Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-11-05 Cont ID  
Sent By hpiskura Date 2002-11-05 Time 11:13 Rev Time 0.00
Received By hpiskura Date 2002-11-05 Time 10:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By btrobaug Date 2002-10-21 Time 17:29 Rev Time 0.50
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-11-15 Cont ID  
Sent By mcarsill Date 2002-11-15 Time 14:34 Rev Time 0.00
Received By mcarsill Date 2002-11-15 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-19 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 08:39 Rev Time 0.00
Received By btrobaug Date 2002-12-19 Time 08:39 Sent To M
Notes
2002-12-19 00:00:00"M" IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-26 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 15:43 Rev Time 0.40
Received By pkrauss Date 2002-12-26 Time 15:24 Sent To  
Notes
2002-12-26 00:00:00CALLED CONTRACTOR - PERMIT PRINTED NEED
 ORIGINAL PERMIT APPLICATION & ADDITIONAL
 SET OF PLANS. LEFT MESSAGE 12-26-02.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-12-18 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 08:39 Rev Time 0.40
Received By pkrauss Date 2002-12-18 Time 09:05 Sent To  
Notes
2002-12-18 00:00:00INSUFFICIENT INFORMATION FOR REVIEW.
 PROVIDE THE FOLLOWING INFORMATION AND
 PLANS WITH MECHANICAL PERMIT APPLICATION
  
 PLAN SHEET A-1 HVAC GENERAL NOTES #7,
 OUTSIDE AIR REQUIREMENTS AS PER ASHRAE
 62-1989, PLEASE PROVIDE CALCULATION ON
 PLAN.INDICATE SIZE, MATERIAL AND
 LOCATION OF THE OUTSIDE AIR DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status I Date 2002-11-21 Cont ID  
Sent By pkrauss Date 2002-11-21 Time 15:47 Rev Time 0.40
Received By pkrauss Date 2002-11-21 Time 15:40 Sent To  
Notes
2002-11-21 00:00:00INSUFFICIENT INFORMATION FOR REVIEW.
  
 PLEASE PROVIDE INFORMATION ON THE
 OUTSIDE AIR.
  
 1.PROVIDE OUTSIDE AIR CALCS.
  
 2.INDICATE DUCT SIZE, MATERIAL, LAYOUT
 AND LOCATION OF INTAKE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-14 Cont ID  
Sent By kstevens Date 2002-12-14 Time 20:44 Rev Time 0.75
Received By kstevens Date 2002-12-14 Time 20:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-12 Cont ID  
Sent By kstevens Date 2002-11-12 Time 18:00 Rev Time 0.50
Received By kstevens Date 2002-11-12 Time 18:00 Sent To  
Notes
2002-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 ALL DEMO OF PLUMBING SHALL BE
 INSPECTED PRIOR TO COVERING.
 2) SHT A-1 WORK ROOM SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE
 PROVIDE A DETAIL.
 3) SHT A-1 TABLE 403.1 REQUIRES A DRINK-
 ING FOUNTAIN. PLEASE GIVE DETAIL FOR
 DRINKING FOUNTAIN SHOWING COMPLIANCE OF
 SECTION 11-4.15 AND ALL SUBSECTIONS.
 SECTION 11-4.1.3(10)(A) FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ALSO SEE SECTION 410.1.
 4) SHT A-1 PLEASE GIVE DIMENSIONS FOR
 BATHROOM. SHOW 5' TURNING RADIUS REQUIR-
 ED PER SECTION 11-4.22.3
 5) SHT A-1 SHOWER SHALL BE ACCESSIBLE.
 PLEASE PROVIDE DETAIL PER SEC 11-4.21
 AND ALL SUBSECTIONS.
 6) SHT A-1 WATER HEATER SHALL COMPLY
 WITH SECTION 504.7.1. DISCHARGE FROM
 RELIEF VALVE SHALL NOT ANY TRAPPED SECT-
 IONS AND SHALL HAVE A VISIBLE AIR GAP.
 ALSO SECTIONS 504.8 AND 504.8.1 HEATER
 EMERGENCY PAN AND DRAIN. PLEASE SHOW
 DETAILS.
  
 REVIEW BY KEN STEVENS