| Plan Review Stops For Permit 02100787 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-12-19 |
Time |
16:07 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
2002-12-19 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-18 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-12-12 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2002-12-12 00:00:00 | SECOND REVIEW | | | | | | FBC 11-5.4 REQUIRES "ALL" DINING AREAS | | | TO BE ACCESSIBLE, NOT JUST THE ONE | | | DESIGNATED AREA SHOWN ON THE PLANS | | | DATED 11/17/02 SHEET A1.PLEASE REVISE | | | AS NECESSARY.SEE ALSO FBC | | | 11-4.1.6(1)(A). | | | | | | FBC 1003.2.7 REQUIRES CHANGES OF LEVEL | | | IN THE MEANS OF EGRESS OF 12" OR LESS | | | TO BE BY RAMP.SEVERAL LOCATIONS ON | | | THE PLAN INDICATE 12" AND 6" CHANGES. | | | PLEASE REVISE AS NECESSARY. | | | | | | PLEASE PROVIDE OR SPECIFY THAT THE EIFS | | | TRIM SHOWN IN SECTION 1/A5 MEETS FBC | | | CLASS "C" AS NOTED ON FBC 803.2 FOR THE | | | INTENDED SIZES, SHAPES AND QUANTITIES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-30 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-30 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2002-10-30 00:00:00 | THE PROPOSED ELEVATED SEATING AREAS ARE | | | REQUIRED TO BE HANDICAP ACCESSIBLE BY | | | FBC 11-5.4PLEASE REVISE AS NECESSARY. | | | | | | PROVIDE AN ENGINEERING ANALYSIS | | | DEMONSTRATING THE EXISTING STRUCTURE | | | CAN SUPPORT THE ADDED DEAD LOAD OF THE | | | SEVERAL SIX INCH CONCRETE AREAS | | | PROPOSED TO BE CONSTRUCTED. | | | | | | PROVIDE THE DESIGN WIND PRESSURES FOR | | | THE PROPOSED EXTERIOR STORE FRONT | | | SYSTEM.SEE FBC 1606.1.7 #5 AND THE | | | METHOD OF HURRICANE MISSILE RESISTANCE. | | | FBC 1606.1.4. | | | | | | IF TEST AND NOTICE OF ACCEPTANCE | | | REPORTS FOR THE STORE FRONT SYSTEM | | | ARE NOT INCLUDED WITH THE PERMIT | | | APPLICATION A SEPARATE PERMIT, PLANS | | | AND FEE WILL BE REQUIRED FOR THEIR | | | INSTALLATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-02-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-24 |
Time |
08:53 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-02-24 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-02-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
09:52 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-02-20 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2003-02-20 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PANELS AND RISER DIAGRAM | | | NEED TO CORRELATE. | | | SPOKE TO ENGINEER, WILL REVISE PLAN. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-21 |
Time |
06:26 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-11-21 |
Time |
06:26 |
Sent To |
|
|
| Notes |
| 2002-11-21 00:00:00 | ************** NOTES REDLINED ******** | | | | | | 1)NOTE: PLEASE NOTE, MAINS ARE TO BE | | | GROUPED PER 230-72. NOTED AND HIGHLIGHT- | | | -ED ON PLANS. | | | | | | 2)NOTE: PLEASE NOTE, GROUNDING FOR | | | TRANSFORMERS PER 250-30. | | | | | | PLEASE SEE NOTES REDLINED!!! | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-05 |
Time |
