Plan Review Details - Permit 02100741
Plan Review Stops For Permit 02100741
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-28 Cont ID  
Sent By dpalmer Date 2002-10-28 Time 07:27 Rev Time 0.50
Received By dpalmer Date 2002-10-28 Time 07:27 Sent To B
Notes
2002-10-28 00:00:00************ NOTES / PROVISO *********
  
 1)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 2)NOTE: PLEASE NOTE KITCHEN COUNTERSPACE
 RECEPTS PER 210-52C-1
  
 3)NOTE: PLEASE NOTE MISSING HALLWAY
 RECEPTS PER 210-52H
  
 4)NOTE : PLEASE NOTE OUTLET SPACING PER
 210-52
  
 5)NOTE: PLEASE NOTE PANEL SCHEUDULE
 SHOWS ONE CENTRAL A/C SYSTEM AND PLANS
 SHOW TWO? PLEASE CORRELATE.
  
 PLEASE NOTE, PLANS NEED TO BE REVISED
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-26 Cont ID  
Sent By jleech Date 2002-10-26 Time 08:55 Rev Time 0.33
Received By jleech Date 2002-10-26 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-26 Cont ID  
Sent By jleech Date 2002-10-26 Time 08:55 Rev Time 0.25
Received By jleech Date 2002-10-26 Time 08:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By lhatten Date 2002-11-04 Time 18:11 Rev Time 3.00
Received By lhatten Date 2002-11-01 Time 18:11 Sent To  
Notes
2002-11-04 00:00:00REVIEW & STAMPED PLANS 11/01/2002
 CALC. FEES & PRINT CARD 11/04/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-24 Cont ID  
Sent By sgraham Date 2002-10-24 Time 15:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***