Plan Review Details - Permit 02100085
Plan Review Stops For Permit 02100085
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-01-08 Cont ID  
Sent By hpiskura Date 2003-01-08 Time 13:49 Rev Time 0.00
Received By hpiskura Date 2003-01-08 Time 08:30 Sent To  
Notes
2003-01-08 00:00:00RE: SHEET A9 PLANS DATED 12/9/02
 SECTION 5/A9 AND NOTE B REFERENCE DESIGN
 FOR FASTENING TO "MANUFACTURER'S
 RECOMMENDATIONS"WHEN DESIGN HAVING
 STRUCTURAL INPUT IS DELEGATED THE
 LOCATION, NATURE, DIRECTION AND
 MAGNITUDE OF THE FORCES TO BE RESISTED
 SHOULD BE PROVIDED BY THE DESIGNER OF
 RECORD.
  
 A TECHNICAL SPECIFICATION MANUAL CITED
 IN ITEM 4 OF VICTOR HERNANDEZ'S LETTER
 DATED 12/9/02 IS NOT FOUND IN THIS
 PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 14:53 Rev Time 0.00
Received By hpiskura Date 2002-10-04 Time 14:48 Sent To  
Notes
2002-10-07 00:00:00THIS PERMIT IS SUBJECT TO THE FOLLOWING
 PROVISIONS:
  
 1SHEET T-2 DECLARES THE NYC BUILDING
 CODE.PROVIDE A SIGNED AND SEALED
 STATEMENT THAT THE DESIGN IS IN
 ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, 2001 EDITION.
  
  
 2SHEET T-2 DECLARES DESIGN TO ACI
 318-89.PLEASE REVISE AND INSURE
 COMPLIANCE WITH ACI-99.
  
 3SHEET A-3, NOTE #3,SPECIFY THE AMOUNT
 OF TENSION THAT WILL BE APPLIED TO THE
 CABLES.
  
 4PROVIDE A SIGNED AND SEALED COPY OF
 THE "TECHNICAL SPECIFICATION MANUAL"
 CALLED OUT ON SHEET T-1 AS BEING "PART
 OF THIS PROJECT"
  
 5SPECIFY WHICH EIFS SYSTEM IS TO BE
 USED AND THE REFERENCE NUMBER FOR
 PRODUCT ACCEPTANCE FROM A RECOGNIZED
 TESTING LABORATORY OR CODE AGENCY.
  
 6WHAT IS MEANT BY THE TERM
 "DEDEFINED"AS IN LOOSE CABLES SHALL BE
 DEDEFINED?
  
 7 SECTIONS 5/A9 & 9/A9.PROVIDE
 SPECIFIC FASTENER AND CONNECTION
 METHODS FOR THE BENT PLATE CONNECTION
 TO THE MASONRY AND TO THE METAL STUDS.
  
 8IF THE BENT PLATES ARE TO FASTEN
 EVERY OTHER STUD TO THE BUILDING, HOW
 ARE THE INTERMEDIATE STUDS SUPPORTED?
  
 9SPECIFY THE 1/2 INCH EXTERIOR SHEATH
 ING TO BE USED AND THE FASTENING METHOD.
  
 10THE PLANS REFENCE "GROUT" IN SEVERAL
 PLACES.SPECIFY THE INTENDED DESIGN
 STRENGTH.
  
 11SECTION 1/A-10, SPECIFY THE WELDS
 AND GROUT STRENGTH TO BE USED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-02 Cont ID  
Sent By btrobaug Date 2002-10-02 Time 13:02 Rev Time 0.25
Received By btrobaug Date 2002-10-02 Time 07:18 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-10-03 Cont ID  
Sent By btrobaug Date 2002-10-02 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2002-10-03 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-19 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 14:53 Rev Time 0.00
Received By btrobaug Date 2002-12-19 Time 14:52 Sent To B
Notes
2002-12-19 00:00:00TO HAROLD P./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-10-02 Cont ID  
Sent By mamini Date 2002-10-02 Time 13:41 Rev Time 0.00
Received By mamini Date 2002-10-02 Time 13:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-10-02 Cont ID  
Sent By mamini Date 2002-10-02 Time 13:41 Rev Time 0.00
Received By mamini Date 2002-10-02 Time 13:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2002-10-08 Cont ID  
Sent By sgraham Date 2002-10-08 Time 11:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2002-10-07 Cont ID  
Sent By mamini Date 2002-10-07 Time 09:33 Rev Time 0.00
Received By mamini Date 2002-10-07 Time 09:33 Sent To  
Notes
***NONE***