Plan Review Details - Permit 02100692
Plan Review Stops For Permit 02100692
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-19 Cont ID  
Sent By rbrown Date 2002-12-19 Time 09:51 Rev Time 0.00
Received By rbrown Date 2002-12-19 Time 09:50 Sent To  
Notes
2002-12-19 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 FBC 13-103.0THE SUBMITTED ENERGY CODE
 COMPLIANCE FORM HAS AN INCORRECT ADDRESS
 THE PROJECT INFORMATION SHALL BE
 AMENDED/ADDED AS FOLLOWS.
 ADDRESS: 210 VALENCIA ROAD
 CITY, STATE: WEST PALM BEACH, FL
 CLIMATE ZONE: 8
 BUILDER: ROGER G THOMAS
 PERMITTING OFFICE: WEST PALM BEACH
 PERMIT NUMBER: 02100692
 JURISDICTION NUMBER: 604700
  
 --PROVISO--
 FBC 2405.2THE GLASS IN THE FRAMELESS
 MASTER BATHROOM SHOWER DOOR SHALL BE
 SAFETY GLASS.
  
 --PROVISO--
 THE SUBMITTED COPIES OF PGT INDUSTRIES
 ALUMINUM TUBE CLIPPED MULLION PRODUCT
 APPROVAL NOA# 01-323.02 HAVE BEEN
 REPEATEDLY FAXED AND SOME OF THE NOTES
 ARE NOT LEGIBLE.SUBMIT LEGIBLE COPIES
 PRIOR TO WINDOW BUCK INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 13:13 Rev Time 0.00
Received By rbrown Date 2002-11-20 Time 13:23 Sent To  
Notes
2002-11-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 1804.2.2SUBMIT A SOIL REPORT
 FROM A FLORIDA LICENSED DESIGN
 PROFESSIONAL.
  
 2) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 3) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 - FRAMELESS MASTER BATH SHOWER DOOR
 - THE THREE WINDOWS ABOVE THE JACUZZI
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
  
 4) FBC 2309.6THE ATTIC ACCESS SHOWN
 SHALL PROVIDE ACCESS TO ALL ATTIC SPACES
 WITH A CLEAR HEIGHT OF NOT LESS THAN 24"
 OR ADDITIONAL ATTIC ACCESS OPENINGS WILL
 BE REQUIRED.
  
 5) FBC 2309.7ATTIC SPACE VENTILATION.
 THE CEILING INSULATION SHALL BE CLEAR OF
 THE UNDERSIDE OF THE ROOF DECKING SUCH
 THAT THE ATTIC SPACE VENTILATION IS
 MAINTAINED (REF SHEETS A-5 AND A-6, WALL
 SECTIONS)
  
 6) FBC 1007.3.3EXTERNAL STEP DETAIL,
 SHEET A-6.RISERS SHALL BE OF UNIFORM
 HEIGHT.THE TOP RISER HEIGHT SHOWN ON
 THE DETAIL IS 2" LESS THAN THE
 REMAINING RISERS.AMEND THE DETAIL.
  
 7) FBC 1012.1.5STEPS OUTSIDE FAMILY
 ROOM FRENCH DOORS.THERE SHALL BE NO
 MORE THAN ONE STEP (7" RISE, MAX.)
 BEFORE A LANDING OR GRADE ON THE
 EXTERIOR SIDE OF THE DOORS.AMEND THE
 PLANS.
  
 8) FLOOR TRUSS ANCHORS.WALL SECTION
 1/A-5 SHOWS USP HC-10 ANCHORS BETWEEN
 THE FLOOR TRUSS AND CONCRETE TIE BEAM.
 USP HC-10 ANCHORS ARE FOR CONECTIONS
 BETWEEN TRUSSES AND WOOD PLATES NOT
 CONCRETE. SPECIFY AN APPROPRIATE ANCHOR.
  
 9) PGT INDUSTRIES' SINGLE HUNG WINDOW
 PRODUCT APPROVAL NOA# 01-0629.08 COVERS
 SINGLE UNIT APPLICATIONS ONLY (SEE NOA
 SHEET 2, ITEM 3.1).SUBMIT A PRODUCT
 APPROVAL FOR AN APPROPRIATE WINDOW
 MULLION TO SUIT THE MULLED BREAKFAST
 ROOM, FAMILY ROOM AND MASTER BEDROOM
 WINDOWS.
  
