Plan Review Details - Permit 02100043
Plan Review Stops For Permit 02100043
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-22 Cont ID  
Sent By dpalmer Date 2002-10-22 Time 10:36 Rev Time 0.50
Received By dpalmer Date 2002-10-22 Time 10:36 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-13 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 16:58 Rev Time 0.00
Received By btrobaug Date 2002-12-13 Time 16:58 Sent To R
Notes
2002-12-13 00:00:00TO ROB M./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By jleech Date 2002-10-19 Time 12:30 Rev Time 0.33
Received By jleech Date 2002-10-19 Time 12:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-29 Cont ID  
Sent By kstevens Date 2003-01-29 Time 15:38 Rev Time 0.33
Received By kstevens Date 2003-01-29 Time 15:38 Sent To  
Notes
2003-01-29 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-17 Cont ID  
Sent By kstevens Date 2002-12-17 Time 12:12 Rev Time 0.25
Received By kstevens Date 2002-12-17 Time 12:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By jleech Date 2002-10-19 Time 12:30 Rev Time 0.25
Received By jleech Date 2002-10-19 Time 12:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-12-17 Cont ID  
Sent By rmcdouga Date 2002-12-17 Time 09:24 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-17 00:00:00BUILDING PROVISO
  
 1) PROVIDE A SOIL TEST REPORT INDICATING
 THE SAFE BEARING CAPACITY OF THE SOIL
 THAT IS SIGNED AND SEALED BY A FL SOIL
 ENGINEER PRIOR TO POURING FOUNDATION PER
 L.HATTEN. SEE CITY OF WPB AMENDMENTS TO
 FBC SECTION 1804.2.2.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE FRENCH DOOR WITH DESIGN
 PRESSURES OF +46 & -60.4 PSF.
 - DOUBLE OUTSWING FRENCH DOORS (THE
 DRAWINGS THAT ACCOMPANY THE COVER SHEET
 DO NOT HAVE THE NEW NOA NUMBER ON THEM.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 16:58 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-31 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A COMPLETE SOIL TEST REPORT
 INDICATING SOIL PREP. RECOMMENDATIONS &
 SOIL BEARING CAPACITY. REPORT IS TO HAVE
 WET SIGNATURE, DATE AND EMBOSSED SEAL OF
 A FL SOIL ENGINEER.
  
 4)PLEASE REVISE CONSTRUCTION TYPE LISTED
 ON A4 TO TYPE VI.
  
 5) SPECIFY THAT THE WWM FOR THE SLAB
 SHALL BE SUPPORTED BY APPROVED MATERIALS
 OR SUPPORTS AT SPACING NOT TO EXCEED 3
 FEET. SEE 2001 FBC SEC. 1909.3.
  
 6)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7) SPECIFY ONE HOUR FIRE RATED GLASS
 BLOCK AT ZERO LOT LINE. REVISE GLASS
 BLOCK DETAIL TO SHOW FIRE RATED GLASS
 BLOCK ASSEMBLY.
  
 8) PROVIDE A LINTEL SCHEDULE FOR THE
 4X8 LINTEL ABOVE ENTRY DOOR AND 8X8
 LINTELS ABOVE WINDOWS & GARAGE DOOR.
  
 9) THE GLASS BLOCKS IN THE MASTER BATH
 ARE IN HAZARDOUS LOCATIONS AND MUST HAVE
 A MINIMUM UNIFORM FACE THICKNESS OF
 0.25 INCH PER FBC 2405.2.2. SPECIFY THIS
 ON PLANS.
  
 10) PROVIDE COMPLETE INFORMATION FOR THE
 2" STEEL HEADER DETAIL. INDICATE THE
 WELD TYPE, THICKNESS OF STEEL, ETC.
  
 11) PROVIDE CALCULATIONS WHICH INDICATE
 THAT THE REQUIRED NET FREE VENTILATING
 AREA WILL BE PROVIDED BY THE AREAS THAT
 DO NOT HAVE THE STYROFOAM TRIM.
  
 12) SPECIFY THE SIZE OF THE WASHERS USED
 ON THE TAPCON FASTENERS FOR THE GARAGE
 DOOR BUCKS ON THE DETAIL ON A8.
  
 13) REVISE THE SWING DOOR BUCK DETAIL ON
 A8 TO COMPLY WITH FBC 1707.4.4.2 WHICH
 REQUIRES THE 2X BUCK TO EXTEND BEYOND
 THE INTERIOR FACE OF THE DOOR FRAME.
  
 14) PROVIDE A STRUCTURAL DETAIL OF THE
 BOLLARD/3" STEEL POST IN THE GARAGE.
  
 15) SPECIFY ON THE PLANS THAT THE DOOR
 BETWEEN THE GARAGE AND CONDITIONED SPACE
 IS SOLID CORE AS REQUIRED BY CHAPTER 13
 OF FBC.
  
 16) PROVIDE (2) COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE INDICATING THE
 SPECIFIC TYPE OF FASTENERS THAT ARE TO
 BE USED FOR THE STORM PANELS. INDICATE
 THE MOUNTING OPTIONS THAT WILL BE USED.
 THIS INFORMATION IS REQUIRED PRIOR TO
 PERMIT OR A SEPARATE PERMIT WITH
 ADDITIONAL FEES WILL BE REQUIRED.
  
 17) THE PRODUCT APPROVAL FOR THE SLIDING
 GLASS DOORS IS MISSING PAGE 2 AND THE
 DRAWINGS HAVE THE WRONG ACCEPTANCE
 NUMBER.
  
 18) PROVIDE SPECIFICATIONS FOR A ONE
 HOUR FIRE RATED GLASS BLOCK ASSEMBLY
 AND THE UL LISTING INFORMATION.
  
 19) PRODUCT APPROVALS WERE SUBMITTED FOR
 GLASS BLOCK FROM TWO DIFFERENT MANUFACT-
 URERS. SUBMIT THE ONE THAT CORRESPONDS
 TO THE DETAILS ON THE PLANS, ALONG WITH
 FIRE RATING LISTING INFORMATION.
  
 20) IN ORDER TO MEET THE WINDLOAD
 PRESSURES LISTED ON THE PLANS, THE FIXED
 GLASS ARCHED AND TRANSOM WINDOWS WILL
 HAVE TO BE 3/16" TEMPERED GLASS ACCORD-
 ING TO THE PRODUCT APPROVALS THAT WERE
 SUBMITTED. SPECIFY TEMPERED GLASS ON THE
 PLANS FOR THESE WINDOWS.
  
 21) THE DESIGN PRESSURES LISTED ON THE
 PLANS FOR SOME OF THE SINGLE HUNG
 WINDOWS EXCEED THE DESIGN PRESSURES IN
 THE PRODUCT APPROVALS. SOME WILL REQUIRE
 TEMPERED GLASS TO COMPLY.
  
 22) THE SITE SPECIFIC PRODUCT APPROVALS
 FOR THE SIDE SWINGING DOORS ARE REQUIRED
 TO BE SIGNED, SEALED AND DATED BY THE
 DESIGNER OF RECORD OF THE STRUCTURE. THE
 LOCATION OF THE STRUCTURE IS REQUIRED TO
 BE ON THE FORM. PROVIDE THE TEST REPORTS
 FOR LARGE MISSLE IMPACT AS REQUIRED BY
 GENERAL NOTE 7.5 ON THE FORM.
  
 23) PROVIDE PRODUCT APPROVALS FOR
 STRUCTURAL MULLIONS AT WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-15 Cont ID  
Sent By sgraham Date 2002-10-15 Time 12:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***