| 2002-11-20 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE SIGNED AND SEALED COPY OF SOILS |
| | REPORT FROM SOILS ENGINEER. |
| | |
| | 4) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 5) GLASS BLOCK ON THE ZERO LOT LINE IS |
| | REQUIRED TO HAVE A ONE HOUR FIRE |
| | RESISTANCE. PROVIDE MANUFACTURES |
| | SPECIFICATIONS AND LISTING INFORMATION |
| | FOR A ONE HOUR FIRE RATED GLASS BLOCK |
| | ASSEMBLY. REVISE GLASS BLOCK DETAIL ON |
| | A5 TO COMPLY WITH ONE HOUR FIRE RATED |
| | INSTALLATION. |
| | |
| | 6) THE EXTERIOR WALL AT ZERO LOT LINE IS |
| | REQUIRED TO HAVE A CALCULATED FIRE |
| | RESISTANCE OF ONE HOUR ASSUMING EITHER |
| | SIDE OF THE WALL TO BE EXPOSED TO FIRE. |
| | THE SECOND FLOOR WOOD FRAME WALL DOES |
| | NOT COMPLY. |
| | |
| | 7)ON C1,#11 OF PLAN NOTES SAYS HURRICANE |
| | SHUTTERS ARE REQUIRED IN HVHZ. CITY OF |
| | WPB IS NOT IN HVHZ, HOWEVER, IMPACT |
| | PROTECTION IS REQUIRED. PLEASE REVISE. |
| | |
| | 8) ON C1, FRAMING NOTE #15 SPECIFIES |
| | FASTENER SPACING OF 6" O.C., ASTM C 1063 |
| | REQUIRES 3/8" RIB METAL LATH TO BE |
| | FASTENED AT EACH RIB (4"). |
| | |
| | 9) INDICATE THE LOCATION AND MATERIALS |
| | USED TO PROVIDE DRAFTSTOPPING AT AREAS |
| | GREATER THAN 500 SQFT IN FLOOR/CEILING |
| | ASSEMBLIES. FBC 2305.2.2 |
| | |
| | 10) THE CITY OF WPB AMENDMENTS TO FBC |
| | SECTION 2111.1.9 REQUIRES A 1.5 INCH |
| | RECESS (WATER STOP) WHERE EXTERIOR WALL |
| | CMU BEAR ON A CONCRETE FLOOR SURFACE. |
| | PLEASE REVISE DETAILS ON A1 & A6. |
| | |
| | 11) THERE IS NO F12 FOOTING INDICATED IN |
| | THE FOOTING SCHEDULE ON A1. |
| | |
| | 12) THE MEASUREMENT DESIGNATIONS (FEET |
| | & INCHES) ARE NOT INDICATED FOR SOME OF |
| | THE DIMENSIONS LISTED IN THE FOOTING |
| | SCHEDULE ON A1. |
| | |
| | 13) CITY AMENDMENTS TO THE FBC TABLE |
| | 2306.1 REQUIRE RING SHANK NAILS IN ZONE |
| | 3 WHEN THE MEAN ROOF HEIGHT IS 25' OR |
| | MORE. PLEASE REVISE. |
| | |
| | 14) FBC 2309.6 REQUIRES ACCESS TO ATTIC |
| | SPACE, WHEN THE CLEAR ATTIC SPACE AT THE |
| | PEAK IS 24 INCHES. INDICATE ATTIC ACCESS |
| | OPENINGS TO ANY OF THE LOWER ROOF ATTICS |
| | THAT MEET THIS CRITERIA. |
| | |
| | 15) PROVIDE DETAILS OF ATTACHMENT OF |
| | BALCONY RAILS INDICATING THAT THEY ARE |
| | ADEQUATE IN STRENGTH, DURABILITY AND |
| | ATTACHMENT AS REQUIRED BY FBC 1608.2. |
| | |
| | 16) INDICATE FIREBLOCKING MATERIAL AND |
| | LOCATIONS AT STAIRS AS REQUIRED BY FBC |
| | SECTION 2305.1.4. |
| | |
| | 17) DETAIL 8 ON A7 IS INDICATED ON THE |
| | FRAMING PLAN AT THE WRONG LOCATIONS IN |
| | TWO INSTANCES. PLEASE CORRECT. |
| | |
| | 18) DETAIL 8 ON A7 INDICATES 3-1/4" |
| | HILTI-PINS WITH 4" EMBED. PLEASE |
| | CLARIFY. |
| | |
| | 19) DETAIL 9 ON A7 IS SHOWN ON THE PLAN |
| | AT THE WRONG LOCATION. PLEASE CORRECT. |
| | |
| | 20) DETAIL 13 ON A7 IS NOT INDICATED ON |
| | THE FRAMING PLAN. |
| | |
| | 21) DETAIL 11A ON A7 IS INDICATED ON THE |
| | FRAMING PLAN AND THERE IS NO DETAIL |
| | GIVEN. |
| | |
| | 22) DETAIL 12 ON A8 IS INDICATED ON THE |
| | FRAMING PLAN ON A7, BUT THERE IS NO |
| | DETAIL 12 GIVEN ON SHEET A8. |
| | |
| | 23) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - HORIZONTAL STRUCTURAL MULLIONS |
| | (ONES SUBMITTED ARE FOR VERTICAL |
| | APPLICATIONS ONLY) |
| | - ROOFING MATERIALS |
| | - OVERHEAD GARAGE DOORS |
| | - FRENCH DOORS (WITH GLAZING IN DOORS) |
| | |
| | 24) PROVIDE THE TEST REPORTS FOR IMPACT |
| | RESISTIBILITY FOR THE EXTERIOR DOORS AS |
| | REQUIRED BY GENERAL NOTES ON THE SITE |
| | SPECIFIC PRODUCT SUBMITTAL FORMS. |
| | |
| | 25) THE SITE SPECIFIC PRODUCT APPROVAL |
| | SUBMITTAL FORMS ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE DESIGNER OF |
| | RECORD OF THE STRUCTURE. |
| | |
| | PLEASE INSERT NEW SHEETS INTO PLANS AND |
| | REMOVE OLD ONES. PLEASE RETURN OLD |
| | SHEETS WITH RESUBMITTAL IN ORDER TO |
| | EXPEDITE PLAN REVIEW. |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |