Plan Review Details - Permit 02100056
Plan Review Stops For Permit 02100056
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-18 Cont ID  
Sent By btrobaug Date 2002-11-18 Time 11:19 Rev Time 1.00
Received By btrobaug Date   Time   Sent To R
Notes
2002-11-18 00:00:00TO HAROLD P./WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-18 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 16:37 Rev Time 1.00
Received By btrobaug Date 2002-10-23 Time 06:26 Sent To R
Notes
2002-10-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE LAUNDRY CIRCUIT @
 1500 VA PER 220-16.REVISE CALCS.
  
 3} PLEASE INCLUDE ALL A/C UNITS IN LOAD
 CALCS.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE CHECK ELECTRICAL NOTE #18
 REGARDING 210-12,FOR ACCURACY.
  
 6} PLEASE NOTE THAT A SMOKE DETECTOR IS
 REQUIRED OUTSIDE THE MASTER SUITE PER
 8-1.4.1.6.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 16:37 Sent To E
Notes
2002-11-15 00:00:00TO WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-10-21 Cont ID  
Sent By jleech Date 2002-10-21 Time 17:54 Rev Time 0.00
Received By jleech Date 2002-10-21 Time 17:54 Sent To  
Notes
2002-10-21 00:00:00NO A/C PLAN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-19 Cont ID  
Sent By jleech Date 2003-06-19 Time 16:55 Rev Time 0.50
Received By jleech Date 2003-06-19 Time 16:55 Sent To  
Notes
2003-06-19 00:00:00REVISED RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By jleech Date 2002-10-21 Time 17:55 Rev Time 0.33
Received By jleech Date 2002-10-21 Time 17:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-11-19 Cont ID  
Sent By hpiskura Date 2002-11-19 Time 10:52 Rev Time 0.00
Received By hpiskura Date 2002-11-18 Time 16:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2002-11-18 Time 11:27 Rev Time 0.00
Received By hpiskura Date 2002-11-06 Time 13:05 Sent To  
Notes
2002-11-07 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUN TY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 THE ENERGY CODE FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER OR HIS AGENT. SEE
 FBC 13-600.3ABC2
  
 MIAMI-DADE NOA #01-1031.06 HAS ILLEGIBLE
 DRAWINGS AND THE COMPONENTS ARE NOT
 SELECTED.
  
 THE NORANDEX PRODUCT CERTIFICATION HAS
 ILLEGIBLE PAGES AND THE COMPONENTS,
 (INCLUDING ANCHOR METHODS), ARE NOT
 SELECTED
  
 NOA #00-1106.03 DOES NOT HAVE THE
 COMPONENTS AND INSTALLATION METHOD
 SELECTED.
  
 THE WAYNE DALTON DOORS ARE NOT A
 RECOGNIZED TESTING AGENCY.
  
 THE SBCCI REPORT #2036 FOR THE SHUTTERS
 DOES NOT HAVE THE COMPONENTS AND
 FASTENERS SELECTED.NOTE, READ THE
 LIMITATIONS AND COMPARE THE MATERIALS
 TO THOSE SPECIFIED ON THE PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By sgraham Date 2002-10-07 Time 09:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***