| Plan Review Stops For Permit 02100398 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-13 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-12-13 |
Time |
17:25 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-12-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-10 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-12-04 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2002-12-05 00:00:00 | THE 2'-10" DOORS PROPOSED FOR THE NEW | | | OFFICE SPACES WILL NOT MEET THE MINIMUM | | | 32" WIDTH FOR HANDICAP ACCESSIBILITY AS | | | PROVIDED FOR IN FBC 11-4.13.5PLEASE | | | REVISE AS NECESSARY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-11 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-11 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-11 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2002-10-11 00:00:00 | PLEASE PROVIDE DRAFTSMAN QUALITY | | | DRAWINGS WITH PROPER DIMENSIONS, SCALE, | | | AND NOTES AS NECESSARY.SEE FBC 104.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-11-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-15 |
Time |
08:03 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-11-15 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-10-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-07 |
Time |
07:37 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-10-07 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2002-10-07 00:00:00 | ************* USNAT ****************** | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE W/ PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE NOTE PLANS SHOWN A NEW | | | A/C. PLEASE NOTE NOTHING SHOWN ON | | | ELECTRICAL PLANS. PLEASE NOTE DISC REQ`D | | | PER 440-11. PLEASE SUBMIT LOAD | | | CALCULATIONS FOR ADDING NEW A/C. | | | SHOW SIZE OF EXSITING SERVICE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-11-14 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-14 |
Time |
14:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-10-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-08 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-08 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2002-10-08 00:00:00 | 1) PLANS DO NOT SHOW THE LOCATIONS OF | | | EXISTING OR NEW EXIT SIGNS. PLEASE SHOW | | | HOW OCCUPANTS WILL EXIT THE SPACE. | | | | | | 2) IS THERE EXISTING EMERGENCY LIGHTING | | | AND WHAT ARE THE LOCATIONS? | | | | | | 3) THE PLAN DOES NOT INDICATE THE TYPE | | | OF INTERIOR FINISH BEING USED. PLEASE | | | INDICATE THE TYPE OF INTERIOR FINISH. | | | | | | 4) IS THERE A FIRE SPRINKLER AND ALARM | | | SYSTEM IN THIS BUILDING AND IF SO, HOW | | | DOES THIS WORK IMPACT THOSE SYSTEMS? | | | | | | | | | MIKE WENNERGREN, ACTING CAPTAIN | | | 659-8096, EXT. 8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-05 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-05 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2002-12-05 00:00:00 | COMM BOARD #4./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-13 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-11-13 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2002-11-13 00:00:00 | TO COMM BOARD. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-10 |
Time |
15:23 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-12-10 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2002-12-10 00:00:00 | PROVISO: | | | | | | PLEASE NOTE PLAN SHEET A-1 SECTION | | | DETAIL 1 INDICATES A FIRE RATED WALL. | | | | | | DUCTS PENETRATING WALLS OR PARTITIONS | | | HAVING A FIRE RESISTANCERATING OF 1 | | | HR OR MORE SHALL HAVE FIRE DAMPERS & | | | BE CONSTRUCTED OF METAL IN ACCORDANCE | | | WITH 2001 FBC(M) SECTION 607. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-11-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-25 |
Time |
15:09 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-11-25 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2002-11-25 00:00:00 | DENIED: | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | IN ACCORDANCE WITH 2001 FBC(M) TABLE | | | 403.3. | | | | | | CLARIFY DAMPER IN SIDEWALL AS INDICATED | | | ON PLAN (FIRE DAMPER, VOLUME DAMPER?). | | | PLAN DOES NOTE INDICATE O.A. DUCT BEING | | | TIED INTO THE RETURN AIR DUCT, PLEASE | | | CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-29 |
Time |
14:23 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-10-29 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2002-10-29 00:00:00 | DENIED: | | | | | | PROVIDE OUTSIDE AIR CALCULATIONS AS PER | | | 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89. | | | | | | INDICATE LOCATION, DUCT SIZE & MATERIAL | | | FOR THE OUTSIDE AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-10-29 |
Time |
17:14 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-10-29 |
Time |
17:14 |
Sent To |
|
|
| Notes |
|
|