Plan Review Details - Permit 02100787
Plan Review Stops For Permit 02100787
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-19 Cont ID  
Sent By lmartine Date 2002-12-19 Time 16:07 Rev Time 1.00
Received By lmartine Date 2002-12-19 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-12-12 Cont ID  
Sent By kstevens Date 2002-12-18 Time 13:43 Rev Time 0.00
Received By hpiskura Date 2002-12-12 Time 11:30 Sent To  
Notes
2002-12-12 00:00:00SECOND REVIEW
  
 FBC 11-5.4 REQUIRES "ALL" DINING AREAS
 TO BE ACCESSIBLE, NOT JUST THE ONE
 DESIGNATED AREA SHOWN ON THE PLANS
 DATED 11/17/02 SHEET A1.PLEASE REVISE
 AS NECESSARY.SEE ALSO FBC
 11-4.1.6(1)(A).
  
 FBC 1003.2.7 REQUIRES CHANGES OF LEVEL
 IN THE MEANS OF EGRESS OF 12" OR LESS
 TO BE BY RAMP.SEVERAL LOCATIONS ON
 THE PLAN INDICATE 12" AND 6" CHANGES.
 PLEASE REVISE AS NECESSARY.
  
 PLEASE PROVIDE OR SPECIFY THAT THE EIFS
 TRIM SHOWN IN SECTION 1/A5 MEETS FBC
 CLASS "C" AS NOTED ON FBC 803.2 FOR THE
 INTENDED SIZES, SHAPES AND QUANTITIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-30 Cont ID  
Sent By hpiskura Date 2002-10-30 Time 13:49 Rev Time 0.00
Received By hpiskura Date 2002-10-30 Time 10:09 Sent To  
Notes
2002-10-30 00:00:00THE PROPOSED ELEVATED SEATING AREAS ARE
 REQUIRED TO BE HANDICAP ACCESSIBLE BY
 FBC 11-5.4PLEASE REVISE AS NECESSARY.
  
 PROVIDE AN ENGINEERING ANALYSIS
 DEMONSTRATING THE EXISTING STRUCTURE
 CAN SUPPORT THE ADDED DEAD LOAD OF THE
 SEVERAL SIX INCH CONCRETE AREAS
 PROPOSED TO BE CONSTRUCTED.
  
 PROVIDE THE DESIGN WIND PRESSURES FOR
 THE PROPOSED EXTERIOR STORE FRONT
 SYSTEM.SEE FBC 1606.1.7 #5 AND THE
 METHOD OF HURRICANE MISSILE RESISTANCE.
 FBC 1606.1.4.
  
 IF TEST AND NOTICE OF ACCEPTANCE
 REPORTS FOR THE STORE FRONT SYSTEM
 ARE NOT INCLUDED WITH THE PERMIT
 APPLICATION A SEPARATE PERMIT, PLANS
 AND FEE WILL BE REQUIRED FOR THEIR
 INSTALLATION.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-02-24 Cont ID  
Sent By btrobaug Date 2003-02-24 Time 08:53 Rev Time 0.50
Received By btrobaug Date 2003-02-24 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 09:52 Rev Time 0.33
Received By dpalmer Date 2003-02-20 Time 09:52 Sent To  
Notes
2003-02-20 00:00:00********* UNSAT ***********
  
 1)NOTE: PANELS AND RISER DIAGRAM
 NEED TO CORRELATE.
 SPOKE TO ENGINEER, WILL REVISE PLAN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-11-21 Time 06:26 Rev Time 0.50
Received By dpalmer Date 2002-11-21 Time 06:26 Sent To  
Notes
2002-11-21 00:00:00************** NOTES REDLINED ********
  
 1)NOTE: PLEASE NOTE, MAINS ARE TO BE
 GROUPED PER 230-72. NOTED AND HIGHLIGHT-
 -ED ON PLANS.
  
 2)NOTE: PLEASE NOTE, GROUNDING FOR
 TRANSFORMERS PER 250-30.
  