 10) FBC* 104.2.1.2NEW 4"X 4" STEEL
 COLUMNS (DETAIL 2/A-2) ARE SPECIFIED
 WITHOUT REFERENCE TO CORROSION
 PROTECTION, ABOVE GROUND OR IN CONTACT
 WITH THE GROUND.AMEND THE PLANS TO
 STATE THE MEANS OF CORROSION PROTECTION.
  
 11) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-13 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 13:11 Rev Time 1.00
Received By btrobaug Date 2002-12-13 Time 11:24 Sent To B
Notes
2002-12-13 00:00:00PUT ON ROBERT BROWN'S DESK FROM WHENCE
 IT CAME./WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 18:13 Rev Time 1.00
Received By btrobaug Date 2002-10-31 Time 17:16 Sent To P
Notes
2002-11-01 00:00:00PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE NOTE ON THE RISER DIAGRAM SHOWS 2
 4/0 CU & 1-2/0 CU GROUND.
  
 A) THERE CAN BE NO EQ."GROUND" FROM
 THE METER TO THE DISCONNECT.
  
 B) THERE MUST BE AN EQUIPMENT GROUND
 FROM THE DISCONNECT TO THE PANEL.
  
 C) THERE MUST BE A NEUTRAL TO BOTH,
 PLEASE CLARIFY.
  
 3} THE #4 G.E.C. MUST BE A #1/OCU PER
 250-66,AND MUST HAVE A GROUND ROD IN
 THE SYSTEM PER 250-50(A)(2).
  
 4} RECEPTACLES MUST BE PROVIDED ON THE
 COUNTERTOPS TO THE WEST & EAST SIDE
 OF THE NORTH KITCHEN DOORS TO COMPLY
 WITH 210-52(C)(1).
  
 5} THE RECEPTACLE FOR THE JACUZZI MUST
 GFCI PROTECTED PER 680-70.
  
 6} THERE MUST BE A RECEPTACLE LOCATED IN
 THE ATTIC TO SERVICE THE AHU PER 210-
 63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-27 Cont ID  
Sent By btrobaug Date 2002-11-27 Time 12:05 Rev Time 0.00
Received By btrobaug Date 2002-11-27 Time 12:05 Sent To M
Notes
2002-11-27 00:00:00IN BOX./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 18:07 Rev Time 0.00
Received By btrobaug Date 2002-10-10 Time 18:06 Sent To E
Notes
2002-10-30 00:00:00TO WRT.10/30/02./WRT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2002-12-06 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 16:26 Rev Time 0.25
Received By pkrauss Date 2002-12-06 Time 16:26 Sent To B
Notes
2002-12-06 00:00:00MECHANICAL APPLIED SEPARATELY PERMIT
 02111600

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-27 Time 12:05 Rev Time 0.15
Received By pkrauss Date 2002-11-06 Time 12:51 Sent To  
Notes
2002-11-06 00:00:00AS PER CONVERSATION WITHROGER THOMAS,
 ACTION AIR & APPLIANCE TO APPLY FOR
 SEPARATE PERMIT & WILL SUBMIT PLANS &
 CALCS WITH MECH PERMIT APPLICATION.
  
 11/6/02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-04 Cont ID  
Sent By pkrauss Date 2002-11-04 Time 09:50 Rev Time 0.40
Received By pkrauss Date 2002-11-04 Time 08:17 Sent To B
Notes
2002-11-04 00:00:00DENIED:
  
 NO MECHANICAL INFORMATION SUBMITTED FOR
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 INFORMATION.
  
 INDICATE IF A/C SYSTEM WILL BE NEW OR
 EXISTING.PROVIDE THE FOLLOWING
 MANUFACTURER INFORMATION - MODEL #, BTU,
 KW HEAT STRIP, & SEER OF CONDENSER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-02 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 09:34 Rev Time 0.50
Received By kstevens Date 2002-11-02 Time 05:56 Sent To  
Notes
2002-11-02 00:00:00PASSED PROVISO - CAPPED OFF PLUMBING
 FOR DEMO SHALL BE INSPECTED PRIOR TO
 COVERING

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-24 Cont ID  
Sent By sgraham Date 2002-10-24 Time 16:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***