Plan Review Details - Permit 02100382
Plan Review Stops For Permit 02100382
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-17 Cont ID  
Sent By btrobaug Date 2002-10-17 Time 08:00 Rev Time 0.25
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-18 Cont ID  
Sent By kstevens Date 2002-10-18 Time 16:34 Rev Time 1.00
Received By kstevens Date 2002-10-18 Time 16:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-16 Cont ID  
Sent By kstevens Date 2002-10-16 Time 14:47 Rev Time 0.25
Received By kstevens Date 2002-10-16 Time 14:47 Sent To  
Notes
2002-10-16 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE SUBMIT A PIPING DIAGRAM FOR
 ALL NEW PIPING ADDED TO SYSTEM.
 SHOW ALL EQUIPMENT, VALVES, FILTERS ECT.
 2) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 5) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 6) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 7) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377