16:04 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2002-11-05 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2002-11-05 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE, PLANS ARE REQ`D | | | TO BE DONE BY A PE. UNDER FS/FAC. | | | 471.003(2)(H)1/ FBC 104.4.1.3, FAC | | | 553-79(6)A. | | | | | | 2)NOTE: PLEASE CLARIFY CIRCUTIING FOR | | | EM LTS AND EXIT LTS. 700-12 | | | | | | 3)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | GRROUND BETWEEN PANEL AND TRANSFORMERTS | | | SIZE 250--122 | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCUALTIONS, | | | PER 220-3,220-310, 220-20,220-11, | | | 220-13.215-3/230-42 | | | | | | 5)NOTE: PLEASE NOTE ON PLANS, FEEDER | | | COLORS PER LOCALAMENDMENTS 215-5 | | | BROWN/PURPL/YELLOW. | | | | | | 6)NOTE: PLEASE SHOW GROUNDING FOR | | | TRANSFORMER. PER 250-30 | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | 110-9/215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-11-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-11-22 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-22 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2002-11-22 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD,DUCT, AND EXTINGUISHING | | | SYSTEM. | | | | | | 2) DIRECTIONAL ARROW ON EXIT SIGN | | | NEAR STAIRWAY IS NOT NECESSARY. | | | | | | 3) MANUAL PULL STATION AND HORN | | | STROBE SHOULD BE RELOCATED AWAY FROM | | | ENTRY HANDICAP RAMP. | | | | | | 4) THE MANUAL PULL STATION IS NOT | | | NEEDED NEAR THE WEST SIDE OF ENTRY | | | HANDICAP RAMP. (HOSTESS AREA) | | | | | | 5) THE HOOD SYSTEM EXHAUST SHALL BE A | | | MINIMUM OF AT LEAST 40" ABOVE THE | | | ROOF. | | | | | | 6) PERMANANT PLATFORMS " SHALL BE OF | | | MATERIALS REQUIRED FOR THE TYPE OF | | | BUILDING CONSTRUCTION EXCEPT THE FLOOR | | | FINISH MAY BE OF WOOD. IF THE SPACE | | | BENEATH THE PLATFORM IS USED FOR STORAGE | | | OR ANY OTHER PURPOSE OTHER THAN | | | EQUIPMENT WIRING OR PLUMBING, THE FLOOR | | | CONSTRUCTION SHALL NOT BE LESS THAN ONE | | | HOUR". RE: NFPA 101, THE LIFE SAFETY | | | CODE, NEW ASSEMBLY OCCUPANCIES. | | | | | | 7) ALL STAIRS, RAMPS, AND HANDRAILS ARE | | | TO COMPLY WITH THE FLORIDA BUILDING CODE | | | AND THE FLORIDA FIRE PREVENTION CODE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-31 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-31 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | 1) PLEASE PROVIDE A LIFE SAFETY PLAN | | | TO THIS OFFICE FOR THE STEAKHOUSE. | | | | | | 2) PLEASE INDICATE INTERIOR | | | CLASSIFICATION FOR THE WALLS AND | | | CEILINGS. | | | | | | 3) PLEASE INDICATE WHERE HANDICAPPED | | | SEATING EXISTS. | | | | | | 4) THE EXISTING HARDWARE ON THE EXISTING | | | DOOR MUST HAVE PANIC HARDWARE. | | | | | | 5) PLANS INDICATE A FIRE ALARM PANEL | | | INSIDE STEAKHOUSE. NO NEW FIRE ALARM | | | PANELS ARE ALLOWED TO BE INSTALLED IN | | | ANY TENANT SPACE. ALL FIRE ALARM DEVICES | | | MUST BE CONNECTED TO THE EXISTING BASE | | | BUILDING SYSTEMS. PLEASE REVISE PLANS. | | | | | | 6) IS THERE ANY WAITING SPACES WITHIN | | | TENANT SPACE. IF SO, WHAT ARE YOU | | | USING FOR SQUARE FOOTAGE PER PERSON. | | | | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF ANY NEW HOODS. | | | DUCTS, OR SUPPRESSION SYSTEMS. | | | | | | 8) NO INFORMATION PROVIDED WITH REGARDS | | | TO THE FIRE SPRINKLER SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-16 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-16 |
Time |
17:30 |
Sent To |
P |
|
| Notes |
| 2002-12-16 00:00:00 | TO"P" IN BOX./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-20 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-20 |
Time |
18:12 |
Sent To |
|
|
| Notes |
| 2002-11-20 00:00:00 | TO COMM BOARD,# 51./WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-02-07 |
Time |
08:31 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2003-02-07 |
Time |
08:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-18 |
Time |
14:27 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-12-18 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2002-12-18 00:00:00 | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, AND WALK-IN COOLERS & | | | FREEZERS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-12-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-05 |
Time |
14:06 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-12-05 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2002-12-05 00:00:00 | PLAN SHEETM-1 PLEASE SEE NOTE #1 | | | BELOW. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, GAS, & WALK-IN COOLER/ | | | FREEZER.PROVIDE MANUFACTURER SUBMITTAL | | | DATA & INSTALLATION INSTRUCTIONS WITH | | | WALK-IN COOLER/FREEZER APPLICATION. | | | IF CONDENSERS ARE REMOTE TYPE, PROVIDE | | | SUBMITTAL ON COND UNIT STAND IF LOCATED | | | ON THE ROOF. | | | | | | HOOD PLAN REVIEW: | | | 1.PLAN SHEET M-1 INDICATES 2 SF #1 ON | | | THE PLAN & AIR BALANCE SCHEDULE.HOOD | | | DEPOT DWG 1 & 3 INDICATE SF #1 & 2, | | | PLEASE CORRECT PLAN SHEET M-1 TO REFLECT | | | WHAT IS SHOWN ON SHOP DWG. | | | PROVISO: | | | TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP | | | AIR & THE AIR IN THE CONDITIONED SPACE | | | SHALL NOT EXCEED 10 DEGREES F. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-10-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-30 |
Time |
15:11 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-10-30 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2002-10-30 00:00:00 | HVAC PLANS SUBMITTED ARE CODE COMPLIANT. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION & WALK-IN COOLER/FREEZER | | | | | | WALK-IN COOLERS & FREEZERS - | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL & | | | INSTALLATION INSTRUCTIONS.INDICATE ON | | | PLANS IF COOLERS ARE SELF CONTAINED OR | | | HAVE A REMOTE CONDENSER.SHOULD | | | CONDENSER BE REMOTE PROVIDE DETAIL OF | | | STAND SHOWING COMPLIANCE WITH 2001 FBC | | | 1511.7 (MINIMUM CLEARANCE BETWEEN THE | | | ROOF SURFACE & BOTTOM OF THE SUPPORT | | | RAIL). | | | | | | HOOD & GREASE DUCT - | | | SHOW COMPLIANCE WITH 2001 FBC(M) 506 | | | THRU 508 - GREASE DUCT, HOOD & MAKE UP | | | AIR.PLEASE NOTE TERMINATION OF GREASE | | | DUCT ABOVE THE ROOF SHALL BE A MINIMUM | | | 40" ABOVE THE ROOF SURFACE AS PER NFPA | | | 96. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-18 |
Time |
13:42 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-12-18 |
Time |
13:42 |
Sent To |
B |
|
| Notes |
| 2002-12-18 00:00:00 | PASSED PROVISO - REVISION REQUIRED FOR | | | GAS RISER SHOWING RED LINE CHANGES PRIOR | | | TO FINAL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-12-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-16 |
Time |
17:31 |
Rev Time |
1.75 |
| Received By |
kstevens |
Date |
