Plan Review Details - Permit 02091769
Plan Review Stops For Permit 02091769
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-08-24 Cont ID  
Sent By rbrown Date 2004-08-24 Time 12:11 Rev Time 0.00
Received By rbrown Date 2004-08-24 Time 12:10 Sent To  
Notes
2004-08-24 00:00:00REVISION SUBMITTED 8/24/04 FOR COLUMN
 DETAIL SKETCH SK8

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-07-15 Cont ID  
Sent By rbrown Date 2004-07-15 Time 08:26 Rev Time 0.00
Received By rbrown Date 2004-07-15 Time 08:25 Sent To  
Notes
2004-07-15 00:00:00REVISION FOR SHEETS ASP-1, A-203, A-204
 & A-302.
  
 PROVISO:
 SITE-WALL CROSS-SECTION DETAIL RED-LINED
 TO SHOW 1#4 VERTICAL BAR @ 48" O.C. IN
 CONCRETE FILLED CELLS AS AGREED WITH
 HOWARTH LEWIS (ARCHITECT OF RECORD)
 DURING A TELEPHONE CONVERSATION ON
 7/15/04.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:47 Rev Time 0.00
Received By rbrown Date 2004-06-30 Time 13:38 Sent To  
Notes
2004-06-30 00:00:00REVISION FOR SHEETS ASP-1, A-203, A-204
 & A-302, RE-SUBMITTED 6/25/04 (AMENDED
 IN RESPONSE TO 6/15/04 DENIAL OF THE
 REVISION ORIGINALLY SUBMITTED 6/8/04):
  
 2) FBC* 1606.1CABANA ROOM WINDOW.
 THIS COMMENT HAS NOT BEEN ADDRESSED
 SINCE THE LAST REVIEW.THE SIZE OF THE
 PROPOSED 7'-2" WIDE CABANA ROOM WINDOW
 EXCEEDS THE SIZE COVERED BY THE
 SUBMITTED PGT INDUSTRIES SINGLE HUNG
 WINDOW PRODUCT APPROVAL NOA# 02-0419.13.
 STRUCTURAL MULLIONS ARE REQUIRED.
 SUBMIT A PRODUCT APPROVAL FOR THE
 MULLIONS, OR SUBMIT ENGINEERING FOR
 MULLIONS.
  
 4) FBC 2103.2.4SHEET A-203, NEW SITE
 WALL.THE WALL SHALL HAVE A MINIMUM OF
 1#4 VERTICAL BAR AT 48" O.C. IN CONCRETE
 FILLED CELLS.AMEND THE PLAN.
  
 NOTE:
 THE REVISED SHEET A-204 DOES NOT INCLUDE
 THE GUARDRAIL STRENGTH PROVISO NOTE
 (COPY ATTACHED FOR EASE OF REFERENCE)
 THAT WAS ATTACHED TO THE PERMIT APPROVED
 COPY OF SHEET S204/SK3 AT THE TIME OF
 PERMIT ISSUE.AMEND THE PLAN BEFORE
 RE-SUBMITTING THE REVISION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:30 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 09:19 Sent To  
Notes
2004-06-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 6/8/04 FOR SHEET
 A-203.
  
 1) FBC* 104.2.1WEST ELEVATION OF
 CABANA ROOM.SHEET A-302, ELEVATIONS,
 HAS NOT BEEN REVISED TO REFLECT THE
 PROPOSED CHANGES TO THE CABANA ROOM
 WINDOW.SUBMIT A REVISED ELEVATION.
  
 2) FBC* 1606.1THE SIZE OF THE PROPOSED
 7'-2" WIDE CABANA ROOM WINDOW EXCEEDS
 THE SIZE COVERED BY THE SUBMITTED PGT
 INDUSTRIES SINGLE HUNG WINDOW PRODUCT
 APPROVAL NOA# 02-0419.13.STRUCTURAL
 MULLIONS ARE REQUIRED.SUBMIT A PRODUCT
 APPROVAL FOR THE MULLIONS, OR SUBMIT
 ENGINEERING.
  
 3) FBC* 104.2.1SOUTH ELEVATION AND
 SECOND FLOOR PLAN. SHEET A-302 -
 ELEVATIONS, AND SHEET A-204 - SECOND
 FLOOR PLAN HAVE NOT BEEN REVISED TO
 REFLECT THE PROPOSED CHANGES TO THE
 COLUMN ARRANGEMENT.SUBMIT REVISED
 SHEETS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-07-10 Cont ID  
Sent By csiegber Date 2004-06-08 Time 09:14 Rev Time 0.00
Received By rbrown Date 2003-07-10 Time 13:22 Sent To M
Notes
2003-07-10 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC 1005.4BEDROOMS #2 AND #3 ARE SHOWN
 AS HAVING WINDOWS WITH SUFFICIENT HEIGHT
 AND WIDTH FOR EGRESS. ALSO, THE BEDROOMS
 SHALL EACH HAVE AT LEAST ONE OF THOSE
 WINDOWS WITH A MINIMIUM NET CLEAR
 OPENING OF 5.7 SQ FT.
  
 --PROVISO--
 FBC 1608.2.2.1IN ADDITION TO THE
 STRENGTH REQUIREMENT STATED ON SHEET
 S204/SK3, A 200 POUND POINT LOAD SHALL
 BE RESISTED WHEN APPLIED (AS A SEPARATE
 LOAD) IN ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL.
  
 --PROVISO--
 THE SUBMITTED ENERGY CODE COMPLIANCE
 FORM INCORRECTLY STATES THE CONDITIONED
 FLOOR AREA OF THE WHOLE HOUSE AS
 1147 SQ FT.SUBMIT TWO COPIES OF FORMS
 WITH THE CORRECT AREA (3647 SQ FT).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:31 Rev Time 0.00
Received By rbrown Date 2003-06-23 Time 15:53 Sent To E
Notes
2003-06-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENT
 NUMBERING FOLLOWS ON FROM THE BUILDING
 PLAN REVIEW OF 5/19/03:
  
 15) FBC 3401.7.1.2AREA OF ADDITION V'S
 AREA OF EXISTING BUILDING (NOTE: SEE
 COMMENT #19 BELOW FOR AN EXPLANATION OF
 THE EFFECTS OF THE CODE REVISIONS COMING
 INTO EFFECT JULY 1, 2003).IT IS NOTED
 THAT ON SHEETS ASP-1 AND A-203 THE AREA
 OF THE EXISTING BUILDING HAS NOW BEEN
 DECLARED AS 2680 S.F. (WAS 3872 S.F ON
 THE PREVIOUS REVISION OF THE PLANS). THE
 AREA OF THE ADDITION, AT 967 S.F., NOW
 EXCEEDS 25% OF THE EXISTING BUILDING
 AREA.BOTH THE EXISTING BUILDING AND
 THE ADDITION SHALL BE MADE TO COMPLY
 WITH ALL REQUIREMENTS OF FBC FOR A
 BUILDING OF A SIZE EQUAL TO THE COMBINED
 AREA AS FOLLOWS:
  
 16) FBC 1005.4 EMERGENCY EGRESS WINDOWS.
 AMEND OR ANNOTATE THE PLANS TO SHOW THAT
 THE WINDOWS TO THE EXISTING BEDROOMS #2
 AND #3 PROVIDE MINIMUM CLEAR OPENINGS OF
 24" HIGH X 20" WIDE FOR SECONDARY EGRESS
 ALSO THE MINIMUM NET CLEAR OPENING SHALL
 BE 5.7 SQ FT.
  
 17) FBC 13-103.0ENERGY CODE COMPLIANCE
 THE SUBMITTED FORMS ARE FOR THE ADDITION
 ONLY.AS PER COMMENT #15 (ABOVE) THE
 WHOLE HOUSE SHALL BE SHOWN TO COMPLY BY
 SUBMITTAL OF CODE COMPLIANCE FORMS FOR
 THE WHOLE HOUSE.
  
 18) FBC 1015.3STAIR GUARDRAIL.AMEND/
 ANNOTATE THE PLANS TO SHOW THAT THE
 STAIR GUARDRAIL ON THE EXISTING STAIR IS
 AT LEAST 36" HIGH AND THE RAILS ARE
 SPACED SO THAT A 4" SPHERE CANNOT PASS
 THROUGH ANY OPENING UPTO A HEIGHT OF 34"
  
 19) WITH REFERENCE TO COMMENT #15 ABOVE,
 NOTE THAT, AFTER THE JULY 1, 2003
 REVISIONS TO THE FLORIDA BUILDING CODE
 COME INTO EFFECT, FBC 3701.7.1.2 WILL NO
 LONGER BE APPLICABLE TO R3 OCCUPANCIES
 (WHICH INCLUDES ONE AND TWO FAMILY
 DWELLINGS).FOR GROUP R3 OCCUPANCY THAT
 SECTION WILL BE REPLACED BY NEW SECTION
 FBC 3401.7.1.2, WHICH STATES THAT WHEN
 THE ADDITION CONSTITUTES 25% OR MORE OF
 THE AREA OF THE EXISTING BUILDING, THE
 ADDITION SHALL BE MADE TO COMPLY WITH
 THE CODE, AND THE EXISTING BUILDING
 SHALL COMPLY WITH THE FOLLOWING:
 A) G.F.C.I. OUTLETS SHALL BE INSTALLED
 WHERE REQUIRED BY THE CODE.
 B) SMOKE DETECTORS SHALL BE INSTALLED
 WHERE REQUIRED BY THE CODE.
 C) IN NO CASE SHALL THE EXISTING
 BUILDING AND THE ADDITION EXCEED
 THE SIZE/TYPE LIMITS OF TABLE 500.
 THESE, LESS RESTRICTIVE REQUIREMENTS ARE
 APPLICABLE TO ANY BUILDING PERMIT
 APPLICATION RECEIVED ON/AFTER
 JULY 1, 2003.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-19 Cont ID  
Sent By btrobaug Date 2003-06-19 Time 16:26 Rev Time 0.00
Received By rbrown Date 2003-05-19 Time 14:12 Sent To  
Notes
2003-05-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 11/5/02:
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.BEFORE A BUILDING PERMIT
 CAN BE ISSUED, THE SUBMITTED ENERGY CODE
 COMPLIANCE FORMS SHALL BE SIGNED BY THE
 BUILDING OWNER, THE OWNER'S ARCHITECT
 OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.ALSO THE
 PROJECT INFORMATION HAS NOT BEEN
 COMPLETED.ENTER THE NAME OF THE
 BUILDER, PERMITTING OFFICE (WEST PALM
 BEACH), JURISDICTION NUMBER (604700) AND
 PERMIT NUMBER (02091769).CORRECT THE
 PROJECT ADDRESS CITY TO READ 'WEST PALM
 BEACH' INSTEAD OF "PLM BCH CO".
  
 4) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT PRODUCT APPROVALS FOR THE NEW
 CEMENT TILE ROOFING, NEW AND REPLACEMENT
 WINDOWS, AND THE NEW GLAZED EXTERIOR
 DOORS.THE SPECIFICATION OF IMPACT
 RESISTANT GLAZING FOR BOTH THE NEW AND
 EXISTING WINDOWS IS NOTED.
  
 7) ANCHORS AND STRAPS.THE ADDITION OF
 ANCHOR REFERENCES ON THE PLANS IS NOTED
 BUT THE TYPE AND NUMBER OF ANCHOR
 FASTENERS TO THE TRUSSES JOISTS, BEAMS
 ETC SHALL BE SPECIFIED ON THE PLANS.
  
 11) FBC 2405.2SAFETY GLAZING FOR NEW
 EXTERIOR DOORS.THE GLASS IN THE NEW
 ALUMINUM CABANA BATH DOOR IS NOT SHOWN
 AS IMPACT RESISTANT ON SHEET A-203
 (FIRST FLOOR PLAN) OR SHEET A-302
 (ELEVATION).THIS GLASS IS IN A
 'HAZARDOUS LOCATION' AND IS REQUIRED TO
 BE SAFETY GLASS SATISFYING THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 13) THE SUBMITTED NOTICE OF
 COMMENCEMENT IS MORE THAN ONE YEAR OLD
 AND HAS EXPIRED.A VALID RECORDED COPY
 OF THE NOTICE OF COMMENCEMENT MUST BE
 BE SUBMITTED BEFORE A BUILDING PERMIT
 CAN BE ISSUED.
  
 14) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By kstevens Date 2003-05-14 Time 17:25 Rev Time 0.00
Received By rbrown Date 2002-11-05 Time 08:37 Sent To  
Notes
2002-11-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FBC* 104.2.1.2THE CHIMNEY IS SHOWN
 ON EACH OF THE EXISTING ELEVATIONS BUT
 IT IS OMITTED FROM THE PROPOSED
 ELEVATIONS.THERE ARE NO NOTES STATING
 THAT THE CHIMNEY IS TO BE REMOVED.
 CLARIFY/AMEND THE PLANS AS APPROPRIATE
 TO FULLY DESCRIBE THE SCOPE OF WORK.
 IS THE CHIMNEY TO BE REMOVED?
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS (FORM
 600C-01 SOUTH)
  
 4) SUBMIT PRODUCT APPROVALS FOR THE NEW
 CEMENT TILE ROOFING, NEW AND REPLACEMENT
 WINDOWS, AND THE NEW GLAZED EXTERIOR
 DOORS.THE SPECIFICATION OF IMPACT
 RESISTANT GLAZING FOR BOTH NEW WINDOWS
 AND THE REPLACEMENT OF EXISTING WINDOWS
 IS NOTED.
  
