| Plan Review Stops For Permit 02101188 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-10-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-24 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-24 |
Time |
11:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-10-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-23 |
Time |
16:23 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-10-23 |
Time |
16:23 |
Sent To |
FIRE |
|
| Notes |
| 2002-10-24 00:00:00 | PROVISO: | | | | | | EXHAUST FANS SHALL TERMINATE: | | | | | | 1.A MINIMUM OF 10FT FROM ANY ADJACENT | | | BUILDINGS, PROPERTY LINE, AND AIR | | | INTAKES. | | | | | | 2.EXHAUST FLOW DIRECTED UP & AWAY FROM | | | THE SURFACE OF THE ROOF & A MINIMUM | | | OF 40" ABOVE THE ROOF SURFACE. | | | NFPA 96 4-8.2 (A) & (B). | | | | | | AS PER 2001 FBC(M) 506.3.9, GREASE DUCT | | | SHALL HAVE 1/4" PER FT SLOPE FOR DUCTS | | | LESS THAN 75 FT, 1" PER FT GREATER THAN | | | 75 FT. | | | | | | PLEASE NOTE ALL WELDS TO BE INSPECTED | | | PRIOR TO COVERING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|