2002-12-13 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2002-12-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHTS P-1 AND P-2 FROM PREVIOUS RE- | | | VIEW. ALL INDIRECT WASTE SHALL DRAIN IN- | | | TO A FLOOR SINK. SEC 802.3 - SEE THE | | | STEAMER, BOTH ICE BINS IN BAR AREA, AND | | | CONDENSATE BY WATER HEATER. | | | 2) FOLLOWING ISSUES FOR GAS APPLICATION. | | | FOLLOWING MANUFACTURE SHEETS NOT SUB- | | | MITTED. STEAMER, CHEESE MELTER, ROTISS- | | | ERIE, AND THE WATER HEATER. | | | DISCREPENCIES BETWEET GAS RISER AND MAN- | | | UFACTURE SHEETS. *********** | | | CHARBROILER SHOWS 160K ON RISER - MANUF. | | | SHEETS SHOW 195K. | | | FRYERS SHOW (3) @ 122K ON RISER - MANUF. | | | SHEETS SHOW 90K EACH. | | | OVENS SHOW90K ON RISER - MANUF. SHEETS | | | SHOW 88K. | | | RANGE @ 230K NOT SHOWN ON RISER. | | | PLEASE CLAIRFY. THIS SHALL AFFECT THE | | | PIPE SIZING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-05 |
Time |
09:58 |
Rev Time |
5.00 |
| Received By |
kstevens |
Date |
2002-11-02 |
Time |
18:17 |
Sent To |
|
|
| Notes |
| 2002-11-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) PLEASE ROUTE PLANS TO DEPT OF BUSIN- | | | ESS REGULATION, HOTEL AND RESTAURANT DIV | | | 2) PLEASE SUBMIT CALCULATIONS FOR MINI- | | | MUM FACILITIES PER TABLE 1003.1 BLDG. | | | CODE AND TABLE 403.1 PLUMBING CODE. IN- | | | DICATE IF SEATING IS FIXED OR NOT. | | | 3) SHT D-1 ALL CAPPED OFF PLUMBING SHALL | | | BE INSPECTED PRIOR TO COVERING. | | | 4) SHT P-1 PLUMBING NOTES #16, AIR CHAM- | | | BERS ARE NOT APPROVED. WATER HAMMER ARR- | | | ESTORS REQUIRED BY SECTION 604.9 SHALL | | | BE LOCATED NEAR THE FIXTURE IN AN "EFF- | | | ECTIVE RANGE" NOT AT TOP OF DROP IN | | | CEILING PER MANUFACTURE INSTALLATION IN- | | | STRUCTIONS AND PDI-WH 201. | | | 5) RPZ BACKFLOW IS REQUIRED ON WATER | | | SERVICE IN SPACE LOCATED MAXIMUM OF 4' | | | AFF FOR SERVICING AND TESTING. | | | 6) SHTS P-1/P-3 FOOD PREP SINK, #56, | | | SHALL BE DRAINED INDIRECTLY INTO A FLOOR | | | SINK PER SECTION 802.1.1 | | | 7) SHTS P-1/P-3 ALL INDIRECT WASTE SHALL | | | BE DRAINED INTO A FLOOR SINK PER SECTION | | | 802.3. SAFE WASTES AND HUB DRAINS ARE | | | NOT APPROVED. | | | 8) SHTS P-1/P-3 DISHWASHER SHALL DRAIN | | | TO SANITARY NOT GREASE WASTE PER UTILITY | | | DEPT. | | | 9) SHT P-2 INDICATE TEMPERATURE OF WATER | | | FROM WATER HEATER. 110 DEGREE MAXIMUM | | | TEMP. FOR HAND SINKS. | | | 10) SHT P-3 FLOOR DRAIN SHOWN ON SHT P-1 | | | NOT SHOWN ON SANT. RISER DIAGRAM. | | | 11) SHT A-1 DOORS SHALL NOT SWING INTO | | | THE CLEAR FLOOR SPACE OF ANY FIXTURE. | | | SECTION 11-4.17.5. SEE MEN'S/WOMEN'S | | | STALLS IN RESTROOMS | | | 12) SHT P-3 GAS PIPING NOTES #1, CODE | | | IN USE FBC-2001 FUEL GAS, NOT STANDARD | | | GAS CODE. PLEASE CHANGE REFERENCE. | | | 13) SHT P-3 GAS RISER DIAGRAM, TOTAL | | | DEVELOPED LENGTH IS APPROX 150' NOT 137' | | | AS SHOWN. PLEASE ADJUST PIPE SIZES NOTED | | | IN RED ON PLANS AND CHANGE ACCORDINGLY. | | | 14) TYPE OF GAS, (LP OR NATURAL) | | | 15)SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 | | | FUEL GAS CODE SEC. 402.2 | | | 16) SHT P-3 GAS RISER DIAGRAM, UNION RE- | | | QUIRED BETWEEN MANUAL SHUT OFF VALVE AND | | | AUTOMATIC SHUT OFF VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|