| 2002-10-22 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 02101251 |
| | ADD: 4431 EMBARCADERO |
| | CONT: MIKE MOORE |
| | TEL: (561)775-3447 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 3) THE LETTER FROM OLIVER & GLIDEN |
| | INDICATES THAT THE EXISTING 1-HR RATED |
| | CEILING GRID & TILE ARE TO BE REPLACED. |
| | NO INFORMATION ON THE RATING OF THE GRID |
| | NOR TILE HAS BEEN SUBMITTED. NEITHER IS |
| | INFORMATION SUBMITTED ON THE LIGHT FIX- |
| | TURES IF THE CANS ARE 1 HR RATED OR IF |
| | RATED ENCLOSERES ARE TO BE USED. SEE |
| | 705.1.1 FIRE RATED ASSEMBLIES, 705.6 FOR |
| | PENETRATION OF HORIZONTAL ASSEMBLIES, |
| | AND 705.6.2 MEMBRANE PENETRATIONS. |
| | |
| | 4)705.1.2 PENETRATIONS SHALL BE PRO- |
| | TECTED BY AN APPROVED PENETRATION FIRE- |
| | STOP SYSTEM AS TESTED IN ACCORDANCE WITH |
| | ASTM E 814, WITH A MINIMUM POSITIVE |
| | PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| | WATER COLUMN AND AN F RATING OF NOT LESS |
| | THAN REQUIRED RATING OF THE WALL |
| | PENETRATED. INDICATE HOW CEILING TILE IS |
| | TO BE HELD IN PLACE, ACCESS TO AREA |
| | ABOVE THE CEILING, ETC? |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |