Plan Review Details - Permit 02100039
Plan Review Stops For Permit 02100039
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-03-03 Cont ID  
Sent By btrobaug Date 2003-03-03 Time 09:28 Rev Time 0.50
Received By btrobaug Date 2003-03-03 Time 09:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-02-26 Cont ID  
Sent By btrobaug Date 2003-02-26 Time 11:39 Rev Time 0.33
Received By btrobaug Date 2003-02-26 Time 11:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-11 Cont ID  
Sent By btrobaug Date 2003-02-11 Time 17:37 Rev Time 0.50
Received By btrobaug Date 2003-02-11 Time 17:37 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 12:58 Rev Time 0.50
Received By dpalmer Date 2002-12-19 Time 12:58 Sent To P
Notes
2002-12-19 00:00:00******* NOTES REDLINED ***************

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-22 Cont ID  
Sent By dpalmer Date 2002-10-22 Time 12:59 Rev Time 0.50
Received By dpalmer Date 2002-10-22 Time 12:59 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 16:43 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 16:42 Sent To B
Notes
2003-05-15 00:00:00RM DESK, NEED RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 14:01 Sent To B
Notes
2003-02-27 00:00:00TO ROBERT MCD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-13 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 17:09 Rev Time 0.00
Received By btrobaug Date 2002-12-13 Time 17:09 Sent To R
Notes
2002-12-13 00:00:00ROB M./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-28 Cont ID  
Sent By pkrauss Date 2003-02-28 Time 15:32 Rev Time 0.35
Received By pkrauss Date 2003-02-28 Time 15:03 Sent To  
Notes
2003-02-28 00:00:00MECHANICAL REVISION PERMIT 02100060

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By btrobaug Date 2003-02-11 Time 17:37 Rev Time 0.33
Received By jleech Date 2002-10-19 Time 09:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-20 Cont ID  
Sent By kstevens Date 2002-12-20 Time 16:58 Rev Time 0.25
Received By kstevens Date 2002-12-20 Time 16:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 12:58 Rev Time 0.25
Received By jleech Date 2002-10-19 Time 09:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-12-23 Cont ID  
Sent By rmcdouga Date 2002-12-23 Time 16:09 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-23 00:00:00BUILDING PROVISO
  
 1) PROVIDE A SOIL TEST REPORT INDICATING
 THE SAFE BEARING CAPACITY OF THE SOIL
 THAT IS SIGNED AND SEALED BY A FL SOIL
 ENGINEER PRIOR TO POURING FOUNDATION PER
 L.HATTEN SEE CITY OF WPB AMENDMENTS TO
 FBC SECTION 1804.2.2.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE FRENCH DOOR WITH DESIGN
 PRESSURES OF +46 AND -60.4 PSF.
 - DOUBLE OUTSWING DOORS AT FRONT ENTRY

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 17:11 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-31 00:00:00 
 BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A COMPLETE SOIL TEST REPORT
 INDICATING SOIL PREPARATION AND SOIL
 BEARING CAPACITY. REPORT SHALL HAVE THE
 WET SIGNATURE, DATE AND EMBOSSED SEAL
 OF A FL SOIL ENGINEER.
  
 4) PLEASE REVISE THE CONSTRUCTION TYPE
 LISTED ON A4 TO TYPE VI.
  
 5) SPECIFY THAT THE WWM FOR THE SLAB
 SHALL BE SUPPORTED BY APPROVED APPROVED
 MATERIALS OR SUPPORTS AT SPACINGS NOT TO
 EXCEED 3 FEET. SEE 2001 FBC SEC. 1909.3.
  
 6)THE EXPOSURE CATEGORY FOR THE
 STRUCTURE GIVEN ON A1 IS B NOT C.
 PLEASE REVISE.
  
 7) SPECIFY ONE HOUR FIRE RATED GLASS
 BLOCK AT ZERO LOT LINE. REVISE THE GLASS
 BLOCK DETAIL ON A8 TO SHOW A ONE HOUR
 RATED GLASS BLOCK ASSEMBLY.
  
 8) PROVIDE A LINTEL SCHEDULE.
  
 9) THE GLASS BLOCK IN THE MASTER BATH
 ARE IN HAZARDOUS LOCATIONS AND MUST HAVE
 A MINIMUM UNIFORM FACE THICKNESS OF 0.25
 INCH PER FBC 2405.2.2. SPECIFY THIS ON
 THIS ON THE PLANS.
  
