| 2002-11-20 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC* 1804.2.2SUBMIT A SOIL REPORT |
| | FROM A FLORIDA LICENSED DESIGN |
| | PROFESSIONAL. |
| | |
| | 2) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 3) FBC 2405.2THE FOLLOWING GLAZING IS |
| | IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201): |
| | - FRAMELESS MASTER BATH SHOWER DOOR |
| | - THE THREE WINDOWS ABOVE THE JACUZZI |
| | SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE |
| | |
| | 4) FBC 2309.6THE ATTIC ACCESS SHOWN |
| | SHALL PROVIDE ACCESS TO ALL ATTIC SPACES |
| | WITH A CLEAR HEIGHT OF NOT LESS THAN 24" |
| | OR ADDITIONAL ATTIC ACCESS OPENINGS WILL |
| | BE REQUIRED. |
| | |
| | 5) FBC 2309.7ATTIC SPACE VENTILATION. |
| | THE CEILING INSULATION SHALL BE CLEAR OF |
| | THE UNDERSIDE OF THE ROOF DECKING SUCH |
| | THAT THE ATTIC SPACE VENTILATION IS |
| | MAINTAINED (REF SHEETS A-5 AND A-6, WALL |
| | SECTIONS) |
| | |
| | 6) FBC 1007.3.3EXTERNAL STEP DETAIL, |
| | SHEET A-6.RISERS SHALL BE OF UNIFORM |
| | HEIGHT.THE TOP RISER HEIGHT SHOWN ON |
| | THE DETAIL IS 2" LESS THAN THE |
| | REMAINING RISERS.AMEND THE DETAIL. |
| | |
| | 7) FBC 1012.1.5STEPS OUTSIDE FAMILY |
| | ROOM FRENCH DOORS.THERE SHALL BE NO |
| | MORE THAN ONE STEP (7" RISE, MAX.) |
| | BEFORE A LANDING OR GRADE ON THE |
| | EXTERIOR SIDE OF THE DOORS.AMEND THE |
| | PLANS. |
| | |
| | 8) FLOOR TRUSS ANCHORS.WALL SECTION |
| | 1/A-5 SHOWS USP HC-10 ANCHORS BETWEEN |
| | THE FLOOR TRUSS AND CONCRETE TIE BEAM. |
| | USP HC-10 ANCHORS ARE FOR CONECTIONS |
| | BETWEEN TRUSSES AND WOOD PLATES NOT |
| | CONCRETE. SPECIFY AN APPROPRIATE ANCHOR. |
| | |
| | 9) PGT INDUSTRIES' SINGLE HUNG WINDOW |
| | PRODUCT APPROVAL NOA# 01-0629.08 COVERS |
| | SINGLE UNIT APPLICATIONS ONLY (SEE NOA |
| | SHEET 2, ITEM 3.1).SUBMIT A PRODUCT |
| | APPROVAL FOR AN APPROPRIATE WINDOW |
| | MULLION TO SUIT THE MULLED BREAKFAST |
| | ROOM, FAMILY ROOM AND MASTER BEDROOM |
| | WINDOWS. |
| | |
| | 10) FBC* 104.2.1.2NEW 4"X 4" STEEL |
| | COLUMNS (DETAIL 2/A-2) ARE SPECIFIED |
| | WITHOUT REFERENCE TO CORROSION |
| | PROTECTION, ABOVE GROUND OR IN CONTACT |
| | WITH THE GROUND.AMEND THE PLANS TO |
| | STATE THE MEANS OF CORROSION PROTECTION. |
| | |
| | 11) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |