Plan Review Details - Permit 02101307
Plan Review Stops For Permit 02101307
Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-03-03 Cont ID  
Sent By jleahy Date 2006-03-03 Time 14:27 Rev Time 0.00
Received By jleahy Date 2006-03-03 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-02-07 Cont ID  
Sent By dpalmer Date 2006-02-07 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2006-02-07 Time 11:55 Sent To  
Notes
2006-02-07 00:00:00******* UNSAT ******
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE SEE NOTE # 4 FROM
 PREVIOUS REVIEW. PLEASE INDICATE THE KW
 RATINGS FOR POOL HEATERS.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 FIGURED AT 125%, POOL PUMP(S), POOL
 HEATER(S).
 PLEASE SEE LOAD SHOWN ON POOL PANEL IS
 ALREADY SHOWN AT 96A'S WHICH IS OF
 CONCERN WITH THE ADDED LOADS FROM
 ORIGINAL PLANS.
  
  
 2)NOTE: PLEASE INDICATE ALL THE KW
 RATINGS FOR A/C EITH CU'S OR AHU'S
 WHICHEVER LOAD IS GREATER.
 THE LOADS SHOWN ON THE PANEL SCHEDULE(S)
 MENTIONS THE LOADS ALREADY @65%, HOWEVER
 EACH AHU SEEMS TO BE ABOUT 5KW OR SO,
 WHICH @65% WOULD NOT BE THE LOADS SHOWN.
 215.5
  
 3)NOTE: PLEASE SEE ALL SUB PANELS ARE
 NOW INDICATED AS "GARAGE PANELS"?
 PLEASE CORRELATE THE IDENTIFICATION WITH
 RISER.
  
 4)NOTE: PLEASE SEE RISER NOW SHOWS A
 DISCONNECTING MEANS AHEAD OF THE GARAGE
 PANEL "E', YET PLANS DO NOT SHOW THIS
 DISCONNECT. PLEASE ALSO SEE RISER WHICH
 SHOWS A MCB IN PANEL AT GARAGE?
 PLEASE CORRLELATE.
 PLEASE SEE THE EQUIPMENT GROUNDING
 CONDUCTOR FROM PANEL "C" IN MAIN HOUSE
 IS NOW MISSING TO THE GARAGE PANEL "E".
 PLEASE SEE 250.32.
 AN EQUIPMENT GROUNDING CONDUCTOR IS
 REQUIRED; THE ONLY EXCEPTION IS IF THERE
 ARE COMPLETELY NO OTHER METAL PARTS
 CONNECTED BETWEEN BLDGS. THIS WOULD BE ,
 WATER PIPES, CATV, PHONE ETC.
 THE CHANCES OF THERE BEING NO METALS
 PATHS OR FUTURE PHONE ETCIS VERY
 UNLIKELY.
 PLEASE INCLUDE THE EQUIPMENT GROUND AS
 SHOWN ON PREVIOUS PLANS.
  
 5)NOTE: PLEASE SEE LOAD CALCUALTIONS
 PROVIDE DO NOT PROVIDE ENOUGH
 INFORMATION FOR REVIEW OF MINS'
 REQUIRED. PLEASE EITHER SHOW A BREAK
 DOWN OR INDICATE THE VA/KW ON PANEL
 SCHEDULES. ( SMALL APPL, LAUNDRY/WASHER,
 DRYER ETC ETC.
 220,215.5
  
 NEW NOTE:
  
 6)NOTE: PLEASE SEE GARAGE SHOWS A 220V
 RECEPT, HOWEVER THIS IS NOT ON PANEL
 SCHEDULE FOR GARAGE.
 215.5
  
 ** PLEASE KNOW, THIS OFFICE IS UNABLE TO
 VERIFY CORRECT OCP AND AWG FOR SOME
 CIRCUITS AS LOADS ARE NOT SHOWN OR GIVEN
 IN BREAKDOWN OF PANELS AND LOAD
 CALCULATIONS.
 PLEASE ALSO SEE DE-RATING OF SUB PANELS
 MAY NOT BE DONE FOR ALL MOTOR/HEAT LOADS
 .
  
  
 PELASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 07:11 Sent To PC
Notes
2006-01-20 00:00:00************ UNSAT ************
  
  
 1)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH PANEL SCHEDULES.
 PLEASE SEE LTS ON SMALL APPL, LTS ON
 DRYER, BATHS, KIT, APPLIANCES, ETC ETC.
 PLEASE SEE THERE ARE FAR TOO MANY TO
 WRITE UP OR REDLINE. PLEASE SEE MANY OF
 THESE WERE REDLINED, HOWEVER BY NO MEANS
 ALL.
  
 2)NOTE: PLEASE SEE SMOKE DETECTORS'S
 SHOWN ON THREE OR MORE CIRCUITS. PLEASE
 SEE NFPA-72 8-1 WHICH REQUIRES SD'S TO
 BE WIRED "IN-LINE". IF WIRED IN-LINE,
 THEN THESE CAN NOT BE ON MORE THAN ONE
 CIRCUIT. ALSO SHOWN ON MULTIPLE PANELS.
  
 3)NOTE: PLEASE SEE 210.52D,210.11C3,
 WHICH REQUIRES ALL BATH(S) CIRCUIT(S)
 RECEPTS TO BE ON A MIN OF 20A AND #`12.
 PLEASE SEE CIRCUITING AS MANY ARE SHOWN
 ON OTHER CIRCUITS WHICH ARE 15A AND #14
 AWG.
  
