| Plan Review Stops For Permit 02100300 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2003-07-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-07-08 |
Time |
11:09 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-07-08 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-06-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:51 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-06-05 |
Time |
15:43 |
Sent To |
B |
|
| Notes |
| 2003-06-05 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND MAKE NECESSARY CHANGES | | | TO THE PLANS FOR CODE COMPLIANCE. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 3} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 4} THE EQ GROUND FROM THE METER TO THE | | | FIRST MEANS IS CREATING A PARALLEL PATH | | | TO GROUND AND IS IN VIOLATION OF | | | 250-24. REMOVE IT . | | | | | | 5} SEE REVIEWED PLAN FOR AREAS THAT DO | | | NOT COMPLY WITH 210-52(A)(1),210-52(C)& | | | 210-52(D). | | | | | | 6} THE REVISION SHEET INDICATES THE | | | AREAS OF CHANGE WOULD BE CLOUDED,THERE | | | ARE NO CLOUDS ON SHEET A-11,PLEASE | | | CLOUD SAME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-01-15 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-03 |
Time |
14:27 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-01-15 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2003-01-15 00:00:00 | REDLINED, RISER TO HAVE NO EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | PANEL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-17 |
Time |
06:10 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-12-17 |
Time |
06:10 |
Sent To |
B |
|
| Notes |
| 2002-12-17 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, NOTES FROM FIRST | | | REVIEW WERE NOT ADDRESSED. | | | | | | PLEASE SEE FIRST REVIEW COMMENTS AND | | | SUBMIT FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-10-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-09 |
Time |
18:10 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-10-24 |
Time |
07:40 |
Sent To |
B |
|
| Notes |
| 2002-10-24 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW AIC RATINGS FOR | | | MAINS/ PANELS/BRKRS REQ`D PER 110-9/ | | | 215-5. | | | | | | 2)NOTE: PLEASE NOTE MISSING SD IN GUEST | | | BEDROOM. PLEASE SEE NFPA-72 8-1.4.1.6 | | | | | | 3)NOTE: PLEASE SEE SERVICE CONDUCTORS, | | | PLEASE NOTE AN EQUIPMENT GROUNDING | | | CONDUCTOR IS NOT INSTALLED BETWEEN | | | METER AND MAIN DISC. 250-24. PLEASE | | | ALSO SEE WIRE SIZES. SOME SHOWN MUCH | | | LARGER(MISPRINT) 6/0 AND 10/0`S ?? | | | PLEASE NOTE THAT THESE ARE NOT WIRE | | | SIZES THAT CORRELATE WITH NEC. 310-16 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2003-07-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-11 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-11 |
Time |
11:24 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-07-08 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-08 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-08 |
Time |
09:41 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-07 |
Time |
09:52 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-07 |
Time |
09:51 |
Sent To |
E |
|
| Notes |
| 2003-07-07 00:00:00 | BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-06-03 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-03 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-03 |
Time |
14:27 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-05-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-14 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-14 |
Time |
09:18 |
Sent To |
B |
|
| Notes |
| 2003-05-14 00:00:00 | RBROWN.REVISION, PRODUCT APPROVALS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-09 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-09 |
Time |
18:09 |
Sent To |
E |
|
| Notes |
| 2002-12-09 00:00:00 | TO DVP./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-07-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-14 |
Time |
13:35 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-07-14 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2003-07-14 00:00:00 | PROVISO: | | | | | | AIR HANDLING UNIT #2 - | | | AIR HANDLING UNITS INSTALLED IN ATTICS | | | SHALL COMPLY WITH THE FOLLOWING AS PER | | | 2001 FBC CHAPTER 13 SUB-CHAPTER 6 SEC | | | 610.1.ABC.3.5.2 & 2001 FBC(M) 306.3: | | | | | | 1. THE SERVICE PANEL OF THE EQUIPMENT IS | | | LOCATED WITHIN 6 FEET OF AN ATTIC ACCESS | | | | | | 2. A DEVICE IS INSTALLED TO ALERT THE | | | OWNER OR SHUT THE UNIT DOWN WHEN THE | | | CONDENSATION DRAIN IS WORKING PROPERLY. | | | | | | 3. THE ATTIC ACCESS OPENING SHALL BE | | | SUFFICIENT SIZE TO REPLACE THE AHU, NOT | | | LESS THAN 20" X 30". | | | | | | 4. A NOTICE IS POSTED ON THE ELECTRIC | | | SERVICE PANEL INDICATING TO THE HOME | | | OWNER THAT THE AHU IS LOCATED IN THE | | | ATTIC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-10-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-10-21 |
Time |
17:28 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-10-21 |
Time |
17:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-07-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-12 |
Time |
14:16 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-12 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2003-07-12 00:00:00 | REVISION OK - SANT. RISER DIAGRAM - | | | DELETED POWDER ROOM - MOVED TUB IN MAST- | | | ER BATH |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-11 |
Time |
11:24 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-07 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2003-07-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA STATUTES | | | | | | 1) ALL CHANGES TO A SIGNED AND SEALED | | | SET OF PLANS SHALL BE SIGNED, SEALED AND | | | DATED BY ARCHITECT OF RECORD. | | | 61G1-16.003 - A TITLE BLOCK SHALL ALSO | | | BE REQUIRED WITH NAME, ADDRESS, PHONE | | | NUMBER, AND FIRM LICENSE NUMBER SHOWN. | | | 2) ARCHITECTURAL FLOOR PLAN SHALL RE- | | | FLECT THE CHANGES IN THE SANITARY RISER | | | DIAGRAM. SUBMIT REVISION FOR FLOOR PLAN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-10-21 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:52 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2002-10-21 |
Time |
17:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2003-06-11 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-06-11 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-06-11 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2003-06-11 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | REVISION SUBMITTED 6/3/03 FOR RELOCATION | | | OF INTERIOR WALLS. | | | | | | --PROVISO-- | | | SEE REDLINED COMMENTS ON REVISED SHEETS | | | A-2 AND A-8 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2003-06-10 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-06-10 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-06-10 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2003-06-10 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | SUBMITTAL 6/3/03 FOR SLIDING GLASS DOOR | | | PRODUCT APPROVAL. | | | | | | --PROVISO-- | | | IT IS NOTED THAT LEGIBLE COPIES OF THE | | | DRAWINGS HAVE NOW BEEN SUBMITTED FOR THE | | | PLAZA DOOR COMPANY SLIDING GLASS DOOR | | | PRODUCT APPROVAL NOA# 03-0206.01 BUT | | | THEY STILL DO NOT CARRY THE MIAMI-DADE | | | COUNTY PRODUCT CONTROL APPROVAL STAMP | | | BEARING THE NOA NUMBER AND EXPIRATION | | | DATE.THIS COMMENT WAS RAISED WHEN THIS | | | PRODUCT APPROVAL WAS PREVIOUSLY | | | SUBMITTED.SUBMIT VALID PRODUCT | | | APPROVAL DRAWINGS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2003-05-20 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-05-20 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-05-20 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2003-05-20 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | REVISION SUBMITTED 5/12/03 FOR | | | ALTERNATIVE DOOR, WINDOW AND SLIDING | | | GLASS DOOR PRODUCT APPROVALS. | | | | | | --PROVISO-- | | | THE SUBMITTED PLAZA DOOR COMPANY SLIDING | | | GLASS DOOR PRODUCT APPROVAL | | | NOA# 03-0206.01 IS ACCOMPANIED BY | | | DRAWINGS WHICH DO NOT CARRY THE MIAMI- | | | DADE COUNTY PRODUCT CONTROL APPROVAL | | | STAMP BEARING THE NOA NUMBER AND | | | EXPIRATION DATE.ALSO THE COPIES ARE | | | POOR QUALITY.SUBMIT LEGIBLE COPIES OF | | | THE APPROPRIATE DRAWINGS BEARING THE | | | REQUIRED STAMP. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2002-12-24 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-12-24 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-12-24 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2002-12-24 00:00:00 | NEEDS NOTICE OF COMMENCEMENT AND TO PAY | | | IMPACT FEES. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-11-14 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-11-14 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2002-11-15 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) FBC* 104.2.1.2BOUNDARY SURVEY. | | | SUBMIT TWO COPIES OF A SIGNED, SEALED | | | AND DATED SURVEY DRAWING. | | | | | | 4) FBC 1606.1.1VERTICAL WALL REINF. | | | SPACING (REF: SBCCI STANDARD, SSTD-10, | | | TABLE 205C).WHAT IS THE BASIS OF THE | | | LOADS IN THE UPLIFT TABLE ON SHEET A-1? | | | SHEET A-6, DETAIL 1 - TYPICAL WALL | | | SECTION, SPECIFIES #5 VERTICAL REINF. IN | | | FILLED CELLS.SSTD 10, TABLE 205C | | | REQUIRES 1#5 AT 6FT MAX. SPACING FOR 8" | | | MASONRY WITH A CEILING HEIGHT OF 10 FT. | | | SHEET A-1, FOUNDATION PLAN, SHOWS | | | GREATER SPACING, UPTO 9'-10".ALTHOUGH | | | SOME DOUBLE FILLED CELLS ARE SHOWN, | | | AMEND THE PLANS PER TABLE 205C OR | | | JUSTIFY DEVIATION FROMTHE PRESCRIPTIVE | | | STANDARD. | | | | | | 5) THE SUBMITTED THERMA-TRU CORP. DOUBLE | | | OUTSWING OPAQUE INSULATED STEEL DOOR, | | | PRODUCT APPROVAL NOA# 02.0805.03 IS | | | ACCOMPANIED BY DRAWINGS WHICH DO NOT | | | CARRY THE MIAMI-DADE COUNTY PRODUCT | | | CONTROL RENEWAL STAMP BEARING THE ABOVE | | | NOA NUMBER AND EXPIRATIONDATE.ALSO, | | | THE COPIES ARE POOR QUALITY.SUBMIT | | | LEGIBLE COPIES OF THE APPROPRIATE | | | DRAWINGS BEARING THE REQUIRED STAMP. | | | | | | 6) FOR YOUR INFORMATION, SHEET A-4 - | | | LEFT AND RIGHT ELEVATIONS DO NOT SHOW | | | THE CORRECT PROFILE FOR THE ROOF OVER | | | THE FOYER. | | | | | | 7) FBC 1005.4 EGRESS WINDOWS.THE FACT | | | THAT THE SPECIFIED EGRESS WINDOW SIZES | | | DO CONFORM TO CODE, IS NOTED.FOR YOUR | | | INFORMATION, THE NOTE ON SHEET A-8 WOULD | | | NOT ENSURE COMPLIANCE WITH FBC 1005.4.4 | | | IT STATES THAT THE MINIMUM TOTAL GLASS | | | AREA FOR A GROUND FLOOR EGRESS WINDOW IS | | | 5.0 SQ FT AND THAT THE NET CLEAR OPENING | | | SHALL NOT BE LESS THAN 4 SQ FT.THE | | | NOTE SHOULD REQUIRE A MINIMUM OF 5 SQ FT | | | NET CLEAR OPENING FOR THE GROUND FLOOR | | | EGRESS WINDOWS (REF: RBC 1005.4.4) | | | | | | 8) IF NEW PLAN SHEETS ARE REQUIRED, IN | | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHALL BE INCLUDED WITH THE | | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-10-07 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-10-07 |
Time |
09:27 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|