Plan Review Details - Permit 02101068
Plan Review Stops For Permit 02101068
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hpiskura Date 2003-01-16 Time 09:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-11 Cont ID  
Sent By hpiskura Date 2002-12-11 Time 09:29 Rev Time 0.00
Received By hpiskura Date 2002-12-11 Time 09:07 Sent To  
Notes
2002-12-11 00:00:00PROVISO:
  
 THE WORK SHOWN AS "NEW 2940 STONE
 PANELS" IS REQUIRED TO BE 2 HR FIRE
 RATED WALL CONSTRUCTION IN ACCORDANCE
 WITH FBC 701.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-04 Cont ID  
Sent By hpiskura Date 2002-11-04 Time 15:11 Rev Time 0.00
Received By hpiskura Date 2002-11-04 Time 12:16 Sent To  
Notes
2002-11-04 00:00:00SHEET A2 SHOWS WINDOWS TO BE INSTALLED
 ON THE WEST ELEVATION WHICH IS A ZERO
 LOTLINE.FBC TABLE 600 DOES NOT ALLOW
 OPENINGS IN EXTERIOR WALLS WITHIN 3' OF
 A COMMON PROPERTY LINE.
  
 WHAT ARE "MUTTS" SHOWN ON SHEET A2?
  
 SHEET A1, SHOW THE HANDRAILS FOR THE
 STAIRS AND RAMP TO DEMONSTRATE
 COMPLIANCE WITH FBC 1007.5.
  
 SHOW HANDRAILS FOR BOTH SIDES OF THE HC
 RAMP IN ACCORDANCE WITH FBC 11-4.8.5.
  
 SHOW THE CONSTRUCTION DETAILS FOR THE
 STAIRS AND THE RAMP.SEE FBC 104.2.
  
 WHERE IS THE FOUR HOUR RATED PARTITION
 SHOWN IN SECTION 3/A1 USED?
  
 THE CHANGE IN USE MAY BE SUBJECT TO
 IMPACT FEES COLLECTED BY THE COUNTY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 11:09 Rev Time 0.50
Received By dpalmer Date 2002-12-27 Time 10:37 Sent To  
Notes
2002-12-27 00:00:00************* NOTE *************
  
 CALLED CONT, LEFT MESSAGE, CONT TO PICK
 UP PLANS AND CHANGE OUT SHEETS.
 TAKE OUT OLD AND MAKE TWO COMPLETE NEW
 SETS FOR STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DWEEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-24 Cont ID  
Sent By dpalmer Date 2002-10-24 Time 15:13 Rev Time 0.50
Received By dpalmer Date 2002-10-24 Time 15:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-21 Cont ID  
Sent By mcarsill Date 2002-11-21 Time 16:29 Rev Time 0.00
Received By mcarsill Date 2002-11-21 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-01 Cont ID  
Sent By mcarsill Date 2002-11-01 Time 16:28 Rev Time 0.00
Received By mcarsill Date 2002-11-01 Time 16:28 Sent To  
Notes
2002-11-01 00:00:001) BUILDING ADDRESS REQUIRED ON
 APPROPRIATE ELEVATION.
  
 2) PLEASE EXPLAIN EXITING RATIONALE TO
 THIS OFFICE.
  
 3) PLEASE INDICATE ON PLANS IF HANDRAILS
 ARE PRESENT AT ALL EXISTING STAIRS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2002-12-27 Time 11:40 Sent To  
Notes
2002-12-27 00:00:00TO COMM BOARD #45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2002-12-23 Time 11:10 Sent To  
Notes
2002-12-23 00:00:00RESUB W/ NO PERMIT APPL AND ORIG PLANS,
 GIVEN TO LOU MARTINEZ 12/23/02.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-05 Cont ID  
Sent By pkrauss Date 2002-12-05 Time 13:27 Rev Time 0.30
Received By pkrauss Date 2002-12-05 Time 13:16 Sent To  
Notes
2002-12-05 00:00:00MECHANICAL PERMIT 02101090

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-12 Cont ID  
Sent By pkrauss Date 2002-11-12 Time 14:04 Rev Time 0.40
Received By pkrauss Date 2002-11-12 Time 13:13 Sent To  
Notes
2002-11-12 00:00:00DENIED:MECHANICAL PERMIT 02101090
  
 PLAN SHEET A-1 INDICATES THE MECH/ELEC
 ROOM HAS A 1 HR RATING.NO FIRE DAMPERS
 ARE INDICATED ON PLAN.
  
 PLEASE NOTE, AS PER 2001 FBC(M) 401.5,
 OUTSIDE AIR EXHAUST SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM LOT LINES OR
 BUILDINGS ON THE SAME LOT.401.5.2,
 EXHAUST AIR SHALL NOT BE DIRECTED ONTO
 WALKWAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-07 Cont ID  
Sent By kstevens Date 2003-01-07 Time 17:15 Rev Time 0.50
Received By kstevens Date 2003-01-07 Time 17:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-10 Cont ID  
Sent By kstevens Date 2002-12-10 Time 17:06 Rev Time 0.75
Received By kstevens Date 2002-12-10 Time 17:06 Sent To  
Notes
2002-12-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 WATER SPOUT ON A SINK FOR
 DRINKING WATER DOES NOT REPLACE A DRINK-
 ING FOUNTAIN. DRINKING FOUNTAINS ARE
 FIXTURES REQUIRED BY TABLE 403.1. ALSO
 SEE SECTION 410.1. (SEE SECTION 404.2.1,
 404.2.2, 404.2.3, 404.2.4, & 404.2.5.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By kstevens Date 2002-11-05 Time 16:37 Rev Time 0.50
Received By kstevens Date 2002-11-05 Time 16:37 Sent To  
Notes
2002-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN FOR MINIMUM FACILITIES. ALSO
 SEE SEC 410.1. (AIR-1010)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377