 4)NOTE: PLEASE CORRELATE ALL POOL
 EQUIPMENT ON PLANS WITH PANEL SCHEDULES
 AND LOAD CALCUALTIONS. PLEASE SEE
 CIRCUITING ON PLANS IS ALSO SHOWN AS
 COND UNITS.??
 PLEASE SEE PLANS SHOW TWO ELEC POOL
 HEATERS, HOWVER PANEL SCHEDULE SHOWS
 ONE??
 PLEASE ALSO SEE ALL CONTINUOUS LOADS
 SUCH AS POOL HEATER AND POOL PUMP SHALL
 BE SHOWN AT 125%. 215.3,230.42,
 PLEASE SEE MIN OCP SHALL BE SIZED AT
 125% PER 680.9. PLEASE PROVIDE KW
 RATINGS FOR POOL HEATERS.
  
 5)NOTE: PLEASE SEE PLANS, CLEARENCES FOR
 CU DISCONNNECTS DO NOT MEET 110.26.
 PLEASE ALSO SEE ANY AHU'S WHICH APPEAR
 TO SHOW SHELVING DIRECTLY INFRONT OF
 THESE DISCONNECTS AND UNITS.
  
 6)NOTE: PLEASE SEE CORRELATE PANEL
 SCHEDULES AND RISER DIAGRAM. PLEASE SEE
 ALL PANELS INDICATE MAINS (A
 GARAGE PANEL REQUIRED) HOWEVER PANELS
 FOR POOL PANEL AND PANEL C SHOWS MLO ON
 SCHEDULE AND SHOWS MAIN DISCONNECT ON
 RISER?? PLEASE CORRELATE.
 215.5
  
 7)NOTE: PLEASE SEE PLANS SHOWS POOL
 PANEL AND A PANEL "D"??
 PLEASE CORRELATE.215.5
  
 8)NOTE: PLEASE SEE CIRCUITS SHOWN ON
 PLANS AS GEN LTS, PELASE SEE CIRCUITING
 SHALL BE SPECIFIC TO AREA/ROOMS.
 215.5, 408.4
  
 9)NOTE: PLEASE SEE KITCHEN AREA WHERE
 APPEARS TO BE A MISSING COUNTERSPACE GFI
 RECEPT. 210.52C1
 SEE CIRCUITING, REDLINED.
  
 10)NOTE: PLEASE SEE ALL RECEPTS SERVING
 KITCHEN/KITCHEN AREA COUNTERSPACE ARE TO
 BE GFI/GFI PROTECTED.
  
 11)NOTE: PLEASE INDICATE THE KW RATINGS
 FOR AHU'S AND HEAT BEING USED FOR LOAD
 CALCS.
 215.5.
  
 12)NOTE: PLEASE SEE PANEL "B" WHICH
 INDICATES A SEPARATE OVEN AND A SEPRATE
 RANGE, HOWEVER LOAD CALCS SEEMT O ONLY
 SHOW 8KW FOR BOTH UNITS??
 PLEASE VERIFY AND ADJUST AS CIRCUITS
 SEEM TO BE FOR MORE THAN 8KW FOR BOTH.
 215.5, 220
  
 13)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS STILL BEING SHOWN
 FROM METER TO THE FIRST MEANS OF
 DICCONNECT. PLEASE SEE 250.6, 250.24 THE
 "EQUIPMENT GROUNDING CONDUCTOR" IS ONLY
 INSTALLED "AFTER" THE FIRST MEANS OF
 DISCONNECT.
  
 PLEASE BE SURE TO CORRELATE ALL
 CIRCUITING ON PLANS WITH PANEL
 SCHEDULES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND STAMPING. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-10-13 Cont ID  
Sent By dpalmer Date 2005-10-13 Time 11:11 Rev Time 0.40
Received By dpalmer Date 2005-10-13 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-09-30 Cont ID  
Sent By dpalmer Date 2005-09-30 Time 15:34 Rev Time 0.33
Received By dpalmer Date 2005-09-30 Time 15:20 Sent To  
Notes
2005-09-30 00:00:00****** UNSAT ******
  
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULES.
 PLEASE SEE PANEL "A" IS SHOWN FEEDING
 BOTH SUB PANELS, HOWEVER RISER INDICATES
 ONE SUB PANEL FROM "A" AND ONE FROM
 "B"??
  
  
 2)NOTE: PLEASE SEE TWO NEW MAIN
 DISCONNECTS ADDED TO RISER.
 PLEASE SUBMIT AIC RATINGS FOR NEW MAINS
 PER 110.9, 215.5
 PLEASE NOW SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS "A" AND "B".
 250.110, 250.24, 250.122
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-09-14 Cont ID  
Sent By dpalmer Date 2005-09-14 Time 09:50 Rev Time 0.00
Received By dpalmer Date 2005-09-14 Time 09:37 Sent To  
Notes
2005-09-14 00:00:00****** UNSAT ********
  
 1)NOTE: PLEASE SEE PANEL SCHEDULES NOW
 SUBMITTED ONLY INDICATE THE ITEM AND
 CIRCUIT NUMBER.
 PLEASE SEE MISSING OVERCURRENT
 PROTECTIVE DEVICE FOR EACH.
 SUB-PANELS ETC.
 PLEASE SEE MISSING CONDUCTOR SIZES FOR
 EACH.
 PLEASE SEE THE PANEL SCHEDULES AS SHOWN
 ON PLANS, WOULD IN-FACT BE WHAT MAY BE
 INSIDE THE PANEL AT JOB-SITE.
  
 2)NOTE: PLEASE SEE THAT LOAD
 CALCULATIONS ARE NOW MISSING FROM EACH
 OF THE PANEL SCHEDULES AND ONLY THE LOAD
 IS SHOWN FOR THE SERVICE.
 CAN NOTVERIFY CONDUCTORSIZES ETC.
 220., 215.5,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-10-20 Cont ID  
Sent By csiegber Date 2004-10-07 Time 15:00 Rev Time 0.50
Received By dpalmer Date 2003-10-20 Time 06:26 Sent To P
Notes
2003-10-20 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE THAT ONE SET OF PLANS
 HAVE COME FOR A RE-STAMP, YET PLANS
 HAS CHANGES ON PLANS, THEREFORE MAKING'
 THESE "REVISIONS".
 PLEASE SEE THAT ONLY ONE SET WAS SUB-
 -MITTED FOR STAMPING AND TWO SETS REQ'D
 DUE TO REVISIONS.
  