 PLEASE SEE NOTES REDLINED!!!
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By dpalmer Date 2002-11-05 Time 16:04 Rev Time 1.00
Received By dpalmer Date 2002-11-05 Time 16:04 Sent To  
Notes
2002-11-05 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, PLANS ARE REQ`D
 TO BE DONE BY A PE. UNDER FS/FAC.
 471.003(2)(H)1/ FBC 104.4.1.3, FAC
 553-79(6)A.
  
 2)NOTE: PLEASE CLARIFY CIRCUTIING FOR
 EM LTS AND EXIT LTS. 700-12
  
 3)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 GRROUND BETWEEN PANEL AND TRANSFORMERTS
 SIZE 250--122
  
 4)NOTE: PLEASE SHOW LOAD CALCUALTIONS,
 PER 220-3,220-310, 220-20,220-11,
 220-13.215-3/230-42
  
 5)NOTE: PLEASE NOTE ON PLANS, FEEDER
 COLORS PER LOCALAMENDMENTS 215-5
 BROWN/PURPL/YELLOW.
  
 6)NOTE: PLEASE SHOW GROUNDING FOR
 TRANSFORMER. PER 250-30
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 09:39 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 09:38 Sent To  
Notes
2002-11-22 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT, AND EXTINGUISHING
 SYSTEM.
  
 2) DIRECTIONAL ARROW ON EXIT SIGN
 NEAR STAIRWAY IS NOT NECESSARY.
  
 3) MANUAL PULL STATION AND HORN
 STROBE SHOULD BE RELOCATED AWAY FROM
 ENTRY HANDICAP RAMP.
  
 4) THE MANUAL PULL STATION IS NOT
 NEEDED NEAR THE WEST SIDE OF ENTRY
 HANDICAP RAMP. (HOSTESS AREA)
  
 5) THE HOOD SYSTEM EXHAUST SHALL BE A
 MINIMUM OF AT LEAST 40" ABOVE THE
 ROOF.
  
 6) PERMANANT PLATFORMS " SHALL BE OF
 MATERIALS REQUIRED FOR THE TYPE OF
 BUILDING CONSTRUCTION EXCEPT THE FLOOR
 FINISH MAY BE OF WOOD. IF THE SPACE
 BENEATH THE PLATFORM IS USED FOR STORAGE
 OR ANY OTHER PURPOSE OTHER THAN
 EQUIPMENT WIRING OR PLUMBING, THE FLOOR
 CONSTRUCTION SHALL NOT BE LESS THAN ONE
 HOUR". RE: NFPA 101, THE LIFE SAFETY
 CODE, NEW ASSEMBLY OCCUPANCIES.
  
 7) ALL STAIRS, RAMPS, AND HANDRAILS ARE
 TO COMPLY WITH THE FLORIDA BUILDING CODE
 AND THE FLORIDA FIRE PREVENTION CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-31 Cont ID  
Sent By mcarsill Date 2002-10-31 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 10:47 Sent To  
Notes
2002-10-31 00:00:001) PLEASE PROVIDE A LIFE SAFETY PLAN
 TO THIS OFFICE FOR THE STEAKHOUSE.
  
 2) PLEASE INDICATE INTERIOR
 CLASSIFICATION FOR THE WALLS AND
 CEILINGS.
  
 3) PLEASE INDICATE WHERE HANDICAPPED
 SEATING EXISTS.
  
 4) THE EXISTING HARDWARE ON THE EXISTING
 DOOR MUST HAVE PANIC HARDWARE.
  
 5) PLANS INDICATE A FIRE ALARM PANEL
 INSIDE STEAKHOUSE. NO NEW FIRE ALARM
 PANELS ARE ALLOWED TO BE INSTALLED IN
 ANY TENANT SPACE. ALL FIRE ALARM DEVICES
 MUST BE CONNECTED TO THE EXISTING BASE
 BUILDING SYSTEMS. PLEASE REVISE PLANS.
  
 6) IS THERE ANY WAITING SPACES WITHIN
 TENANT SPACE. IF SO, WHAT ARE YOU
 USING FOR SQUARE FOOTAGE PER PERSON.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF ANY NEW HOODS.
 DUCTS, OR SUPPRESSION SYSTEMS.
  
