| 2002-11-19 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02100862 |
| | ADD: 3009 SANTA MARGARITA RD |
| | CONT: DOUBLE R |
| | TEL: (954)796-0777 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE SIGNED/ SEALED COPY OF SOILS |
| | REPORT WITH THE SAFE MINIMUM BEARING |
| | VALUE. |
| | |
| | 3)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. |
| | SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL |
| | OF RECORD. |
| | |
| | 4) ZERO-LOT LINE/SECOND STORY FRAME, |
| | < THAN 5'-0" FROM PROP. REQUIRES 1 HR |
| | RATING FROM BOTH SIDES, 1/2" DRYWALL |
| | ONLY MAKES 50 MINUTES. |
| | 709.6.2.2 THE FIRE RESISTANCE RATING OF |
| | A WOOD FRAMED ASSEMBLY IS EQUAL TO THE |
| | SUM OF THE TIME ASSIGNED TO THE MEMBRANE |
| | ON THE FIRE EXPOSED SIDE, THE TIME |
| | ASSIGNED TO THE FRAMING MEMBERS AND THE |
| | TIME ASIGNED FOR ADDITIONAL CONTRIBUTION |
| | BY OTHER PROTECTIVE MEASURES SUCH AS |
| | INSULATION. THE MEMBRANE ON THE |
| | UNEXPOSED SIDE SHALL NOT BE INCLUDED IN |
| | DETERMINING THE FIRE RESISTANCE OF THE |
| | ASSEMBLY. |
| | |
| | 5) TABLE 600 ZERO-LOT LINE, GLASS BLOCK |
| | ON ZERO LOT LINE REQUIRES 1 HR RATING, |
| | MISSING INFO. |
| | |
| | 6) 1606.1.5 MEAN ROOF HEIGHT, THE DIMEN- |
| | SION FROM GRADE TO THE AVERAGE OF THE |
| | ROOF EAVE HEIGHT, AND THE HIGHEST POINT |
| | ON THE ROOF SURFACE. MEAN ROOF HEIGHT |
| | IS NOT GIVEN, CALAULATED MEAN ROOF |
| | HEIGHT IS 26"-7 1/2". SEE TABLE 2306.1 |
| | COUNTY AMENDMENTS FOR ZONE# 3, RING |
| | SHANK NAILS. |
| | |
| | 7) SHEET C-1, FRAMING NOTE# 15, HIGH RIB |
| | METAL LATH, SPACING 6" O.C., ASTM C-1063 |
| | 7.10.1.1. 3/8" RIB LATH SHALL BE NAILED |
| | (ATTACHED) AT EACH RIB (4"). |
| | |
| | 8)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |