Plan Review Details - Permit 02100300
Plan Review Stops For Permit 02100300
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-07-08 Cont ID  
Sent By btrobaug Date 2003-07-08 Time 11:09 Rev Time 0.50
Received By btrobaug Date 2003-07-08 Time 10:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:51 Rev Time 0.75
Received By btrobaug Date 2003-06-05 Time 15:43 Sent To B
Notes
2003-06-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND MAKE NECESSARY CHANGES
 TO THE PLANS FOR CODE COMPLIANCE.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4} THE EQ GROUND FROM THE METER TO THE
 FIRST MEANS IS CREATING A PARALLEL PATH
 TO GROUND AND IS IN VIOLATION OF
 250-24. REMOVE IT .
  
 5} SEE REVIEWED PLAN FOR AREAS THAT DO
 NOT COMPLY WITH 210-52(A)(1),210-52(C)&
 210-52(D).
  
 6} THE REVISION SHEET INDICATES THE
 AREAS OF CHANGE WOULD BE CLOUDED,THERE
 ARE NO CLOUDS ON SHEET A-11,PLEASE
 CLOUD SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-15 Cont ID  
Sent By shernand Date 2003-06-03 Time 14:27 Rev Time 1.00
Received By dpalmer Date 2003-01-15 Time 15:27 Sent To  
Notes
2003-01-15 00:00:00REDLINED, RISER TO HAVE NO EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-12-18 Cont ID  
Sent By dpalmer Date 2002-12-17 Time 06:10 Rev Time 0.25
Received By dpalmer Date 2002-12-17 Time 06:10 Sent To B
Notes
2002-12-17 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE NOTE, NOTES FROM FIRST
 REVIEW WERE NOT ADDRESSED.
  
 PLEASE SEE FIRST REVIEW COMMENTS AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-24 Cont ID  
Sent By btrobaug Date 2002-12-09 Time 18:10 Rev Time 0.50
Received By dpalmer Date 2002-10-24 Time 07:40 Sent To B
Notes
2002-10-24 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW AIC RATINGS FOR
 MAINS/ PANELS/BRKRS REQ`D PER 110-9/
 215-5.
  
 2)NOTE: PLEASE NOTE MISSING SD IN GUEST
 BEDROOM. PLEASE SEE NFPA-72 8-1.4.1.6
  
 3)NOTE: PLEASE SEE SERVICE CONDUCTORS,
 PLEASE NOTE AN EQUIPMENT GROUNDING
 CONDUCTOR IS NOT INSTALLED BETWEEN
 METER AND MAIN DISC. 250-24. PLEASE
 ALSO SEE WIRE SIZES. SOME SHOWN MUCH
 LARGER(MISPRINT) 6/0 AND 10/0`S ??
 PLEASE NOTE THAT THESE ARE NOT WIRE
 SIZES THAT CORRELATE WITH NEC. 310-16
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:24 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 11:24 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 09:41 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 09:41 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:52 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 09:52 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:51 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 09:51 Sent To E
Notes
2003-07-07 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 14:27 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 14:27 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 09:18 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 09:18 Sent To B
Notes
2003-05-14 00:00:00RBROWN.REVISION, PRODUCT APPROVALS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-09 Cont ID  
Sent By btrobaug Date 2002-12-09 Time 18:09 Rev Time 0.00
Received By btrobaug Date 2002-12-09 Time 18:09 Sent To E
Notes
2002-12-09 00:00:00TO DVP./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-14 Cont ID  
Sent By pkrauss Date 2003-07-14 Time 13:35 Rev Time 0.35
Received By pkrauss Date 2003-07-14 Time 13:35 Sent To  
Notes
2003-07-14 00:00:00PROVISO:
  
 AIR HANDLING UNIT #2 -
 AIR HANDLING UNITS INSTALLED IN ATTICS
 SHALL COMPLY WITH THE FOLLOWING AS PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 6 SEC
 610.1.ABC.3.5.2 & 2001 FBC(M) 306.3:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FEET OF AN ATTIC ACCESS
  
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT THE UNIT DOWN WHEN THE
 CONDENSATION DRAIN IS WORKING PROPERLY.
  
 3. THE ATTIC ACCESS OPENING SHALL BE
 SUFFICIENT SIZE TO REPLACE THE AHU, NOT
 LESS THAN 20" X 30".
  
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE HOME
 OWNER THAT THE AHU IS LOCATED IN THE
 ATTIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By jleech Date 2002-10-21 Time 17:28 Rev Time 0.33
Received By jleech Date 2002-10-21 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-12 Cont ID  
Sent By kstevens Date 2003-07-12 Time 14:16 Rev Time 0.50
Received By kstevens Date 2003-07-12 Time 14:16 Sent To  
Notes
2003-07-12 00:00:00REVISION OK - SANT. RISER DIAGRAM -
 DELETED POWDER ROOM - MOVED TUB IN MAST-
 ER BATH

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:24 Rev Time 0.50
Received By kstevens Date 2003-07-07 Time 13:42 Sent To  
Notes
2003-07-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) ALL CHANGES TO A SIGNED AND SEALED
 SET OF PLANS SHALL BE SIGNED, SEALED AND
 DATED BY ARCHITECT OF RECORD.
 61G1-16.003 - A TITLE BLOCK SHALL ALSO
 BE REQUIRED WITH NAME, ADDRESS, PHONE
 NUMBER, AND FIRM LICENSE NUMBER SHOWN.
 2) ARCHITECTURAL FLOOR PLAN SHALL RE-
 FLECT THE CHANGES IN THE SANITARY RISER
 DIAGRAM. SUBMIT REVISION FOR FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:52 Rev Time 0.25
Received By jleech Date 2002-10-21 Time 17:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2003-06-11 Cont ID  
Sent By rbrown Date 2003-06-11 Time 11:57 Rev Time 0.00
Received By rbrown Date 2003-06-11 Time 11:57 Sent To  
Notes
2003-06-11 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 6/3/03 FOR RELOCATION
 OF INTERIOR WALLS.
  
 --PROVISO--
 SEE REDLINED COMMENTS ON REVISED SHEETS
 A-2 AND A-8

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2003-06-10 Cont ID  
Sent By rbrown Date 2003-06-10 Time 16:56 Rev Time 0.00
Received By rbrown Date 2003-06-10 Time 16:56 Sent To  
Notes
2003-06-10 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL 6/3/03 FOR SLIDING GLASS DOOR
 PRODUCT APPROVAL.
  
 --PROVISO--
 IT IS NOTED THAT LEGIBLE COPIES OF THE
 DRAWINGS HAVE NOW BEEN SUBMITTED FOR THE
 PLAZA DOOR COMPANY SLIDING GLASS DOOR
 PRODUCT APPROVAL NOA# 03-0206.01 BUT
 THEY STILL DO NOT CARRY THE MIAMI-DADE
 COUNTY PRODUCT CONTROL APPROVAL STAMP
 BEARING THE NOA NUMBER AND EXPIRATION
 DATE.THIS COMMENT WAS RAISED WHEN THIS
 PRODUCT APPROVAL WAS PREVIOUSLY
 SUBMITTED.SUBMIT VALID PRODUCT
 APPROVAL DRAWINGS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2003-05-20 Cont ID  
Sent By rbrown Date 2003-05-20 Time 09:48 Rev Time 0.00
Received By rbrown Date 2003-05-20 Time 09:47 Sent To  
Notes
2003-05-20 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 5/12/03 FOR
 ALTERNATIVE DOOR, WINDOW AND SLIDING
 GLASS DOOR PRODUCT APPROVALS.
  
 --PROVISO--
 THE SUBMITTED PLAZA DOOR COMPANY SLIDING
 GLASS DOOR PRODUCT APPROVAL
 NOA# 03-0206.01 IS ACCOMPANIED BY
 DRAWINGS WHICH DO NOT CARRY THE MIAMI-
 DADE COUNTY PRODUCT CONTROL APPROVAL
 STAMP BEARING THE NOA NUMBER AND
 EXPIRATION DATE.ALSO THE COPIES ARE
 POOR QUALITY.SUBMIT LEGIBLE COPIES OF
 THE APPROPRIATE DRAWINGS BEARING THE
 REQUIRED STAMP.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-12-24 Cont ID  
Sent By rbrown Date 2002-12-24 Time 15:17 Rev Time 0.00
Received By rbrown Date 2002-12-24 Time 15:17 Sent To  
Notes
2002-12-24 00:00:00NEEDS NOTICE OF COMMENCEMENT AND TO PAY
 IMPACT FEES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By rbrown Date 2002-11-14 Time 16:59 Rev Time 0.00
Received By rbrown Date 2002-11-14 Time 16:59 Sent To  
Notes
2002-11-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 104.2.1.2BOUNDARY SURVEY.
 SUBMIT TWO COPIES OF A SIGNED, SEALED
 AND DATED SURVEY DRAWING.
  
 4) FBC 1606.1.1VERTICAL WALL REINF.
 SPACING (REF: SBCCI STANDARD, SSTD-10,
 TABLE 205C).WHAT IS THE BASIS OF THE
 LOADS IN THE UPLIFT TABLE ON SHEET A-1?
 SHEET A-6, DETAIL 1 - TYPICAL WALL
 SECTION, SPECIFIES #5 VERTICAL REINF. IN
 FILLED CELLS.SSTD 10, TABLE 205C
 REQUIRES 1#5 AT 6FT MAX. SPACING FOR 8"
 MASONRY WITH A CEILING HEIGHT OF 10 FT.
 SHEET A-1, FOUNDATION PLAN, SHOWS
 GREATER SPACING, UPTO 9'-10".ALTHOUGH
 SOME DOUBLE FILLED CELLS ARE SHOWN,
 AMEND THE PLANS PER TABLE 205C OR
 JUSTIFY DEVIATION FROMTHE PRESCRIPTIVE
 STANDARD.
  
 5) THE SUBMITTED THERMA-TRU CORP. DOUBLE
 OUTSWING OPAQUE INSULATED STEEL DOOR,
 PRODUCT APPROVAL NOA# 02.0805.03 IS
 ACCOMPANIED BY DRAWINGS WHICH DO NOT
 CARRY THE MIAMI-DADE COUNTY PRODUCT
 CONTROL RENEWAL STAMP BEARING THE ABOVE
 NOA NUMBER AND EXPIRATIONDATE.ALSO,
 THE COPIES ARE POOR QUALITY.SUBMIT
 LEGIBLE COPIES OF THE APPROPRIATE
 DRAWINGS BEARING THE REQUIRED STAMP.
  
 6) FOR YOUR INFORMATION, SHEET A-4 -
 LEFT AND RIGHT ELEVATIONS DO NOT SHOW
 THE CORRECT PROFILE FOR THE ROOF OVER
 THE FOYER.
  
 7) FBC 1005.4 EGRESS WINDOWS.THE FACT
 THAT THE SPECIFIED EGRESS WINDOW SIZES
 DO CONFORM TO CODE, IS NOTED.FOR YOUR
 INFORMATION, THE NOTE ON SHEET A-8 WOULD
 NOT ENSURE COMPLIANCE WITH FBC 1005.4.4
 IT STATES THAT THE MINIMUM TOTAL GLASS
 AREA FOR A GROUND FLOOR EGRESS WINDOW IS
 5.0 SQ FT AND THAT THE NET CLEAR OPENING
 SHALL NOT BE LESS THAN 4 SQ FT.THE
 NOTE SHOULD REQUIRE A MINIMUM OF 5 SQ FT
 NET CLEAR OPENING FOR THE GROUND FLOOR
 EGRESS WINDOWS (REF: RBC 1005.4.4)
  
 8) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By sgraham Date 2002-10-07 Time 09:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***