 5) FBC 1606.1.7WIND LOAD DESIGN
 INFORMATION.THE INFORMATION SHOWN ON
 THE PLANS IS NOTED, BUT FOR DESIGN OF
 EXTERIOR COMPONENTS AND CLADDING THE
 ROOF PRESSURES EXTRACTED FROM FBC TABLE
 1606.2B ARE FOR A ROOF ANGLE OF 30 TO 45
 DEGREES WHICH IS NOT CORRECT.AS THE
 ANGLE OF THE PROPOSED ROOF IS BETWEEN
 10 AND 30 DEGREES, IT WILL BE SUBJECTED
 TO GREATER NEGATIVE WIND PRESSURES IN
 ZONES 2 AND 3.AMEND THE EXTRACTS ON
 BOTH SHEET S-203 AND SHEET S-701, AND
 REVIEW THE DESIGN ACCORDINGLY.
  
 6) FBC 1606.2.3SHEET S-701.THE EDGE
 STRIP AND END ZONE DIAGRAM EXTRACTS FROM
 FBC FIGURE 1606.2(C) FOR COMPONENT AND
 CLADDING WIND LOAD ARE INCORRECT.
 ZONE 5 IS NOT SHOWN ON THE BUILDING
 ELEVATION, AND THE ZONES FOR HIPPED
 ROOFS HAVE BEEN INCORRECTLY LABELLED.
 AMEND THE PLANS.
  
 7) ANCHORS AND STRAPS.SHEETS S-202 AND
 S-203 DO NOT STATE THE UPLIFT AT THE
 TRUSS SUPPORTS AND DO NOT SPECIFY ANCHOR
 REFERENCES AT FLOOR FRAMING OR ROOF
 TRUSS SUPPORT LEVELS.ADD THE REQUIRED
 INFORMATION TO THE PLANS.
  
 8) WALL SECTION THROUGH LIBRARY.SHEET
 A-702, SECTION D SPECIFIES 'LSC18 STRAP'
 AT THE CABANA ROOM TRUSS SUPPORT.
 UNLIKE THE ANCHORS SPECIFIED ELSEWHERE
 ON THE PLANS, THIS IS NOT A SIMPSON
 REFERENCE.CLARIFY/AMEND THE REFERENCE
 AS APPROPRIATE.
  
 9) FBC* TABLE 2306.1THE ROOF SHEATHING
 FASTENER TYPE AND SPACING SHALL ADDED TO
 THE PLANS TO DEMONSTRATE COMPLIANCE WITH
 THIS CITY OF WPB AMENDMENT TO FBC 2001.
  
 10) FBC 2309.6ACCESS TO ATTIC SPACE.
 AMEND THE PLANS TO SHOW THE PROVISION OF
 AN OPENING, NOT LESS THAN 20"X 36", FOR
 EACH ATTIC SPACE THAT HAS A CLEAR HEIGHT
 OF 24" OR GREATER.
  
 11) FBC 2405.2THE GLAZING IN THE NEW
 ALUMINUM EXTERIOR DOORS IS IN A
 'HAZARDOUS LOCATION' AND IS REQUIRED TO
 BE SAFETY GLASS SATISFYING THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 12) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-07 Cont ID  
Sent By btrobaug Date 2004-01-07 Time 12:15 Rev Time 0.50
Received By btrobaug Date 2004-01-07 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-06-19 Cont ID  
Sent By csiegber Date 2003-12-23 Time 13:26 Rev Time 0.50
Received By btrobaug Date 2003-06-19 Time 15:30 Sent To B
Notes
2003-06-26 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THESE PLANS ARE APPROVED PENDING THERE
 ARE NO CHANGES IN THE PLANS RESULTING
 FROM BUILDING REVIEW REGARDING CHAPTER
 34 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-06-12 Time 09:54 Rev Time 0.75
Received By btrobaug Date 2003-05-09 Time 13:58 Sent To M
Notes
2003-05-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SUBMIT LOAD CALCULATIONS
 PER 220,215-5,FOR EXISTING LOADS AND
 ALL ADDED LOADS.
  
 3} PROVIDE A RISER DIAGRAM INDICATING
 ALL CONDUIT & CONDUCTOR SIZES.ALSO SHOW
 THE GROUNDING ELECTORDE SYSTEM
 COMPLYING WITH 250-50 & 250-66.
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE.(FOR THE CABANA ROOM).210-12.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.ON SCHEDULE.
  
 6} INDICATE THE OVER CURRENT PROTECTION
 IN THE METER/MAIN FOR THE EQUIPMENT IT
 FEEDS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-15 Cont ID  
Sent By shernand Date 2003-04-28 Time 13:34 Rev Time 0.50
Received By btrobaug Date 2002-10-15 Time 16:06 Sent To M
Notes
2002-10-15 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING DISCREPANCIES
 ON THE PLANS,MAKE ANY NECESSARY CHANGES
 AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT LOAD CALCAULATION
 -S.PER 220,215-5.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 6} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-08-24 Cont ID  
Sent By ptjomsto Date 2004-08-24 Time 12:20 Rev Time 0.00
Received By ptjomsto Date 2004-08-24 Time 12:20 Sent To  
Notes
2004-08-24 00:00:00GIVEN TO ROBERT BROWN

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:47 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 09:47 Sent To B
Notes
2004-07-09 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:30 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 12:30 Sent To B
Notes
2004-06-25 00:00:00TO RB DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-06-08 Time 09:14 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 09:14 Sent To B
Notes
2004-06-08 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 13:26 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 13:26 Sent To E
Notes
2003-12-23 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:31 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 16:31 Sent To B
Notes
2003-07-08 00:00:00RBROWN DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 09:54 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 09:54 Sent To E
Notes
2003-06-12 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 13:34 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 13:34 Sent To E
Notes
2003-04-28 00:00:00BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-07-16 Cont ID  
Sent By pkrauss Date 2003-07-16 Time 14:38 Rev Time 0.35
Received By pkrauss Date 2003-07-16 Time 14:38 Sent To  
Notes
2003-07-16 00:00:00PLEASE PROVIDE REVISED ENERGY CALCS
 WITHIN 10 DAYS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-02 Cont ID  
Sent By rbrown Date 2003-07-10 Time 14:12 Rev Time 0.15
Received By pkrauss Date 2003-07-02 Time 09:13 Sent To  
Notes
2003-07-02 00:00:00PLANS APPROVED 5-13-03 - NO CHANGES ON
 THIS SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By kstevens Date 2003-06-27 Time 13:23 Rev Time 0.30
Received By pkrauss Date 2003-05-13 Time 12:01 Sent To P
Notes
2003-05-13 00:00:00PROVISO:
  
 PROVIDE AIR TRANSFER OR RETURN FROM THE
 SECOND FLOOR SITTING ROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-19 Cont ID  
Sent By btrobaug Date 2003-05-09 Time 14:48 Rev Time 0.75
Received By hmoser Date 2002-10-19 Time 10:55 Sent To  
Notes
2002-10-19 00:00:00PLAN DENIED
 1) NO EQUIPMENT SCHEDULE
 2) IS EQUIPMENT EXISTING OR NEW.IF NEW
 NEED ENERGY CALCULATIONS,MANUAL (J)
 3) NO DUCT SIZE ON PLAN
 4) NEED EXHAUST FAN IN CABANA BATH AND
 IN LAV.BY EXISTING BEDROOM #2
 5) NOT ENOUGH INFORMATION ON PLAN
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 3 Status N Date 2003-06-27 Cont ID  
Sent By kstevens Date 2003-06-27 Time 13:22 Rev Time 0.25
Received By kstevens Date 2003-06-27 Time 13:22 Sent To M
Notes
2003-06-27 00:00:00NO NEW PLUMBING PLANS - BECAUSE OF SIZE
 OF ADDITION, THE WHOLE HOUSE SHALL BE
 BROUGHT UP TO FBC-2001 COMPLIANCE. NO
 CHANGE FOR RESIDENTIAL.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-14 Cont ID  
Sent By kstevens Date 2003-05-14 Time 17:24 Rev Time 0.33
Received By kstevens Date 2003-05-14 Time 17:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By pkrauss Date 2003-05-13 Time 12:07 Rev Time 0.45
Received By pschmitz Date   Time   Sent To  
Notes
2002-10-21 00:00:00PLUMBING PLAN REVIEW, APPROVED. PES
 FBC 2001,NO PLBG ISOMETRIC PROVIDED,
 ALL WORKSUBJECT TO FIELD INSPECTOR
 APPROVAL, PES.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-09 Cont ID  
Sent By sgraham Date 2002-10-09 Time 08:56 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***