Plan Review Details - Permit 02101336
Plan Review Stops For Permit 02101336
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By hpiskura Date 2002-11-04 Time 15:49 Rev Time 0.00
Received By dpalmer Date 2002-11-04 Time 07:07 Sent To  
Notes
2003-01-13 00:00:00PASSED PER HHP.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-01-13 Cont ID  
Sent By dpalmer Date 2003-01-13 Time 12:39 Rev Time 0.75
Received By dpalmer Date 2003-01-13 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 07:07 Rev Time 1.00
Received By dpalmer Date 2002-12-19 Time 07:07 Sent To  
Notes
2002-12-19 00:00:00***************UNSAT ************
  
 1)NOTE: PLEASE NOTE, NOT ALL NOTES FROM
 PREVIOUS REVIEWS ARE COMPLETE, PLANS
 STILL SHOW A NEW? PANEL ON E-2 THAT IS
 NOT CLARIFIED??RISER DIAGRAM IS THE
 SMAE ONE SUBMITTED PREVIUOUSLY EXCEPT
 THERE IS NO D-1SHOWN THISTIME?
 PLEASE ONLY SHOW EQUIPMENT PERTAINING
 TO THIS SPACE.
  
 2)NOTE: PLEASE NOTE UNDER FS/FAC ANY
 ADDTIONAL PAPER SUBMITTED W/ARCH SEAL
 AND SIGNATURE MUST ALSO CONTAIN TITLE
 BLOCK AS REQ`D BY FS. 61G1-16.004.
 WORK MUST BE DONE BY ARCH OF RECORD.
  
 3)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. 215-3,230-42
  
 4)NOTE: PLEASE SEE LETTER ATTACHED WITH
 RESPECT TO DESIGN PROFESSIONALS.
 553.80(2) (B).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-11-21 Time 06:55 Rev Time 0.50
Received By dpalmer Date 2002-11-21 Time 06:55 Sent To  
Notes
2002-11-21 00:00:00************ UNSAT ****************
  
 ** PLEASE NOTE, NOT ALL NOTES FROM FIRST
 REVIEW WERE ADDRESSED AND NOW A COMPLETE
 -LY NEW RISER DRAWING WAS SUBMITTED ON
 E-3???
  
 1)NOTE: PLEASE NOTE, AIC RATINGS FOR
 ALL NEW EQUIPMENT. 110-9/215-5
 NEW RISER SHOWS NEW AND RELOCATED WORK
 WITH NO CLEAR VIEW ON WHERE ALL THESE
 ITEMS ARE LOCATED? PLEASE PROVIDE AN
 OVER VIEW FOR NEW/EXSITING ELECTRICAL
 ROOM(S) THAT THESE ITEMS ARE GOING IN.
 PLEASE NOTE A NEW PANEL IS BEING ADDED
 AND IS SHOWN ON E-1 BUT WHICH PANEL IS
 THIS ON RISER DIAGRAM?
 LOADS FROM DISC`S ARE SHOWN GOING BACK
 INTO A GUTTER THAT IS BEING TAPPED AGIAN
 ??
 PLEASE PROVIDE A SINGLE -LINEDIAGRAM
 THAT SHOWS LAYOUT.
 PLANS SHOW ONE NEW PANEL AND RISER SHOWS
 MORE?
  
 2)NOTE: PLEASE SHOW CIRCUITING AND
 CORRELATE W/ PANEL SCHEDULES AS NOTED
 ON FIRST REVIEW.
  
 3)NOTE: PLEASE SEE NOTE FROM FIRST
 REVIEW FOR CIRCUITING OF EM/EX LTS PER
 700-12E. THEY ARE SHOWN AS BEING ON
 SEPARATE CIRCUITS FROM LTS.
  
 4)NOTE:PLEASE CLARIFY WHERE RECEPT LOADS
 ARE IN LOAD CALCULATIONS. 220-13
 NOT FROM 220-11.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. IF AN APPOINTMENT IS NEEDED
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-10-24 Time 14:09 Rev Time 0.25
Received By dpalmer Date 2002-10-24 Time 14:09 Sent To  
Notes
2002-10-24 00:00:00*********** ***** UNSAT **************
  
 1)NOTE: PLEASE SSHOW CIRCUITING ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE, PANEL SCHEDULE IS
 SHOWN BLANK W/ NO INFORMATION??
 PLEASE PROVIDE INFORMATION FOR PANEL.
 PLANS SHOW NEW PANEL? WHERE, HOW IS
 PANEL BEING FED??
 215-5, SEE 110-9 AND SUBMIT AIC RATING
 FOR ANY NEW MAINS/PANELS.
  
 3)NOTE; PLEASE SEE 700-12 FOR CIRCUITING
 OF EM LTS AND EXIT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 08:46 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 08:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-10-31 Cont ID  
Sent By mcarsill Date 2002-10-31 Time 12:42 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 12:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 17:42 Rev Time 0.00
Received By btrobaug Date 2002-11-15 Time 17:40 Sent To  
Notes
2002-11-20 00:00:00TO COMM BOARD,# 49./WRT.