 10) PROVIDE COMPLETE INFORMATION FOR THE
 2" STEEL HEADER DETAIL. INDICATE THE
 WELD TYPE, THICKNESS OF STEEL, ETC.
  
 11) PLEASE CORRECT THE CONSTRUCTION TYPE
 LISTED ON A4 TO TYPE VI.
  
 12) PROVIDE CALCULATIONS WHICH INDICATE
 THAT THE REQUIRED NET FREE VENTILATING
 AREA WILL BE PROVIDED BY THE AREAS THAT
 DO NOT HAVE THE STYROFOAM TRIM.
  
 13) SPECIFY THE SIZE OF THE WASHERS USED
 ON THE TAPCONS FASTENING THE GARAGE DOOR
 BUCKS IN THE DETAIL ON A8.
  
 14) REVISE THE SWING DOOR BUCK DETAIL ON
 A8 TO COMPLY WITH FBC 1707.4.4.2.
  
 15) PROVIDE A STRUCTURAL DETAIL OF THE
 BOLLARD/3" STEEL POST IN THE GARAGE.
  
 16) SPECIFY ON THE PLANS THAT THE DOOR
 BETWEEN THE GARAGE AND CONDITIONED SPACE
 IS SOLID CORE OR INSULATED AS REQUIRED
 BY CHAPTER 13 OF THE FBC.
  
 17) PROVIDE (2) COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE INDICATING THE
 SPECIFIC TYPE OF FASTENERS THAT ARE TO
 BE USED FOR THE STORM PANELS. INDICATE
 THE MOUNTING OPTIONS THAT WILL BE USED.
 THIS INFORMATION IS REQUIRED PRIOR TO
 PERMIT OR A SEPARATE PERMIT WILL BE
 REQUIRED WITH ADDITIONAL FEES.
  
 18) THE PRODUCT APPROVALS FOR THE
 SLIDING GLASS DOORS IS MISSING PAGE 2
 AND THE DRAWINGS HAVE THE WRONG
 ACCEPTANCE NUMBER.
  
 19) PROVIDE MANUFACTURES SPECS. AND UL
 LISTING INFORMATION FOR ONE HOUR RATED
 GLASS BLOCK ASSEMBLIES.
  
 20) PRODUCT APPROVALS WERE SUBMITTED FOR
 GLASS BLOCK FROM TWO DIFFERENT MANUFACT-
 URERS. SUBMIT THE ONE THAT IS TO BE
 INSTALLED ALONG WITH THE INFORMATION
 REQUESTED ABOVE AN THAT CORRESPONDS TO
 THE DETAIL ON THE PLANS.
  
 21) IN ORDER TO MEET THE WINDLOAD
 PRESSURES LISTED ON THE PLANS, THE FIXED
 GLASS WINDOWS WILL HAVE TO BE TEMPERED
 GLASS ACCORDING TO THE PRODUCT APPROVALS
 THAT WERE SUBMITTED. SPECIFY ON THE
 PLANS THAT THESE WINDOWS WILL HAVE
 TEMPERED GLASS.
  
 22) THE SITE SPECIFIC PRODUCT APPROVALS
 FOR THE SIDE SWINGING DOORS ARE REQUIRED
 TO BE SIGNED, SEALED AND DATED BY THE
 DESIGNER OF RECORD OF THE STRUCTURE. THE
 LOCATION OF THE STRUCTURE IS REQUIRED TO
 BE ON THE FORM. PROVIDE THE TEST REPORTS
 FOR MISSLE IMPACT AS REQUIRED BY GENERAL
 NOTE 7.5 ON THE FORM.
  
 23) THE DESIGN PRESSURES LISTED ON THE
 PLANS FOR SOME OF THE SINGLE HUNG
 WINDOWS EXCEED THE DESIGN PRESSURES IN
 THE PRODUCT APPROVALS. SOME WILL REQUIRE
 TEMPERED GLASS TO COMPLY.
  
 24) PROVIDE PRODUCT APPROVALS FOR
 STRUCTURAL MULLIONS AT WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-31 Cont ID  
Sent By rmcdouga Date 2002-10-31 Time 13:07 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-31 00:00:00OK PER S.GRAHAM 10-7-02