Plan Review Details - Permit 02100425
Plan Review Stops For Permit 02100425
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-07 Cont ID  
Sent By hpiskura Date 2003-02-07 Time 07:54 Rev Time 0.00
Received By hpiskura Date 2003-02-05 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-01-03 Cont ID  
Sent By jwitmer Date 2003-01-03 Time 09:02 Rev Time 3.75
Received By jwitmer Date   Time   Sent To  
Notes
2003-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02100425
 ADD: 6901 OKEECHOBEE BLVD
 CONT: D & J CONSTRUCTION
 TEL: (954)689-6405 #204
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) MISSING ORIGINAL PERMIT APPLICATION
 ONLY 1ST RESUB SHEET SUBMITTED.
  
 2) AS INDICATED ON FIRST REVIEW, PERMIT
 FEES ARE TO LOW, PROVIDE A SIGNED COPY
 OF CONTRACT WITH DETAILED TAKE OFF.
  
 3)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 THE PRODUCT TESTING REPORT SUBMITTED IN-
 DICATES IT IS FOR WIND, NOT LARGE MISSLE
 IMPACT RESISTANT.
 W.P.B. STANDARD FOR LARGE MISSLE IMPACT:
 (17) IF THE PRODUCT TESTING REPORTS
 SUBMITTED AT TIME OF PERMIT APPLICATION
 DO NOT REFRENCE THE LARGE MISSLE TESTING
 THEN A SEPERATE PERMIT WILL BE REQUIRED
 FOR THE PROTECTION DEVICE/ ASSEMBLY AND
 NO CERTIFICATE OF OCCUPANCY OR CERTIFI-
 CATE OF COMPLETION SHALL BE ISSUED UNTIL
 INSTILLATION OF GLAZING PROTECTION IS
 COMPLETE. PROVIDE STORM SHUTTER APPROVAL
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 PROVIDE INFORMATION AS WHEN STORM
 SHUTTERS ARE BEING INSTALLED HOW WILL
 CUSTOMERS AND EMPLOYEES EXIT THE BUILD-
 ING. PROVIDE A LIFE SAFETY PLAN FOR THIS
 SENARIO!
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-11 Cont ID  
Sent By hpiskura Date 2002-10-11 Time 14:06 Rev Time 0.00
Received By hpiskura Date 2002-10-11 Time 11:25 Sent To  
Notes
2002-10-11 00:00:00PROVIDE NOTICE OF ACCEPTANCE AND/OR TEST
 REPORTS FOR THE STORE FRONT DOOR
 SYSTEM AND SHOW HOW HURRICANE MISSILE
 IMPACT RESISTANCE WILL BE ACCOMPLISHED.
 SEE FBC 1606.1.4.
  
 THE $20,000.00 DECLARED PERMIT VALUATION
 APPEARS TOO LOW FOR THIS SCOPE OF WORK.
 PLEASE PROVIDE A COPY OF THE SIGNED
 CONTRACT AND A DETAILED TAKEOFF.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 12:24 Rev Time 0.25
Received By dpalmer Date 2003-02-13 Time 12:23 Sent To  
Notes
2003-02-13 00:00:00NO CHANGES SAME PLANS,

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 15:19 Rev Time 0.25
Received By dpalmer Date 2002-12-27 Time 15:19 Sent To  
Notes
2002-12-27 00:00:00SAME PLANS, NO CHANGES.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-10 Cont ID  
Sent By dpalmer Date 2002-10-10 Time 06:33 Rev Time 0.50
Received By dpalmer Date 2002-10-10 Time 06:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-02-19 Cont ID  
Sent By nmccray Date 2003-02-19 Time 11:30 Rev Time 0.00
Received By nmccray Date 2003-02-19 Time 11:30 Sent To  
Notes
2003-02-19 00:00:00PROVISO
 1) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS REMODEL.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD AND SUPPRESSION SYSTEMS.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 09:34 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-31 Cont ID  
Sent By mcarsill Date 2002-10-31 Time 08:44 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 08:44 Sent To  
Notes
2002-10-31 00:00:001) ALL EXITS ARE TO REMAIN CLEAR
 AND ACCESSIBLE DURING CONSTRUCTION.
  