 8) NO INFORMATION PROVIDED WITH REGARDS
 TO THE FIRE SPRINKLER SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 17:31 Rev Time 0.00
Received By btrobaug Date 2002-12-16 Time 17:30 Sent To P
Notes
2002-12-16 00:00:00TO"P" IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 18:12 Rev Time 0.00
Received By btrobaug Date 2002-11-20 Time 18:12 Sent To  
Notes
2002-11-20 00:00:00TO COMM BOARD,# 51./WRT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-02-07 Cont ID  
Sent By hmoser Date 2003-02-07 Time 08:31 Rev Time 0.50
Received By hmoser Date 2003-02-07 Time 08:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By pkrauss Date 2002-12-18 Time 14:27 Rev Time 0.30
Received By pkrauss Date 2002-12-18 Time 14:27 Sent To  
Notes
2002-12-18 00:00:00ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, AND WALK-IN COOLERS &
 FREEZERS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-12-13 Cont ID  
Sent By pkrauss Date 2002-12-05 Time 14:06 Rev Time 0.50
Received By pkrauss Date 2002-12-05 Time 13:36 Sent To  
Notes
2002-12-05 00:00:00PLAN SHEETM-1 PLEASE SEE NOTE #1
 BELOW.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, GAS, & WALK-IN COOLER/
 FREEZER.PROVIDE MANUFACTURER SUBMITTAL
 DATA & INSTALLATION INSTRUCTIONS WITH
 WALK-IN COOLER/FREEZER APPLICATION.
 IF CONDENSERS ARE REMOTE TYPE, PROVIDE
 SUBMITTAL ON COND UNIT STAND IF LOCATED
 ON THE ROOF.
  
 HOOD PLAN REVIEW:
 1.PLAN SHEET M-1 INDICATES 2 SF #1 ON
 THE PLAN & AIR BALANCE SCHEDULE.HOOD
 DEPOT DWG 1 & 3 INDICATE SF #1 & 2,
 PLEASE CORRECT PLAN SHEET M-1 TO REFLECT
 WHAT IS SHOWN ON SHOP DWG.
 PROVISO:
 TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP
 AIR & THE AIR IN THE CONDITIONED SPACE
 SHALL NOT EXCEED 10 DEGREES F.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-30 Cont ID  
Sent By pkrauss Date 2002-10-30 Time 15:11 Rev Time 0.50
Received By pkrauss Date 2002-10-30 Time 14:21 Sent To  
Notes
2002-10-30 00:00:00HVAC PLANS SUBMITTED ARE CODE COMPLIANT.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION & WALK-IN COOLER/FREEZER
  
 WALK-IN COOLERS & FREEZERS -
 PLEASE PROVIDE MANUFACTURER SUBMITTAL &
 INSTALLATION INSTRUCTIONS.INDICATE ON
 PLANS IF COOLERS ARE SELF CONTAINED OR
 HAVE A REMOTE CONDENSER.SHOULD
 CONDENSER BE REMOTE PROVIDE DETAIL OF
 STAND SHOWING COMPLIANCE WITH 2001 FBC
 1511.7 (MINIMUM CLEARANCE BETWEEN THE
 ROOF SURFACE & BOTTOM OF THE SUPPORT
 RAIL).
  
 HOOD & GREASE DUCT -
 SHOW COMPLIANCE WITH 2001 FBC(M) 506
 THRU 508 - GREASE DUCT, HOOD & MAKE UP
 AIR.PLEASE NOTE TERMINATION OF GREASE
 DUCT ABOVE THE ROOF SHALL BE A MINIMUM
 40" ABOVE THE ROOF SURFACE AS PER NFPA
 96.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By kstevens Date 2002-12-18 Time 13:42 Rev Time 1.25
Received By kstevens Date 2002-12-18 Time 13:42 Sent To B
Notes
2002-12-18 00:00:00PASSED PROVISO - REVISION REQUIRED FOR
 GAS RISER SHOWING RED LINE CHANGES PRIOR
 TO FINAL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-13 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 17:31 Rev Time 1.75
Received By kstevens Date 2002-12-13 Time 10:25 Sent To  
Notes
2002-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) SHTS P-1 AND P-2 FROM PREVIOUS RE-
 VIEW. ALL INDIRECT WASTE SHALL DRAIN IN-
 TO A FLOOR SINK. SEC 802.3 - SEE THE
 STEAMER, BOTH ICE BINS IN BAR AREA, AND
 CONDENSATE BY WATER HEATER.
 2) FOLLOWING ISSUES FOR GAS APPLICATION.
 FOLLOWING MANUFACTURE SHEETS NOT SUB-
 MITTED. STEAMER, CHEESE MELTER, ROTISS-
 ERIE, AND THE WATER HEATER.
 DISCREPENCIES BETWEET GAS RISER AND MAN-
 UFACTURE SHEETS. ***********
 CHARBROILER SHOWS 160K ON RISER - MANUF.
 SHEETS SHOW 195K.
 FRYERS SHOW (3) @ 122K ON RISER - MANUF.
 SHEETS SHOW 90K EACH.
 OVENS SHOW90K ON RISER - MANUF. SHEETS
 SHOW 88K.
 RANGE @ 230K NOT SHOWN ON RISER.
 PLEASE CLAIRFY. THIS SHALL AFFECT THE
 PIPE SIZING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By kstevens Date 2002-11-05 Time 09:58 Rev Time 5.00
Received By kstevens Date 2002-11-02 Time 18:17 Sent To  
Notes
2002-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) PLEASE ROUTE PLANS TO DEPT OF BUSIN-
 ESS REGULATION, HOTEL AND RESTAURANT DIV
 2) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES PER TABLE 1003.1 BLDG.
 CODE AND TABLE 403.1 PLUMBING CODE. IN-
 DICATE IF SEATING IS FIXED OR NOT.
 3) SHT D-1 ALL CAPPED OFF PLUMBING SHALL
 BE INSPECTED PRIOR TO COVERING.
 4) SHT P-1 PLUMBING NOTES #16, AIR CHAM-
 BERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE LOCATED NEAR THE FIXTURE IN AN "EFF-
 ECTIVE RANGE" NOT AT TOP OF DROP IN
 CEILING PER MANUFACTURE INSTALLATION IN-
 STRUCTIONS AND PDI-WH 201.
 5) RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE IN SPACE LOCATED MAXIMUM OF 4'
 AFF FOR SERVICING AND TESTING.
 6) SHTS P-1/P-3 FOOD PREP SINK, #56,
 SHALL BE DRAINED INDIRECTLY INTO A FLOOR
 SINK PER SECTION 802.1.1
 7) SHTS P-1/P-3 ALL INDIRECT WASTE SHALL
 BE DRAINED INTO A FLOOR SINK PER SECTION
 802.3. SAFE WASTES AND HUB DRAINS ARE
 NOT APPROVED.
 8) SHTS P-1/P-3 DISHWASHER SHALL DRAIN
 TO SANITARY NOT GREASE WASTE PER UTILITY
 DEPT.
 9) SHT P-2 INDICATE TEMPERATURE OF WATER
 FROM WATER HEATER. 110 DEGREE MAXIMUM
 TEMP. FOR HAND SINKS.
 10) SHT P-3 FLOOR DRAIN SHOWN ON SHT P-1
 NOT SHOWN ON SANT. RISER DIAGRAM.
 11) SHT A-1 DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY FIXTURE.
 SECTION 11-4.17.5. SEE MEN'S/WOMEN'S
 STALLS IN RESTROOMS
 12) SHT P-3 GAS PIPING NOTES #1, CODE
 IN USE FBC-2001 FUEL GAS, NOT STANDARD
 GAS CODE. PLEASE CHANGE REFERENCE.
 13) SHT P-3 GAS RISER DIAGRAM, TOTAL
 DEVELOPED LENGTH IS APPROX 150' NOT 137'
 AS SHOWN. PLEASE ADJUST PIPE SIZES NOTED
 IN RED ON PLANS AND CHANGE ACCORDINGLY.
 14) TYPE OF GAS, (LP OR NATURAL)
 15)SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 16) SHT P-3 GAS RISER DIAGRAM, UNION RE-
 QUIRED BETWEEN MANUAL SHUT OFF VALVE AND
 AUTOMATIC SHUT OFF VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377