Plan Review Details - Permit 02100837
Plan Review Stops For Permit 02100837
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-17 Cont ID  
Sent By pkrauss Date 2002-10-17 Time 16:04 Rev Time 0.30
Received By pkrauss Date 2002-10-17 Time 16:04 Sent To  
Notes
2002-10-17 00:00:00PROVISO:
  
 1.LOCATION OF THE AHU IN BEDROOM 3 -
 ACCESS FOR THE AHU SHALL BE NO LESS
 THAN 30" X 22" (2001 FBC(M) 306.3)
 AS PER 2001 FBC CHAPTER 13 SECTION
 610.1.ABC.3.5.2, THE SERVICE PANEL
 OF THE EQUIPMENT SHALL BE LOCATED
 WITHIN 6 FT OF THE ATTIC ACCESS.
  
 2.RETURN AIR REQUIRED FROM THE BEDROOM
 AREAS2001 FBC(M) 601.4.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.