Plan Review Details - Permit 02100582
Plan Review Stops For Permit 02100582
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-28 Cont ID  
Sent By jwitmer Date 2002-10-28 Time 14:39 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2002-11-20 Time 06:15 Rev Time 0.25
Received By dpalmer Date 2002-11-20 Time 06:11 Sent To  
Notes
2002-11-20 00:00:00************ NOTES REDLINED **********
  
 1)NOTE: PLEASE SUBMIT CIRCUITING ON PLAN
 -S FOR ALL NEW ELECTRICAL. CORRELATE
 W/ A SUBMITTED PANEL SCHEDULE.
  
 NOTE REDLINED FOR CIRCUITING OF
 EM LTS AND EXT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL INSPECT-
 -ION IS CALLED IN. IFTHERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2002-10-10 Time 06:59 Rev Time 0.50
Received By dpalmer Date 2002-10-10 Time 06:59 Sent To  
Notes
2002-10-10 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT ALL HANDWRITTEN
 CHANGES ON PLANS NEED TO BE RE-PRINTED
 AND SIGNED AND SEALED BY ENGINEER OF
 RECORD. FS/FAC 471.025
 EACH HAND WRITTEN ITEM ON PLAN MAY BE
 INITIALED AND DATED BY ENGINEER OF
 RECORD AS AN ALTERNATIVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-21 Cont ID  
Sent By mcarsill Date 2002-11-21 Time 16:49 Rev Time 0.00
Received By mcarsill Date 2002-11-21 Time 16:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-01 Cont ID  
Sent By mcarsill Date 2002-11-01 Time 16:16 Rev Time 0.00
Received By mcarsill Date 2002-11-01 Time 16:16 Sent To  
Notes
2002-11-01 00:00:001) PLANS FAILS TO INDICATE ANY NEW OR
 EXISTING EMERGENCY LIGHTS OR EXIT SIGNS.
 PLEASE INDICATE ALL LOCATIONS ON PLANS.
  
 2) PLANS FAIL TO INDICATE PROPOSED
 OCCUPANT LOADS.
  
 3) PLANS DO NOT DISPLAY INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 4) PLANS MAKE NO REFERENCE TO ANY
 PORTABLE FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 15:43 Sent To  
Notes
2002-11-15 00:00:00TO COMM BORAD #25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-10-29 Cont ID  
Sent By pkrauss Date 2002-10-29 Time 15:57 Rev Time 0.00
Received By pkrauss Date 2002-10-29 Time 15:57 Sent To  
Notes
2002-10-29 00:00:00NO MECHANICAL WORK INDICATED ON PLAN.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-11-02 Cont ID  
Sent By kstevens Date 2002-11-02 Time 14:05 Rev Time 0.25
Received By kstevens Date 2002-11-02 Time 14:05 Sent To  
Notes
2002-11-02 00:00:00NO PLUMBING WORK INDICATED ON PLAN