 2) DUST AND SECURITY PARTITIONS ARE NOT
 TO BE CONSTRUCTED OF NON FIRE RATED
 MATERIALS. VISQUEEN AND OTHER NON
 APPROVED MATERIALS SHALL NOT BE USED.
  
 3) NEW SLIDING DOORS AT NEW ENTRANCE TO
 COMPLY WITH THE 2000 LSC, SECTION
 7.2.1.9.1.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW HOOD,DUCT AND EXTINGUISHING
 SYSTEMS.
  
 5) PLEASE INDICATE NEW INTERIOR FINISHES
 PLANNED FOR THE LOCATION. PLEASE
 INDICATE WHAT CLASSIFICATION.
  
 6) THE FIRE SPRINKLER SYSTEM SHALL
 REMAIN ON AT ALL TIMES. THE FIRE
 SPRINKLER SYSTEM SHALL NOT BE TURNED
 OFF UNLESS ABSOLUTLELY NECESSARY.
 NOTIFICATION OF FIRE RESCUE IS REQUIRED.
 APPROVED FIRE WATCH ACTIVITIES WILL
 ALSO BE REQUIRED.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER SYSTEM REMODEL.
  
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-30 Cont ID  
Sent By btrobaug Date 2003-01-30 Time 16:22 Rev Time 0.00
Received By btrobaug Date 2003-01-29 Time 16:22 Sent To  
Notes
2003-01-30 00:00:00COM BOARD #42./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-12 Time 14:12 Rev Time 0.00
Received By btrobaug Date 2002-12-12 Time 14:12 Sent To  
Notes
2002-12-12 00:00:00COMM BOARD #3./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-13 Cont ID  
Sent By pkrauss Date 2003-02-13 Time 13:05 Rev Time 0.35
Received By pkrauss Date 2003-02-13 Time 12:48 Sent To  
Notes
2003-02-13 00:00:00PROVISO:
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD AND
 FIRE SUPRESSION.PROVIDE MANUFACTURER
 SUBMITTAL DATA & PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-30 Cont ID  
Sent By pkrauss Date 2002-10-29 Time 16:26 Rev Time 0.00
Received By pkrauss Date 2002-10-29 Time 12:48 Sent To  
Notes
2002-10-29 00:00:00PROVISO:
  
 PRESSURE TEST & INPSECTION REQUIRED FOR
 ANY NEW REFRIGERATION LINES BEING
 INSTALLED.
  
  
 ***************PLEASE NOTE**************
  
 THE ABOVE REVIEW DOES NOT INCLUDE HOOD
 & FIRE SUPRESSION.PLEASE PROVIDE THE
 THE FOLLOWING:
  
 SEPARATE PERMIT REQUIRED FOR HOOD & FIRE
 SUPRESSION.PROVIDE DETAIL OF GREASE
 DUCT LAYOUT & CLEARANCE TO COMBUSTIBLES.
 SPECIFY IF THE NEW HOOD IS TO BE
 INSTALLED AT THE SAME LOCATION OF THE
 EXISTING HOOD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-05 Cont ID  
Sent By kstevens Date 2003-02-05 Time 07:44 Rev Time 0.25
Received By kstevens Date 2003-02-05 Time 07:44 Sent To  
Notes
2003-02-05 00:00:00PASSED/PROVISO - ALL INDIRECT WASTE
 SHALL DRAIN TO FLOOR SINKS - GAS PERMIT
 REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-02 Cont ID  
Sent By kstevens Date 2002-11-02 Time 06:54 Rev Time 1.50
Received By kstevens Date 2002-11-02 Time 06:53 Sent To  
Notes
2002-11-02 00:00:00PASSED - PROVISO-ALL INDIRECT WASTE
 TO FLOOR SINKS-GAS PERMIT REQUIRED.