| 2002-10-28 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02100762 |
| | ADD: 804 S DIXIE |
| | CONT: BATTEN CONT |
| | TEL: (561)820-0027 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PROVIDE SOILS REPORT FOR CONTAMINATED |
| | SOILS & COMPACTION METHODS. |
| | |
| | 3)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. MISSING REPORTS: |
| | A) OVERHEAD GARAGE DOOR |
| | B) STOREFRONT WINDOW SYSTEM |
| | C) NEW STOREFRONT DOOR |
| | D) STORM PANELS |
| | E) ROOFING ASSEMBLIES, INSULATION/ ROOF |
| | |
| | 4)1606.4.4 ANCHOR METHODS. PROVIDE |
| | INFORMATION FOR INSTALLATION OF DOOR |
| | AND WINDOW BUCKS. |
| | |
| | 5)1707.4.4.1 ANCHOR REQUIREMENTS: |
| | WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| | ED IN ACCORDANCE WITH THE PUBLISHED |
| | MANUFACTURER'S RECOMMENDATIONS TO |
| | ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| | SUBSTITUTE ANCHORING SYSTEM USED FOR |
| | THE SUBSTRATE NOT SPECIFIED BY THE |
| | FENESTRATION MANUFACTURER SHALL PROVIDE |
| | EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| | TED BY ACCEPTED ENGINEERING PRACTICES. |
| | |
| | 6)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. MISSING CLEARENCE @ REST- |
| | ROOM DOOR, MINIMUM 12" LATCH SIDE. |
| | |
| | 7)PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| | EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| | TION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |