Plan Review Details - Permit 02100435
Plan Review Stops For Permit 02100435
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-25 Cont ID  
Sent By pkrauss Date 2002-11-22 Time 15:28 Rev Time 0.00
Received By hpiskura Date 2002-11-22 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By pkrauss Date 2002-11-22 Time 08:15 Rev Time 0.00
Received By hpiskura Date 2002-11-05 Time 10:16 Sent To  
Notes
2002-11-05 00:00:00THE PROPOSED ADDITION IS SUBJECT TO
 IMPACT FEES COLLECTED BY THE COUNTY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 PROVIDE ATTIC VENTILATION IN ACCORDANCE
 WITH FBC 2309.7.
  
 THE PRODUCT NOA 01-0711.03 FOR THE
 SINGLE HUNG WINDOW IS ILLEGIBLE.
 PLEASE PROVIDE CLEAR COPIES.
  
 SHOW HOW THE HURRICANE MISSILE IMPACT
 RESISTANCE, (SHUTTERS), WILL BE
 ACCOMPLISHED.
  
 SHOW THE COMPONENT AND CLADDING
 PRESSURES FOR THE ROOF.SEE FBC
 1606.1.7.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-16 Cont ID  
Sent By btrobaug Date 2002-10-16 Time 14:38 Rev Time 0.50
Received By btrobaug Date 2002-10-16 Time 13:44 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 14:53 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 14:52 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-22 Cont ID  
Sent By pkrauss Date 2002-11-22 Time 07:56 Rev Time 0.35
Received By pkrauss Date 2002-11-22 Time 07:47 Sent To B
Notes
2002-11-22 00:00:00PROVISO:
  
 MANUAL J CALCS INDICATE A 5.4 TON SYSTEM
 IS THIS CORRECT FOR 1,338 SQ FT?PLANS
 INDICATE A 2.5 TON SYSTEM.PLEASE
 REVISE & SUBMIT MANUAL J CALCS THAT
 COINCIDE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-19 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 14:53 Rev Time 0.50
Received By hmoser Date 2002-10-19 Time 12:08 Sent To B
Notes
2002-10-19 00:00:00PLAN DENIED
 1) NO ENERGY CALCULATIONS
 2) NO DUCT SIZE ON ADDITION
 3) CHECK SIZE OF A/C SYSTEM.5 TON FOR
 1338 SQ.FT
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-18 Cont ID  
Sent By btrobaug Date 2002-10-16 Time 14:38 Rev Time 0.25
Received By kstevens Date 2002-10-18 Time 19:26 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-09 Cont ID  
Sent By sgraham Date 2002-10-09 Time 13:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***