 2)NOTE: PLEASE ALSO SEE PLANS NEED TO BE
 SIGNED, DATED AND SEALED BY THE ARCH OF
 RECORD. FAC 61G1-16.004, FS 481.221.
  
 3)NOTE: PLEASE SEE RISER, LAST REV
 CONTAINED CONDUCTOR SIZE FROM GUTTTER
 TO DISC FOR ELEVATOR. PLEASE SEE THIS IS
 NOW MISSING.? PLEASE CORRECT.SEE 240.21
 FOR TAPPED CONDUCTORS.
 4)NOTE: PLEASE CLARIFY GFI RECEPT REQ'D
 FOR A/C COND UNITS. 210.63
  
 5)NOTE: PLEASE SEE PLANS, HIGHLIGHTED
 FOR RECEPTS MISSING PER 210.52.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. REVISIONS FEES ARE NOW DUE FOR
 ELECTRICAL PLANS. PLEASE ALSO SEE NOTES
 FROM OTHER REVIEWERS AND FEE THAT MAY
 BE DUE FOR OTHER TRADES ALSO.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-09-26 Cont ID  
Sent By csiegber Date 2003-10-16 Time 09:42 Rev Time 0.75
Received By dpalmer Date 2003-09-26 Time 10:53 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-07-31 Cont ID  
Sent By csiegber Date 2003-09-24 Time 15:22 Rev Time 1.00
Received By dpalmer Date 2003-07-31 Time 11:34 Sent To P
Notes
2003-07-31 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS. RISER SHOWS PANELS AS MCB
 AND PANEL SHOWN AS MLO?
  
 2)NOTE: PLEASE ALSO SEE LOAD CALCULATION
 -S, PLEASE RECONFIGURE AND CLARIFY
 SUB PANEL AND TOTAL LOAD ON SERVICE.
 500MCM ID GOOD FOR 380A'S PER 310-16.
 PLEASE SEE THAT 310-15 B6 MAY BE USED
 BUT STOPS AT 400MCM FOR A 400A SERVICE.
 460A SERV SHOWN.
 PLEASE ALSO CLARIFY WHERE SUB PANEL,
 PANEL SCHEDULE IS?
  
 3)NOTE: PLEASE SUBMIT REVISED PLANS, IN
 ORDER TO VERIFY SERVICE AND LOCATIONS
 OF PANELS.
  
 4)NOTE: PLEASE SHOW ALL REVISIONS WITH
 CLOUDS AND TRIANGLES.
  
 5)NOTE: PLEASE SEE MISSING CONDUCTOR
 SIZES ON RISER FOR SUB PANEL FROM GUTTER
 PER 240-21 .
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FOR ELEV MOTOR,
 250-110/250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-21 Cont ID  
Sent By alange Date 2003-07-30 Time 16:25 Rev Time 1.00
Received By dpalmer Date 2003-01-21 Time 08:38 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 18:00 Rev Time 1.50
Received By dpalmer Date 2002-11-05 Time 12:20 Sent To B
Notes
2002-11-05 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CORRELATE AHU`S ON MECH
 PLANS W/ UNITS SHOWN ON ELECTRICAL
 PLANS. PLEASE NOTE CIRCUITING NEED TO
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
 PLEASE NOTE FOUR AHU`S ARE SHOWN ON
 PLANS AND ONLY THREE CU`S ?
 PLEASE CLARIFY
  
 2)NOTE: PLEASE NOTE DISCONNECT FOR
 ELEVATOR EQUIPMENT MUST BE SERVICE
 ENTRANCE RATED AND SUBMIT AIC RATING FOR
 DISC. 215-5,110-9
  
 3)NOTE: PLEASE CLARIFY SIZE OF COLD
 WATER PIPE ON RISER DIAGRAM 3/9"?
  
 4)NOTE: PLEASE SHOW ROOM DESIGNATION ON
 PLANS.
  
 5)NOTE: PLEASE NOTE CLEARENCE FOR CU
 DISC`S PER 110-26
  
 6)NOTE: PLEASE NOTE PANELS ARE SHOWN
 W/OUT MCB`S? 225-31/240/ RISER SHOWS
 2P/200`S
 7)NOTE: PLEASE NOTE LOAD CALCULATIONS
 DO NOT INCLUDE SAUNA EQUIPMENT/LOADS?
 PLEASE CORRELATE.
  
 8)NOTE: PLEASE NOTE , PANEL SCHEDULE
 ONLY SHOWS ONE WATER HEATER? PLEASE
 CLARFIY, SECOND WATER HEATER AT 1500W?
  
 9)NOTE:PLEASECLARIFY LOADS SHOWN FOR
 A/C CU`S.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 16:28 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 16:28 Sent To E
Notes
2006-02-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 14:49 Sent To E
Notes
2006-01-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 13:49 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 13:49 Sent To E
Notes
2005-10-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 15:02 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 15:02 Sent To E
Notes
2005-09-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 13:57 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 13:57 Sent To B
Notes
2005-09-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-12-06 Cont ID  
Sent By mjacobs Date 2004-12-06 Time 16:18 Rev Time 0.00
Received By mjacobs Date 2004-12-06 Time 16:18 Sent To M
Notes
2004-12-06 00:00:00SENT TO "M/AC" BOX./REV.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 14:49 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 14:49 Sent To B
Notes
2004-11-08 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 15:00 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 15:00 Sent To E
Notes
2004-10-07 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:38 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:38 Sent To B
Notes
2004-08-24 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 09:42 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 09:41 Sent To E
Notes
2003-10-16 00:00:00TO DP DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 15:22 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 15:22 Sent To E
Notes
2003-09-24 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 16:25 Rev Time 0.00
Received By alange Date 2003-07-30 Time 16:25 Sent To E
Notes
2003-07-30 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-30 Cont ID  
Sent By mmclean Date 2003-07-30 Time 12:30 Rev Time 0.00
Received By alange Date 2003-07-25 Time 10:11 Sent To  
Notes
2003-07-25 00:00:00TO ROB M DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 10:30 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 10:30 Sent To B
Notes
2003-03-13 00:00:00SENT TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 11:02 Sent To M
Notes
2003-03-06 00:00:00TO MECH INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-16 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 18:00 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 18:00 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2003-01-06 Time 17:35 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2004-12-16 Time 13:42 Sent To  
Notes
2004-12-16 00:00:00CALLED MECHANICAL CONTRACTOR -
 MECHANICAL REVISION CANNOT BE APPROVED
 UNIL THE ARCHITECT REVISES HIS DESIGN.
 ARCHITECT INDICATES RADIATION DAMPERS.
  

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2004-10-28 Cont ID  
Sent By pkrauss Date 2004-10-28 Time 06:45 Rev Time 0.35
Received By pkrauss Date 2004-10-27 Time 16:28 Sent To R
Notes
2004-10-28 00:00:00PROVISO:
 AS PER 1ST REVIEW -
 1.PLAN SHEET M.3 FLEXIBLE DUCT
 CONNECTION DETAIL, THIS DETIAL DOES NOT
 INDICATE OR REFERENCE THE REQUIREMENT
 FOR A FIRE DAMPER THAT IS DETAILED ON
 PLAN SHEET A.5.
  
 2.PLAN STILL DOES NOT INDICATE TOILET
 EXHAUST TERMINATIONS AS SCREENED.THIS
 IS REQUIRED ON EXHAUST WITH THE
 EXCEPTION BEING FOR THE DRYER AND HOOD
 EXHAUST.2001 FBC(M) 401.6, 504.4 &
 505.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2003-10-30 Cont ID  
Sent By pschmitz Date 2004-10-23 Time 14:50 Rev Time 0.40
Received By pkrauss Date 2003-10-30 Time 14:39 Sent To R
Notes
2003-10-30 00:00:00ONLY ONE SET OF PLANS SUBMITTED.THIS
 SUBMITTAL IS A REVISION, PLEASE PROVIDE
 ADDITIONAL COPY FOR OUR RECORDS.AS PER
 2001 FBC 104.2.1.
  
 PLANS ARE NOT SIGNED, SEALED OR DATED
 AS REQUIRED BY F.S. 481.221.PLANS
 OTHERWISE ARE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-08-09 Cont ID  
Sent By kstevens Date 2003-10-25 Time 06:13 Rev Time 0.50
Received By hmoser Date 2003-08-09 Time 09:08 Sent To  
Notes
2003-08-09 00:00:003ED FLOOR REVISION ONLEY.NO MECHANICAL
 CHANGE ON REVISED PLAN.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-03-10 Cont ID  
Sent By kstevens Date 2003-08-04 Time 12:46 Rev Time 0.40
Received By pkrauss Date 2003-03-10 Time 10:32 Sent To  
Notes
2003-03-10 00:00:00PROVISO:
  
 RADIATION DAMPERS REQUIRED, SEE PLAN
 SHEET A.5 FOR DETAIL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-03-06 Cont ID  
Sent By pkrauss Date 2003-03-06 Time 12:33 Rev Time 0.45
Received By pkrauss Date 2003-03-06 Time 12:19 Sent To  
Notes
2003-03-06 00:00:00DENIED:
  
 PLEASE NOTE, ONE SET OF PLANS WERE
 INADVERTENTLY STAMPED.DENIED COMMENTS
 WERE ATTACHED TO THE RESUB APPLICATION.
  
 PLEASE ADDRESS THE FOLLOWING:
 PLAN SHEET A.1 NOTE INDICATES ONE HOUR
 PROTECTION W/UL DESIGN L521 THROUGHOUT.
  
 THE MECHANICAL PLANS DO NOT REFLECT THIS
 TYPE OF CONSTRUCTION.PLEASE PROVIDE
 INFORMATION ON THE PROTECTION FOR THE
 HVAC SYSTEMS.ITEMS #4 & 5 IN THE UL
 L521 LISTING, INDICATE UL CLASS 0 OR 1
 FOR THE DROPS.
  
 PLEASE REFLECT THE ASSEMBLY ON THE
 MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 11:03 Rev Time 1.45
Received By pkrauss Date 2003-01-21 Time 09:39 Sent To R
Notes
2003-01-21 00:00:00PLAN SHEET A.1 NOTE INDICATES ONE HOUR
 PROTECTION W/UL DESIGN L 521 THROUGHOUT.
  
 THE MECHANICAL PLANS DO NOT REFLECT THIS
 TYPE OF CONSTRUCTION.PLEASE PROVIDE
 INFORMATION ON THE PROTECTION FOR THE
 HVAC SYSTEMS. ITEMS #4 & 5 IN THE UL L
 521 INDICATE UL CLASS 0 OR 1 FOR THE
 DUCTWORK & CEILING DAMPERS REQUIRED FOR
 THE DROPS.
  
 PLEASE CLARIFY THE ASSEMBLY ON THE
 MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-03 Cont ID  
Sent By hmoser Date 2002-11-03 Time 10:21 Rev Time 0.50
Received By hmoser Date 2002-11-03 Time 10:21 Sent To E
Notes
2002-11-03 00:00:00PASS/PROVISO
 1) NEED MODEL NUMBERS OF ALL THREE
 EVAPORATOR COILS FOR FINAL
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-10-23 Cont ID  
Sent By pschmitz Date 2004-10-23 Time 14:49 Rev Time 0.00
Received By pschmitz Date 2004-10-23 Time 14:49 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-10-25 Cont ID  
Sent By kstevens Date 2003-10-25 Time 05:53 Rev Time 0.75
Received By kstevens Date 2003-10-25 Time 05:53 Sent To M
Notes
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1) ONE SET OF PLANS SUBMITTED FOR RE-
 STAMP, BUT NUMERIOUS CHANGES ARE NOTED.
 REVISIONS REQUIRE 2 SETS OF SIGNED AND
 SEALED PLANSSECTION 104.2.1
 FAC 61G1-16.004 - FS 481.221.
  
 2) IT APPEARS THAT A PLUMBING REVISION
 WAS APPROVED ON 8-4-3 BUT THAT REVISION
 WAS PICKED UP ON 8-14-3 BECAUSE OTHER
 TRADES DENIED THEIR PART OF THE REVISION
 REVISION WAS NEVER RETURNED WITH THE
 REVISION SUBMITTED 9-24-3 SO NO COPY OF
 THE PLUMBING REVISION IS ON FILE WITH
 THE CITY OF WPB.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-04 Cont ID  
Sent By dpalmer Date 2003-10-20 Time 06:28 Rev Time 0.50
Received By kstevens Date 2003-08-04 Time 12:46 Sent To M
Notes
2003-08-04 00:00:00REVISION OKCHANGED LOCATION OF TUB
 CHANGED SAUNA TO SHOWER - CHANGED LOCAT-
 ION OF LAV - THIRD FLOOR

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2003-07-31 Time 11:57 Rev Time 0.50
Received By jleech Date 2002-10-31 Time 17:08 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 8 Status N Date 2004-11-10 Cont ID  
Sent By pkrauss Date 2004-10-28 Time 07:04 Rev Time 1.00
Received By rmcdouga Date 2003-11-05 Time 14:17 Sent To  
Notes
2003-11-05 00:00:00RESTAMP DENIED
  
 1) PLANS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE ARCHITECT.
  
 2) SHEET A3 DOES NOT SPECIFY THE CORRECT
 UL NUMBER FOR THE ONE HOUR STEEL COLUMN
 ASSEMBLY.
  
 3) TWO OF THE DETAILS ON S5 ARE NUMBERED
 INCORRECTLY.
  
 IN ORDER TO RESTAMP PLANS THEY MUST
 MATCH THE APPROVED PLANS ON FILE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop R ROOF PLAN REVIEW
Rev No 7 Status P Date 2003-11-05 Cont ID  
Sent By rmcdouga Date 2003-11-05 Time 14:14 Rev Time 2.00
Received By rmcdouga Date 2003-11-05 Time 14:14 Sent To  
Notes
2003-11-05 00:00:00REVISIONS TO SHEETS A1 THROUGH A6 AND
 S1 THROUGH S5 ARE OK.

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status F Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-30 Time 14:54 Rev Time 2.50
Received By rmcdouga Date 2003-10-01 Time 13:01 Sent To  
Notes
2003-10-01 00:00:00REVISION DENIED
  
 1) ON SHEET S3 DETAILS 1 AND 2 HAVE BEEN
 ADDED, BUT ARE NOT CLOUDED. THE TYPICAL
 CONNECTOR DETAIL HAS BEEN REMOVED.
  
 2) ON S5 THE ADDED DETAILS AND ELEVATION
 CHANGE ARE NOT CLOUDED. DETAIL TAGS FOR
 1 AND 2 ON S5 ARE USED TWICE. PLEASE
 CORRECT TO AVOID CONFUSION.
  
 3) THE LOCATIONS FOR BALCONY SECTIONS 1
 AND 2 ON S3 ARE NOT INDICATED ON THE
 FLOOR PLANS. THEY ARE NOT CLOUDED.
  
 4) A REVISED SHEET S2 FOR THE ROOF AND
 3RD FLOOR PLAN WAS NOT SUBMITTED.
  
 5) A REVISED SHEET A5 WITH THE NEW
 ELEVATIONS SHOULD BE SUBMITTED.
  
 6) REVISED SHEET A3 SPECIFIES UL DESIGN
 X637 FOR THE STEEL COLUMNS. THIS DESIGN
 IS FOR ROUND PIPE COLUMNS. THE PLANS
 SPECIFY TUBE COLUMNS. PLEASE SPECIFY AN
 APPROPRIATE UL SYSTEM TO ACHIEVE THE ONE
 HOUR FIRE RATING.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS. ROOFING WAS NOT PART
 OF THE ORIGINAL PERMIT, BUT WAS ADDED
 WHEN CONTRACTOR WAS CHANGED.
  
 8) THE REVISED ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER OR HIS AGENT.
  
 IF YOU HAVE QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2003-07-28 Cont ID  
Sent By rmcdouga Date 2003-07-28 Time 13:55 Rev Time 4.00
Received By rmcdouga Date 2003-07-28 Time 13:55 Sent To  
Notes
2003-07-28 00:00:00REVISION DENIED BY BUILDING
  
 1) SHEET A2 SPECIFIES 10-3/4" STAIR
 TREADS AND SECTION A ON A6 SPECIFIES
 10-1/2" TREADS. PLEASE CORRECT. MUST
 COMPLY WITH FBC 1007.3(1), THE SUM OF
 TWO RISERS AND A TREAD EXCLUSIVE OF THE
 NOSING SHALL BE NOT LESS THAN 24" NOR
 MORE THAN 25".
  
 2) SUBMIT REVISED ENERGY CALCULATIONS
 WHICH INCLUDE THE ADDITIONAL AREA AND
 GLAZED AREA.
  
 3) SHEET A3 APPEARS TO HAVE A TYPO AT
 THE DUMD WAITER. THE PLAN HAS DUMP WATER
 PLEASE CORRECT.
  
 4) THE OPENINGS IN THE NORTH WALL OF THE
 STAIRWELL THAT IS 17'-3" FROM THE
 PROPERTY LINE EXCEEDS 40% OF WALL AREA
 ALLOWED AS OPENINGS BY TABLE 600. PLEASE
 CORRECT.
  
 5) SPECIFY THE HEIGHT, ATTACHMENTS, AND
 COMPLIANCE WITH FBC 2405.5 FOR THE GLASS
 GUARDRAIL AT THE THIRD FLOOR BALCONY ON
 THE WEST ELEVATION. SUBMIT CALCULATIONS
 AND SHOP DRAWINGS AT THIS TIME OR APPLY
 UNDER SEPARATE PERMIT.
  
 6) THE EXTERIOR DOOR TO THE PANTRY DOES
 NOT HAVE AN ID TAG ON SHEET A2.
  
 7) THE NEW EXTERIOR DOOR TO THE PANTRY
 IS NOT CLOUDED ON S1.
  
 8) THE INTERNAL PRESSURE COEFFICIENT IS
 NOT INDICATED AS + OR - ON S3. PLEASE
 CORRECT.
  
 9)CORRECT THE FONT ON TYPICAL SC1 DETAIL
 ON S4, IT IS DIFFICULT TO READ.
  
 10) THE ROOF ELEVATIONS ON A5 AND S5 DO
 NOT CORRESPOND. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2003-03-14 Cont ID  
Sent By rmcdouga Date 2003-03-14 Time 10:38 Rev Time 3.00
Received By rmcdouga Date 2003-03-14 Time 10:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2003-03-10 Cont ID  
Sent By rmcdouga Date 2003-03-10 Time 08:47 Rev Time 3.00
Received By rmcdouga Date 2003-03-10 Time 08:47 Sent To  
Notes
2003-03-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE LOCATIONS AND MATERIALS
 USED FOR DRAFTSTOPPING THE FLOOR/CEILING
 ASSEMBLIES PER FBC 2305.2.2. SINGLE
 FAMILY DWELLINGS. IN FLOOR/CEILING
 ASSEMBLIES SEPARATING USEABLE SPACES
 INTO TWO OR MORE APPROXIMATE AREAS WITH
 NO GREATER THAN 500 SQ FT. DRAFTSTOPPING
 SHALL BE PROVIDED PARALLEL TO THE MAIN
 FRAMING MEMBERS.
  
 3) THE NEW SHEETS OF DRAWINGS DO NOT
 HAVE THE EMBOSSED SEAL OF THE DESIGNER
 OF RECORD.
  
 4) THE TABLE OF DESIGN PRESSURES ON A6
 DOES NOT CORRESPOND WITH THE REST OF THE
 PLANS FOR OPENING MARKS, PRESSURES, ETC.
 NOTE: THE CITY OF WPB IS LOCATED IN A
 140 MPH WIND ZONE.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR FIXED GLASS WINDOWS LARGER
 THAN 50 SQ FT. THIS IS THE MAXIMUM SIZE
 COVERED BY THE PRODUCT APPROVAL THAT WAS
 SUBMITTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2003-01-29 Cont ID  
Sent By pkrauss Date 2003-01-30 Time 08:05 Rev Time 5.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-01-29 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 THIS INFORMATION IS REQUIRED TO BE ON
 THE SIGNED AND SEALED CONSTRUTION
 DRAWINGS. A PAPER STAPLED TO THE
 DRAWINGS IS NOT ACCEPTABLE.
  
 4) SPECIFY THE LOCATIONS AND MATERIALS
 USED FOR DRAFTSTOPPING THE FLOOR/CEILING
 ASSEMBLIES PER FBC 2305.2.2.
  
 5) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE, AN ELEVATION CERTIFICATE
 WILL BE REQUIRED. INDICATE THE PROPOSED
 GROUND FLOOR FINISH ELEVATION BASED ON
 N.G.V.D., NOT MEAN SEA LEVEL. NOTE: THE
 CITY CODE REQUIRES THE LOWEST FLOOR TO
 BE A MINIMUM OF SIX INCHES ABOVE BASE
 FLOOD ELEVATION.
  
 6) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE A SOIL TEST REPORT FROM A
 SOIL ENGINEER. PROVIDE SUBSURFACE SOIL
 INVESTIGATION COMPLETE WITH SOIL BORINGS
 AND RECOMMENDATIONS.
  
 7) STAIRS DO NOT COMPLY WITH FBC 1007.3
 SEE STAIR SECTION A ON A6, WHICH THE
 SUM OF TWO RISERS AND A TREAD (EXCLUSIVE
 OF THE NOSING) IS 23.75". INDICATE THE
 DIMENSIONS OF THE HANDRAIL ON THE PLANS.
 SEE FBC 1007.5.3.
  
 8) CANOPY WILL REQUIRE A SEPARATE PERMIT
 AS INDICATED ON THE PLANS.
  
 9) BALCONY GUARDRAILS WILL REQUIRE A
 SEPERATE PERMIT AS INDICATED ON THE
 PLANS.
  
 10) INDICATE ON THE PLANS THAT THE WIRE
 MESH IN THE SLAB WILL BE SUPPORTED BY
 APPROVED MATERIALS OR SUPPORTS AT
 SPACINGS NOT TO EXCEED THREE FEET. SEE
 FBC 1909.3.
  
