| 2002-11-19 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02100668 |
| | ADD: 4821 S FLAGLER DR |
| | CONT: P. M. WRIGHT CONSTRUCTION |
| | TEL: (561)863-5088 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) 3109.1.3 FLOODPLAIN CONSTRUCTION |
| | SHALL COMPLY WITH THE PROVISIONS OF |
| | CHAPTER 12, FLOOD PREVENTION AND CONTROL |
| | OF THE CODE OF THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | CHAP 12 SEC 12-22 PROVISIONS FOR |
| | FLOOD HAZARD REDUCTION,(B)(1) ALL NEW |
| | CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT |
| | OF ANY EXISTING RESIDENTIAL STRUCTURE |
| | SHALL HAVE THE LOWEST FLOOR, INCLUDING |
| | BASEMENT, ELEVATED TO SIX(6) INCHES |
| | ABOVE THE FLOOD ELEVATION (7'-6"). |
| | |
| | CHAP 12 SEC 12-17 DEFINITIONS: |
| | SUBSTANTIAL IMPROVEMENTS: MEANS ANY COM- |
| | BINATION OF REPAIRS, RECONSTRUCTION, |
| | ALTERATION,OR IMPROVEMENTS TO A STRUC- |
| | TURE, TAKING PLACE DURING THE LIFE OF A |
| | STRUCTURE IN WHICH THE CUMULATIVE COST |
| | EQUALS OR EXCEEDS FIFTY PER CENT OF THE |
| | MARKET VALUE OF THE STRUCTURE. |
| | |
| | PROPERTY APPRAISERS IMPROVEMENT |
| | VALUEIS $104,375.00 . THE REMODEL & |
| | ADDITION VALUE OF THE CURRENT PROJECT IS |
| | $180,000.00+ OR OVER 50% OF THE IMPROVE- |
| | MENT VALUE. THIS MEANS THAT THE FLOOR |
| | LEVEL OF THE EXISTING STRUCTURE PLUS THE |
| | FLOOR OF THE NEW WORK WOULD BE REQUIRED |
| | TO BE ABOVE 7'-6" . |
| | |
| | 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | |
| | 4)905.2.1 APPROVED SINGLE-STATION OR |
| | MULTIPLE STATION SMOKE DETECTORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| | CHAPTER 2, WITHIN EVERY DWELLING UNIT |
| | WITHIN AN APARTMENT HOUSE, CONDOMINIMUM, |
| | OR TOWNHOUSE AND EVERY GUEST OR SLEEPING |
| | ROOM IN A MOTEL, HOTEL, OR DORMITORY & |
| | SLEEPING ROOMS IN RESIDENTIAL CARE/ |
| | ASSISTED LIVING OCCUPANCIES. WHERE MORE |
| | THAN ONE DETECTOR IS REQUIRED TO BE |
| | INSTALLED WITHIN INDIVIDUAL DWELLING |
| | UNIT, THE DETECTOR SHALL BE WIRED IN |
| | SUCH A MANNER THAT THE ACTUATION OF ONE |
| | ALARM WILL ACTIVATE ALL THE ALARMS IN |
| | THE INDIVIDUAL UNIT. |
| | |
| | 5)905.2.1 RESIDENTIAL SMOKE ALARMS: |
| | NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH |
| | MORE THAN ONE BEDROOM AREA OR WITH BED- |
| | ROOMS ON MORE THAN ONE FLOOR, MORE THAN |
| | ONE SMOKE DETECTOR IS REQUIRED. |
| | |
| | 6)FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 7)1503.4 ROOF DRAINS UNLESS ROOFS ARE |
| | SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF |
| | DRAINS SHALL BE INSTALLED AT THE LOWEST |
| | POINT OF THE ROOF. WHERE REQUIRED FOR |
| | ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED |
| | AS DETERMINED BY THE ROOF SLOPE AND CON- |
| | TRIBUTING ROOF AREA. FLAT ROOFED AREA, |
| | DRAINAGE? |
| | |
| | 8)1503.4.2 OVERFLOW DRAINS SHALL BE |
| | THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| | WITH THE INLET FLOW LINE LOCATED 2" |
| | ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| | 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| | OR PARARETS WITH THE INLET FLOW LINE |
| | NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| | |
| | 9) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED.MISSING REPORTS: |
| | A) FRENCH DOORS- IMPACT |
| | B) SINGLE HUNG- IMPACT |
| | C) OVERHEAD GARAGE DOOR 9X7, 16X7 |
| | D) MULLIONS- IMPACT/ W CLIPS |
| | E) ROOFING ASSEMBLIES- BUILT UP ROOF |
| | |
| | 10) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 11) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 12)FL BLD CODE 2309.6 ATTIC ACCESS, PRO- |
| | VIDE ATTIC ACCESS 20"X36". GARAGE & |
| | 2ND STORY. |
| | |
| | 13) DISCREPANCY, ENERGY CALCS CEILING |
| | INSULATION R19 VS A-8 DETAIL R30. |
| | |
| | 14) SHEET A-6 NOTE# 9 REFRENCES HUGHES |
| | STRAP, OUT OF BUSINESS:REFRENCE CURRENT |
| | MANUFACTURER/ MODEL. |
| | |
| | 15)PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | TRUSS ENGINEERING SHEET NOT SIGNED |
| | & SEALED. |
| | |
| | 16) SHEET A-7 DETAIL# 1 INDICATES THE |
| | USE OF 3/4" EXPANSION BOLTS, NO EMBED |
| | LENGHT OR OVERALL LENGHT IS GIVEN? |
| | |
| | 17) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A-7 DETAIL 2, KNEE WALL, THE FLAT |
| | ROOF TRUSS & 2X12 RAFTER ARE STRAPED TO |
| | THE KNEE WALL WITH A MTS16 (1000 LBS) |
| | UPLIFT, WHILE THE BOTTOM OF THE KNEE |
| | WALL IS STRAPED WITH A H2.5 (415 LBS) |
| | CAPACITY OF UPLIFT, WHAT WILL BE THE |
| | UPLIFT LOADS IMPOSED? |
| | |
| | 18) SHEET A-8 ALL DETAILS ARE MISSING |
| | A VAPOR BARRIER REQUIRED FOR MONOLITHIC |
| | SLABS (DAMPPROOFING) 1814.3.2/1816.1.4 |
| | |
| | 19)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |