) ALL IN-
 DIRECT WASTE SHALL BE DISCHARGED INTO A
 FLOOR SINK. FLOOR DRAINS, & TROUGH DRAIN
 IS NOT AN APPROVED INDIRECT WASTE RE-
 CEPTOR. SEC 802.3 - PLEASE PROVIDE FLOOR
 SINKS FOR ALL INDIRECT WASTES AND LOCATE
 THEM SO THEY WILL NOT BE TRIPPING HAZARD
 6) SHT P-1 BIG DIPPER GREASE TRAP IS NOT
 APPROVED FOR THIS SPACE. A GREASE LINE
 IS AVAILABLE FOR USE IN 700 S ROSEMARY
 BLDG. PLEASE CHECK WITH CITY PLACE MAN-
 AGEMENT.
 7) SHT P-1 AN RPZ BACKFLOW IS REQUIRED
 FOR THIS SPACE. MAXIMUM HEIGHT A.F.F. IS
 4' FOR SERVICING AND TESTING.
 8) SHT P-1 DISHWASHER, ITEM #8 SHALL
 DISCHARGE INTO THE SANITARY SYSTEM, NOT
 THE GREASE WASTE SYSTEM AS SHOWN. PER
 UTILITY DEPT. (ALSO SHOW ON SANITARY/
 GREASE RISERS SHT P-2)
 9) SHT P-1 ALL FOOD HANDLING EQUIPMENT
 AND CLEAR WASTE WATER SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE AS SPECI-
 FIED IN SECTIONS 802.1.1 THROUGH 802.1.4
 10) SHTS P-1/P-2WATER HEATER PAN DRAIN
 AND RELIEF LINE SHALL DRAIN INTO A FLOOR
 SINK NOT FLOOR DRAIN AS SHOWN ON FLOOR
 PLAN AND HEATER DETAIL.
 11) SHT P-2 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED PER 607.3
 AND 607.3.2. PLEASE SHOW ON DETAIL.
 12) SHT P-2 PLEASE SUBMIT CALCULATIONS
 FOR WATER SUPPLY FOR FIXTURES. 3/4" FOR
 ALL FIXTURES.
 13) SHT P-3 "NOTE" STATES ALL INDIRECT
 WASTE TO FLOOR DRAINS, PLEASE SHOW ALL
 INDIRECT TO FLOOR SINKS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377