Plan Review Details - Permit 02101073
Plan Review Stops For Permit 02101073
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-28 Cont ID  
Sent By jwitmer Date 2002-10-28 Time 13:06 Rev Time 1.25
Received By jwitmer Date 2002-10-28 Time 13:06 Sent To  
Notes
2002-10-28 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02101073
 ADD: 700 S ROSEMARY SUITE 214
 CONT: SLATER & SONS
 TEL: (561)793-9342
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 2)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) TABLE 600 INDICATE DISTANCE FROM
 BRUZZI & CITY CELLAR,MINIMUM BLDG TYPE?
  
 4) THERE IS NO STRUCTURAL DETAILS FOR
 SECURING BLDG TO EXISTING SLAB?TRUSSES?
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 MISSING REPORTS:
 A) DOOR ASSEMBLY
 B) ROOFING ASSEMBLY
  
 6) MISSING INTERIOR WALL FINISH?
  
 PLANS ARE OF A CONCEPTIAL IN NATURE, NOT
 COMPLETE TO DO A THOROUGH PLAN REVIEW!!!
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-18 Cont ID  
Sent By dpalmer Date 2002-10-18 Time 05:21 Rev Time 0.25
Received By dpalmer Date 2002-10-18 Time 05:21 Sent To  
Notes
2002-10-18 00:00:00NO NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-31 Cont ID  
Sent By mcarsill Date 2002-10-31 Time 09:29 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 09:29 Sent To  
Notes
2002-10-31 00:00:001) NO INFORMATION PROVIDED WITH REGARDS
 TO FIRE SPRINKLER PROTECTING THE
 GUEST SERVICES BUILDING. PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-30 Cont ID  
Sent By pkrauss Date 2002-10-30 Time 13:46 Rev Time 0.30
Received By pkrauss Date 2002-10-30 Time 13:45 Sent To  
Notes
2002-10-30 00:00:00DENIED:
  
 PROVIDE DETAIL AS THE MOUNTING OF THE
 CONDENSER UNIT INSTALLED ON THE ROOF.
 SHOW COMPLIANCE WITH 2001 FBC 1511.7.
  
 PLEASE NOTE, SUFFICIENT CLEARENCE
 REQUIRED FOR SERVICE & REPLACEMENT AS
 PER 2001 FBC(M) 306.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***