Plan Review Details - Permit 02101495
Plan Review Stops For Permit 02101495
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-24 Cont ID  
Sent By btrobaug Date 2002-10-24 Time 14:17 Rev Time 0.50
Received By btrobaug Date 2002-10-24 Time 14:08 Sent To  
Notes
2002-10-24 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION FOR
 THE EXISTING SERVICE.ALSO VERIFY THAT
 NAMEPLATE RATING MATCHES ASSUMED LOAD
 FOR THE ADDED SERVICE.
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 THESE ITEMS NEED TO BE SUBMITTED BEFORE
 ROUGH INSPECTION.IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392