Plan Review Details - Permit 02100398
Plan Review Stops For Permit 02100398
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-13 Cont ID  
Sent By lmartine Date 2002-12-13 Time 17:25 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-12-05 Cont ID  
Sent By pkrauss Date 2002-12-10 Time 15:29 Rev Time 0.00
Received By hpiskura Date 2002-12-04 Time 16:23 Sent To  
Notes
2002-12-05 00:00:00THE 2'-10" DOORS PROPOSED FOR THE NEW
 OFFICE SPACES WILL NOT MEET THE MINIMUM
 32" WIDTH FOR HANDICAP ACCESSIBILITY AS
 PROVIDED FOR IN FBC 11-4.13.5PLEASE
 REVISE AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-11 Cont ID  
Sent By hpiskura Date 2002-10-11 Time 11:19 Rev Time 0.00
Received By hpiskura Date 2002-10-11 Time 11:14 Sent To  
Notes
2002-10-11 00:00:00PLEASE PROVIDE DRAFTSMAN QUALITY
 DRAWINGS WITH PROPER DIMENSIONS, SCALE,
 AND NOTES AS NECESSARY.SEE FBC 104.2.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 08:03 Rev Time 0.25
Received By dpalmer Date 2002-11-15 Time 08:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-07 Cont ID  
Sent By dpalmer Date 2002-10-07 Time 07:37 Rev Time 0.25
Received By dpalmer Date 2002-10-07 Time 07:37 Sent To  
Notes
2002-10-07 00:00:00************* USNAT ******************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE W/ PANEL SCHEDULE.
  
 2)NOTE: PLEASE NOTE PLANS SHOWN A NEW
 A/C. PLEASE NOTE NOTHING SHOWN ON
 ELECTRICAL PLANS. PLEASE NOTE DISC REQ`D
 PER 440-11. PLEASE SUBMIT LOAD
 CALCULATIONS FOR ADDING NEW A/C.
 SHOW SIZE OF EXSITING SERVICE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-14 Cont ID  
Sent By mcarsill Date 2002-11-14 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2002-11-14 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-08 Cont ID  
Sent By mcarsill Date 2002-10-08 Time 09:49 Rev Time 0.00
Received By mcarsill Date 2002-10-08 Time 09:49 Sent To  
Notes
2002-10-08 00:00:001) PLANS DO NOT SHOW THE LOCATIONS OF
 EXISTING OR NEW EXIT SIGNS. PLEASE SHOW
 HOW OCCUPANTS WILL EXIT THE SPACE.
  
 2) IS THERE EXISTING EMERGENCY LIGHTING
 AND WHAT ARE THE LOCATIONS?
  
 3) THE PLAN DOES NOT INDICATE THE TYPE
 OF INTERIOR FINISH BEING USED. PLEASE
 INDICATE THE TYPE OF INTERIOR FINISH.
  
 4) IS THERE A FIRE SPRINKLER AND ALARM
 SYSTEM IN THIS BUILDING AND IF SO, HOW
 DOES THIS WORK IMPACT THOSE SYSTEMS?
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 16:39 Rev Time 0.00
Received By btrobaug Date 2002-12-05 Time 16:39 Sent To  
Notes
2002-12-05 00:00:00COMM BOARD #4./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2002-11-13 Time 14:45 Sent To  
Notes
2002-11-13 00:00:00TO COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-10 Cont ID  
Sent By pkrauss Date 2002-12-10 Time 15:23 Rev Time 0.30
Received By pkrauss Date 2002-12-10 Time 15:23 Sent To  
Notes
2002-12-10 00:00:00PROVISO:
  
 PLEASE NOTE PLAN SHEET A-1 SECTION
 DETAIL 1 INDICATES A FIRE RATED WALL.
  
 DUCTS PENETRATING WALLS OR PARTITIONS
 HAVING A FIRE RESISTANCERATING OF 1
 HR OR MORE SHALL HAVE FIRE DAMPERS &
 BE CONSTRUCTED OF METAL IN ACCORDANCE
 WITH 2001 FBC(M) SECTION 607.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-11-25 Cont ID  
Sent By pkrauss Date 2002-11-25 Time 15:09 Rev Time 0.30
Received By pkrauss Date 2002-11-25 Time 15:07 Sent To  
Notes
2002-11-25 00:00:00DENIED:
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 IN ACCORDANCE WITH 2001 FBC(M) TABLE
 403.3.
  
 CLARIFY DAMPER IN SIDEWALL AS INDICATED
 ON PLAN (FIRE DAMPER, VOLUME DAMPER?).
 PLAN DOES NOTE INDICATE O.A. DUCT BEING
 TIED INTO THE RETURN AIR DUCT, PLEASE
 CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-29 Cont ID  
Sent By pkrauss Date 2002-10-29 Time 14:23 Rev Time 0.35
Received By pkrauss Date 2002-10-29 Time 14:23 Sent To  
Notes
2002-10-29 00:00:00DENIED:
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
  
 INDICATE LOCATION, DUCT SIZE & MATERIAL
 FOR THE OUTSIDE AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-10-29 Cont ID  
Sent By kstevens Date 2002-10-29 Time 17:14 Rev Time 0.25
Received By kstevens Date 2002-10-29 Time 17:14 Sent To  
Notes
***NONE***