Plan Review Details - Permit 02100045
Plan Review Stops For Permit 02100045
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-09 Cont ID  
Sent By dpalmer Date 2003-07-09 Time 16:33 Rev Time 2.00
Received By dpalmer Date 2003-07-09 Time 16:33 Sent To  
Notes
2003-07-09 00:00:00REDLINED ARCH #`S

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-07-07 Time 12:02 Rev Time 0.50
Received By dpalmer Date 2003-06-25 Time 13:18 Sent To  
Notes
2003-06-25 00:00:00*************** UNSAT **************
  
 1)NOTE: RISER NOW SHOWS A MAIN BEING
 INSTALLED OUTSIDE, PLEASE VERIFY OF THE
 200A AND 60A PANELS ARE STILL MCB`S
 (MAIN CIRCUIT BRKR)
 MCB`S ARE NOT REQ`D, HOWEVER IF SHOWN
 ON PLANS, THEN THEY WILL BE REQ`D TO BE
 INSTALLED.
  
 2)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN
 FOR SUB PANEL. PLEASE HAVE ALL CHANGES
 DONE BY THE ARCH OF RECORD.
 FS 481
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN DISC/
 PANEL TO SUB PANEL AND FROM MAIN DISC
 OUTSIDE MAIN,.250-110/250-24
  
 4)NOTE: PLEASE SEE 200 MAIN PANEL,
 SHOWS FEEEDING SUB PANEL W/ 8 CIRCUITS?
 MEANT TO SHOW 2?
  
 5)NOTE: PLEASE SEE 3.2 KW SHOWN FOR EACH
 15A CIRCUIT. PLEASE SEE THAT THESE ARE
 OVERLOADED.
  
 6)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPT PER 210-52C-1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-22 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:04 Rev Time 0.50
Received By dpalmer Date 2002-10-22 Time 16:53 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 12:01 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 12:01 Sent To E
Notes
2003-07-07 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:04 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 11:04 Sent To E
Notes
2003-06-20 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-08 Cont ID  
Sent By dpalmer Date 2003-01-08 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2003-01-08 Time 10:13 Sent To B
Notes
2003-01-08 00:00:00TO LOU HATTEN'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-06 Cont ID  
Sent By btrobaug Date 2003-01-03 Time 16:34 Rev Time 0.00
Received By btrobaug Date 2003-01-03 Time 16:34 Sent To B
Notes
2003-01-06 00:00:00TO LOU H./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By jleech Date 2002-10-19 Time 10:15 Rev Time 0.33
Received By jleech Date 2002-10-19 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By jleech Date 2002-10-19 Time 10:15 Rev Time 0.25
Received By jleech Date 2002-10-19 Time 10:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By lhatten Date 2002-11-04 Time 18:43 Rev Time 2.50
Received By lhatten Date 2002-11-02 Time 18:42 Sent To  
Notes
2002-11-04 00:00:00REVIEW & STAMPED PLANS 11/02/2002
 CALC. FEES & PRINT CARD 11/04/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By sgraham Date 2002-10-07 Time 09:29 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***