Plan Review Details - Permit 02100473
Plan Review Stops For Permit 02100473
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-29 Cont ID  
Sent By hpiskura Date 2002-10-29 Time 13:38 Rev Time 0.00
Received By hpiskura Date 2002-10-29 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-10 Cont ID  
Sent By dpalmer Date 2002-10-10 Time 08:36 Rev Time 0.50
Received By dpalmer Date 2002-10-10 Time 08:35 Sent To  
Notes
2002-10-10 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS/480V ARE REQ`D
 TO BE DONE BY AN ENGINEER FBC 104.4.1.3,
 FS 553-79-6, 471.003.
  
  
 2)NOTE: PLEASE NOTE PLANS ARE SHOWING
 A COMPLETE NEW SERVICE. PLEASE CLARIFY
 LOCATION AND OR IF EXISTING SERVICE IS
 BEING REMOVED?
  
 3)NOTE: PLEASE NOTE VOLTAGE ON TRANS-
 -FORMER SHOWN AT 408V?
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS. TABLE 250-122
  
 5)NOTE:PLEASE SHOW GROUNDING FOR TRANS-
 -FORMERS PER 250-50
  
 6)NOTE: PLEASE NOTE ALL CIRCUITING NEEDS
 TO BE ON PLANS AND CORRELATE W/ PANEL
 SCHEDULES.
  
 7)NOTE: PLEASE NOTE MISSING DETAIL FOR
 GROUNDING ELECTRODE SYSTEM.
  
 8)NOTE: PLEASE SEE FIRE REVIEW COMMENTS,
 PLEASE NOTE 700-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-08 Cont ID  
Sent By mcarsill Date 2002-10-08 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2002-10-08 Time 13:03 Sent To  
Notes
2002-10-08 00:00:001) ALL WORK TO COMPLY WITH LIFE SAFETY
 CODE, NFPA 101 2000 EDITION.
  
 2) PLEASE INDICATE THE LOCATION OF EXIT
 SIGNS AND EMERGENCY LIGHTING.
  
 3) BUILDING FIRE PROTECTION EQUIPMENT TO
 REMAIN OPERABLE DURING DEMOLITION AND
 CONSTRUCTION.
  
 4) DEMOLITION DEBRIS TO REMOVED DAILY.
  
 5) PLEASE INDICATE THE TYPE OF INTERIOR
 FINISH.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-29 Cont ID  
Sent By pkrauss Date 2002-10-29 Time 11:22 Rev Time 0.45
Received By pkrauss Date 2002-10-29 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-28 Cont ID  
Sent By pschmitz Date 2002-10-28 Time 09:57 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-10-28 00:00:00PLUMBING PLAN REVIEW, FBC 2001, DENIED.
 (1) SHT 3 & 5
 SHOW H/C DETAILS WITH ELIVATIONS AND
 DIMENSIONS OF BREAK ROOM SINK, WATER
 COOLER, DRESSING ROOM WITH BENCH AND
 CLEAR FLOOR SPACE, SEC 104.3
 (2) SHT P-1
 PROVIDE A ISOMETRIC DRAWING OF WATER
 PIPING, LIST TYPE OF MATERIAL, LOCATION
 AND TYPE OF WATER HAMMER ARRESTOR IF
 USED. SEC 104.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233