 11) SPECIFY THE CONNECTORS AND UPLIFTS
 FOR THE GIRDER TRUSSES INDICATED ON THE
 ROOF PLAN.
  
 12) SPECIFY HOW THE REQUIRED ONE HOUR
 FIRE PROTECTION WILL BE PROVIDED FOR THE
 STEEL COLUMNS.
  
 13) SHEET S2 SHOWS A 4" COLUMN ON THE
 THIRD FLOOR BETWEEN TWO SLIDING GLASS
 DOORS WITH A WOOD GIRDER TRUSS ABOVE AND
 BELOW. PROVIDE DETAILS INDICATING THE
 ATTACHMENT AT THE BASE AND CAP, COLUMN
 TYPE, FIRE PROTECTION, ETC.
  
 14) PROVIDE A COVER SHEET FOR THE SHEAR
 WALL CALCULATIONS. PROVIDE THE TITLE
 BLOCK FOR THE ENGINEER (AND PHONE #),
 THE DESIGN CRITERIA THE CALCULATIONS ARE
 BASED ON, THE ADDRESS OF THE JOB, THE
 CONCLUSIONS THAT WERE REACHED.
  
 15) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS WIDER THAN 8 FEET
 - SINGLE HUNG WINDOWS
 - FIXED GLASS WINDOWS WHICH INCLUDE
 RECTANGULAR SHAPES UP TO 58 SQ.FT.
  
 16) THE NOTE ON A6 STATES THAT
 HURRICANE SHUTTERS ARE REQUIRED, HOWEVER
 NO STORM PANEL INFORMATION WAS SUBMITTED
 THE PRODUCT APPROVALS SUBMITTED ARE FOR
 IMPACT RESISTANT OR NON-IMPACT RESISTANT
 GLASS. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-11-27 Cont ID  
Sent By pkrauss Date 2003-01-21 Time 09:59 Rev Time 6.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-26 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) THREE STORY R-3 TYPE V STRUCTURE IS
 REQUIRED TO BE FIRE SPRINKLED OR BE ONE
 HOUR FIRE PROTECTED. SEE FBC TABLES 500
 AND 600.
  
 5) SPECIFY LOCATIONS AND MATERIALS USED
 FOR DRAFTSTOPPING AT THE FLOOR/CEILING
 ASSEMBLIES. SEE FBC 2305.2.2
  
 6) SPECIFY FIREBLOCKING AS REQUIRED IN
 CONCEALED SPACES. SEE FBC 705.3.1 AND
 2305.1.
  
 7) REVISE NOTES ON SHEET A1 UNDER
 SECURITY & FORCED ENTRY PREVATION THAT
 REFERENCE THE SFBC. THE CURRENT CODE IS
 THE FLORIDA BUILDING CODE.
  
 8) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED. INDICATE THE PROPOSED
 FINISHED FLOOR ELEVATION. THE MINIMUM
 ELEVATION IS 7.5 FEET.
  
 9) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SOIL TEST REOPRT FROM SOILS
 ENGINEER. SOIL MUST HAVE A BEARING
 CAPACITY OF 3000 PSF PER PLANS.
  
 10)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 SAFETY GLASS IS REQUIRED WITHIN THREE
 FEET HORIZONTALLY OF A TUB OR SHOWER.
  
 11) PROVIDE AT LEAST ONE BATHROOM ON THE
 GROUND FLOOR WITH A DOOR THAT HAS A 29"
 CLEAR OPENING. SEE FBC 11-11. MUST BE
 FULL BATH, UNLESS ONLY A HALF BATH IS
 PROVIDE AT GRADE LEVEL.
  
 12) PROVIDE DETAILS OF STAIRS. SHOW
 COMPLIANCE WITH FBC 1007.3 EXCEPTION (1)
 WHICH REQUIRES THE SUM OF 2 RISERS AND A
 TREAD (EXCLUSIVE OF THE NOSING) TO BE
 NOT LESS THAN 24" NOR MORE THAN 25".
 SPECIFY HANDRAILS AS REQUIRED BY FBC
 1007.5 AND INDICATE HANDRAIL DIMENSIONS
 THAT COMPLY WITH 1007.5.3.
  
 13)1007.8.1 WINDERS SHALL HAVE A
 MINIMUM TREAD DEPTH OF 6" AT THE NARROW-
 EST EDGE & SHALL HAVE A MINIMUM TREAD
 DEPTH OF 11" AT A POINT 12" FROM THE
 NARROW EDGE. WINDERS SHALL BE PERMITTED
 TO BE USED AS A COMPONENT IN MEANS OF
 EGRESS WITHIN A DWELLING UNIT.
  
 14) FBC 2305.1.4 REQUIRES FIREBLOCKING
 AT CONCEALED SPACES BETWEEN STAIR
 STRINGERS AT THE TOP AND BOTTOM OF RUNS.
 INDICATE THE LOCATIONS AND MATERIALS TO
 BE USED.
  
 15) ON SHEET A2 THE STAIR INFORMATION
 GIVEN FOR THE GROUND FLOOR AND SECOND
 FLOOR APPEARS TO BE REVERSED. PLEASE
 CORRECT.
  
 16) PROVIDE STRUCTURAL DETAILS FOR THE
 ALUMINUM CANOPY OR APPLY UNDER SEPARATE
 PERMIT. INDICATE DIMENSIONS, ATTACHMENT
 DETAILS, FASTENERS, ENGINEERING,
 WINDLOADS, ETC.
  
 17)2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR. WINDOWS IN BEDROOM 1 DOES
 NOT COMPLY WITH NET CLEAR OPENING HEIGHT
  
 18) PROVIDE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE PRE-FAB FIRE
 PLACE.
  
