Plan Review Details - Permit 02100647
Plan Review Stops For Permit 02100647
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-01-17 Cont ID  
Sent By lsmith Date 2003-01-17 Time 14:56 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 12:40 Rev Time 0.50
Received By btrobaug Date 2002-11-25 Time 12:06 Sent To R
Notes
2002-11-25 00:00:00 
 TO LOU HATTEN./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-18 Cont ID  
Sent By btrobaug Date 2002-10-18 Time 16:44 Rev Time 1.00
Received By btrobaug Date 2002-10-18 Time 15:53 Sent To B
Notes
2002-10-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5} THE HALL SMOKE DETECTOR BETWEEN BED
 ROOMS 2 & 3 MUST COMPLY WITH ARTICLE
 8-1.4.2 NFPA-72 (3' FROM KITCHEN DOOR
 ETC.).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-12 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 15:54 Rev Time 0.00
Received By btrobaug Date 2002-11-12 Time 15:54 Sent To P
Notes
2002-11-12 00:00:00TO "P" RES RACK./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-11 Cont ID  
Sent By pkrauss Date 2002-10-11 Time 08:16 Rev Time 0.30
Received By pkrauss Date 2002-10-11 Time 08:07 Sent To  
Notes
2002-10-11 00:00:00PROVISO:MECHANICAL PERMIT 02100651
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).BEDROOMS SHALL HAVE R/A.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 BATHROOMS SHALL HAVE MECHANICAL EXHAUST
 AS PER 2001 FBC(M) 402.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-11 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 15:55 Rev Time 0.00
Received By kstevens Date 2002-10-11 Time 16:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-12-02 Cont ID  
Sent By lhatten Date 2002-12-02 Time 07:55 Rev Time 1.00
Received By lhatten Date 2002-11-30 Time 07:54 Sent To  
Notes
2002-12-02 00:00:00SUBMITTED NEW PRODUCT APPR. & SPECIFIED
 COLUMNS ECT. 11/30/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-10-18 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 12:40 Rev Time 2.00
Received By lhatten Date 2002-10-17 Time 15:15 Sent To  
Notes
2002-10-18 00:00:001) ALUMINUM FIXED WINDOW - PRODUCT
 APPROVALS EXPIRED -- NEED NEW SETS (2)
  
 2) FRONT ELEVATIONS - BOTH WINDOW & DOOR
 NEED PRESSURES ( +,- )
  
 3) CLARIFY FRONT COLUMNS ROUND OR SQUARE
  
 4) CLARIFY CONCRETE PADS AS TO SIZES IN
 FRONT FOUNDATION PLAN

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-10 Cont ID  
Sent By sgraham Date 2002-10-10 Time 16:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***