Plan Review Details - Permit 02101188
Plan Review Stops For Permit 02101188
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-10-24 Cont ID  
Sent By pkrauss Date 2002-10-24 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2002-10-24 Time 11:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-24 Cont ID  
Sent By pkrauss Date 2002-10-23 Time 16:23 Rev Time 1.00
Received By pkrauss Date 2002-10-23 Time 16:23 Sent To FIRE
Notes
2002-10-24 00:00:00PROVISO:
  
 EXHAUST FANS SHALL TERMINATE:
  
 1.A MINIMUM OF 10FT FROM ANY ADJACENT
 BUILDINGS, PROPERTY LINE, AND AIR
 INTAKES.
  
 2.EXHAUST FLOW DIRECTED UP & AWAY FROM
 THE SURFACE OF THE ROOF & A MINIMUM
 OF 40" ABOVE THE ROOF SURFACE.
 NFPA 96 4-8.2 (A) & (B).
  
 AS PER 2001 FBC(M) 506.3.9, GREASE DUCT
 SHALL HAVE 1/4" PER FT SLOPE FOR DUCTS
 LESS THAN 75 FT, 1" PER FT GREATER THAN
 75 FT.
  
 PLEASE NOTE ALL WELDS TO BE INSPECTED
 PRIOR TO COVERING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.