 19) PROVIDE STRUCTURAL DETAILS AND
 ENGINEERING FOR THE GLASS AND ALUMINUM
 BALCONY GUARDRAILS. INDICATE ATTACHMENTS
 AT WALLS AND FLOOR, FASTENERS, ETC.
  
 20) GLASS USED FOR GUARDRAILS SHALL
 COMPLY WITH FBC 2405.5.
  
 21) GUTTERS AND LEADERS SHALL BE SIZED
 AND DISCHARGED IN ACCORDANCE WITH FBC
 PLUMBING CODE PER 1503.4.3.
  
 22) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 23) SPECIFY TERMITE PROTECTION PER FBC
 1816.1.
  
 24) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
 SPECIFY ON PLANS.
  
 25) 1707.4.4.2 WHERE BUCK THICKNESS IS
 LESS THAN 1-1/2" WINDOW AND DOOR SHALL
 BE ANCHORED THROUGH THE BUCK DIRECTLY TO
 THE SUBSTRATE. REVISE BUCK DETAILS.
  
 26) PROVIDE HURRICANE ANCHOR SCHEDULE &
 INDICATE THE LOADS TO BE RESISTED.
  
 27) INDICATE CONNECTIONS FOR WOOD
 GIRDERS AT WALLS, COLUMNS, ETC.
  
 28) PROVIDE STRUCTURAL DETAIL FOR
 PARAPET WALLS.
  
 29) PROVIDE STRUCTURAL DETAILS FOR THE
 CONCRETE BALCONIES. INDICATE SIZES,
 SPACING OF STEEL REINFORCEMENT, ETC.
  
 30) THE FOOTING AND COLUMN SCHEDULES DO
 NOT CORRESPOND WITH THE I.D. TAGS GIVEN
 ON THE PLANS.
  
 31) PROVIDE DETAILS OF THE STEEL COLUMNS
 INDICATE ATTACHMENTS AT TOP AND BOTTOM
 OF COLUMNS, FASTNERS ETC.
  
 32) SPECIFY THE TIE BEAMS SIZE, STEEL
 REINFORCEMENT, ETC. AT EACH FLOOR.
  
 34) PROVIDE A DETAIL INDICATING THE
 FRAMING THAT WILL BE USED TO SUPPORT THE
 FLOOR AND CARRY THE CEILING AT THE WALLS
 THAT PARALLEL THE FLOOR/CEILING JOISTS.
  
 35) SPECIFY THE EMBEDDMENT DEPTH OF THE
 WEDGE ANCHORS AT THE 2X8 LEDGER AT THE
 WALL SECTION ON A5.
  
 36) REVISE GENERAL NOTE A ON 5.3 TO
 REFERENCE THE FBC.
  
 37) SHEET A3 SHOWS A WOOD DECK OVER A
 CONCRETE SLAB AND S2 SHOWS WOOD TRUSSES
 IN THE SAME AREA. PLEASE CLARIFY.
 INDICATE HOW THIS AREA WILL BE MADE
 WATER TIGHT, HOW DECK WILL BE FASTENED
 TO CONCRETE, ETC.
  
 38) THE SQUARE FEET OF CONDITION AREA
 IS DIFFERENT FROM THE A/C AREA LISTED ON
 THE PLANS. PLEASE CLARIFY.
  
 39) SPECIFY THE AMOUNT OF ROOF SLOPE ON
 THE PLANS. SEE FBC 1508.3.1 FOR REQUIRED
 MINIMUM FOR BUILT UP ROOFING.
  
 40)REVIEW THE EAST WALL OF THE STRUCTURE
 FOR SHEAR WALL REQUIREMENTS AND PROVIDE
 CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop REV REVISIONS
Rev No 2 Status P Date 2004-11-10 Cont ID  
Sent By rmcdouga Date 2004-11-10 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2004-11-10 Time 07:49 Sent To  
Notes
2004-11-10 00:00:00REVISIONS TO SHEETS A2 AND A3 ARE OK

Review Stop REV REVISIONS
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By rmcdouga Date 2004-11-01 Time 07:34 Rev Time 2.00
Received By rmcdouga Date 2004-11-01 Time 07:34 Sent To  
Notes
2004-11-01 00:00:00DENIED
  
 1) SHEETS A2 AND A3 OF THE REVISED
 PLANS
 HAVE CHANGES THAT ARE NOT CLOUDED OR
 NUMBERED.
  
 2) ON A2 THE MASTER BATH TUB SHAPE IS
 CHANGED AND ADDITIONAL LAVATORY IS
 SHOWN.
  
 3) ON A3 THE THIRD FLOOR LAUNDRY HAS
 BEEN CHANGED TO A HALF BATH. THE NOTE
 FOR W/D STACK IS STILL ON THE PLAN.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop Z ZONING
Rev No 4 Status P Date 2003-10-01 Cont ID  
Sent By rmcdouga Date 2003-10-01 Time 14:18 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-10-01 00:00:00REVISION OK PER M.MCLEAN ON 10-1-03

Review Stop Z ZONING
Rev No 3 Status P Date 2003-07-30 Cont ID  
Sent By mmclean Date 2003-07-30 Time 12:30 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-01-30 Cont ID  
Sent By sgraham Date 2003-01-30 Time 09:55 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 17:36 Rev Time 0.00
Received By sgraham Date 2002-11-26 Time 09:15 Sent To  
Notes
2002-10-21 00:00:001.SUBMIT A CLEAR SITE PLAN SHOWING
 THE CONSTRUCTION BEING BUILT NOW.
 2.SUBMIT A STRUCTURE SHEET SHOWING
 THE HEIGHT AT 30' INSTEAD OF 32'
 3.NO GRAVEL DRIVEWAY IS ALLOWED IN
 THE PRESENT ZONING CODE
 4.THE FRONT YARD MUST MAINTAIN 1000
 SQ.FT OR 75% LANDSCAPED