Plan Review Details - Permit 02100786
Plan Review Stops For Permit 02100786
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By dpalmer Date 2002-11-04 Time 13:12 Rev Time 0.50
Received By dpalmer Date 2002-11-04 Time 13:12 Sent To B
Notes
2002-11-04 00:00:00********** NOTE *****
  
 MISSING RECEPT FOR PENINSULAR.
 210-52-C-2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-01 Cont ID  
Sent By hmoser Date 2002-11-01 Time 14:36 Rev Time 0.50
Received By hmoser Date 2002-11-01 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-28 Cont ID  
Sent By hmoser Date 2002-10-28 Time 18:27 Rev Time 0.50
Received By hmoser Date 2002-10-28 Time 18:27 Sent To  
Notes
2002-10-28 00:00:00PLAN/DENIED
 1) SOME DUCT DO NOT HAVE SIZES
 2) SOME CANS NOT MARKED SIZE,CFM
 3) NEED MANUFACTURE INSTALLITION
 INSTRUCTIONS ON GRILL
 MARKED ON PLAN
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-21 Cont ID  
Sent By kstevens Date 2002-12-21 Time 08:51 Rev Time 0.50
Received By kstevens Date 2002-12-21 Time 08:51 Sent To  
Notes
2002-12-21 00:00:00DENIED
 REFERENCE: FBC-2001 ADMINISTRATIVE CODE
 CHAPTER ONE
 FBC-2001 PLUMBING
  
 1) PER 104.2.1, AS REQUIRED BY 104.3.1.1
 OF THE CODE, TWO OR MORE COPIES OF SPEC-
 IFICATIONS, AND OF DRAWINGS TO SCALE
 WITH SUFFICIENT CLARITY AND DETAIL TO
 INDICATE NATURE AND CHARACTER OF THE
 WORK. - THESE REVISIONS NEED TO INDICATE
 ALL PIPE SIZES, TYPE OF FIXTURE, WHERE
 AIR ADMITTENCE VALVES ARE & MANUF./MODEL
 AND ALSO SHALL BE CLEAR AND EASY TO READ
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-10-26 Cont ID  
Sent By jleech Date 2002-10-26 Time 11:51 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
2002-10-26 00:00:00NO RISER DIAGRAM. NO PLUMBING PLAN REV.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By lhatten Date 2002-11-04 Time 17:37 Rev Time 2.50
Received By lhatten Date 2002-11-03 Time 17:36 Sent To  
Notes
2002-11-04 00:00:00REVIEW & STAMPED PLANS 11/03/2002
 CALC. FEES & PRINT CARD 11/04/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-18 Cont ID  
Sent By sgraham Date 2002-10-18 Time 11:07 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***