Plan Review Details - Permit 02100615
| Plan Review Stops For Permit 02100615 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-29 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-29 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2002-10-29 00:00:00 | THE TWO DOORS IN A SERIES, (VESTIBULES) | | | DO NOT APPEAR TO PROVIDE THE 48" | | | DISTANCE BETWEEN IN ACCORDANCE WITH FBC | | | 11-4.13.7 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-10-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-10-22 |
Time |
13:16 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-22 00:00:00 | PLUMBING PLAN REVIEW, FBC 2001 DENIED | | | (1) SHT T-1,T-2 FACBC 2001 SEC 11-4.1.6 | | | (2)(III), ALTERATIONS TO AN AREA CONTAN- | | | ING PRIMARY FUNCTION, 20% OF THE COST O | | | THE ALTERATIOIN,TO BE USED TO COMPLY W/ | | | SEC 11-417.3 (1), STALL TO CONTAINAN | | | ACCESSIBLE LAVATORY. | | | (2) SHT T-1 MENS RM, QUESTION ON WHAT IS | | | IN THE TURNING RADIUS SPACE? | | | (3) SHT T-1 QUESTION ON BABY CHANGING | | | STATION WHEN IN USE AND OTHER PATRONS | | | TRYING TO USE FACILITIES? | | | (4) SHT T-1 NOTE REGARDING USE OF FACIL- | | | ITIES WHILE CONSTRUCTION IS IN PROGRESS. | | | WILL NOT BE ALLOWED, AS PER B/O NKM. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |