| 2002-10-01 00:00:00 | 1) PLEASE INDICATE WHAT THE VOICE |
| | EVACUATION MESSAGE WILL ADVISE WHEN THE |
| | FIRE ALARM SYSTEM IS ACTIVATED. |
| | |
| | 2) WHY ARE THERE NO SPEAKER STROBES |
| | INSTALLED IN THE RECORDING STUDIO OR |
| | LARGE MUSIC ROOM LOCATED ON THE SECOND |
| | FLOOR. |
| | |
| | 3) PLEASE NOTE ON THE PLANS THAT SMOKE |
| | DETECTORS ARE TO BE INSTALLED NO |
| | CLOSER THAN 3 FEET FROM AIR CONDITIONER |
| | DIFFUSERS. ALSO THE PLACEMENT OF |
| | SMOKE DETECTORS ARE NOT TO EXCEED |
| | MANUFACTURER'S REQUIREMENTS. |
| | |
| | 4) IT WAS NOTED THAT SMOKE DETECTORS |
| | ARE INSTALLED IN TWO OF THE STAIRS ON |
| | THE THIRD LEVEL EXCEPT FOR ONE. WHAT |
| | IS THE DIFFERENCE. |
| | |
| | 5) ALL INITIATING DEVICES ARE TO |
| | ACTIVATE THE FIRE ALARM SYSTEM. |
| | |
| | 6) THE LOCATION OF THE FIRE ALARM |
| | CONTROL PANEL IS NOT VERY GOOD. IT |
| | HAS VERY LIMITED QUICK ACCESS AND TRAVEL |
| | IS REQUIRED DOWN A HALLWAY. IT APPEARS |
| | THAT NO REMOTE ANNUNICIATORS HAVE BEEN |
| | PROVIDED. ONE WAS LOCATED BUT HOW IS |
| | ACCESS PROVIDED. |
| | 7) ARE THERE ANY SECURITY DEVICES LIKE |
| | MAG LOCKS OR OTHER DEVICES CONNECTED |
| | TO THE FIRE ALARM PANEL. PLEASE ADVISE. |
| | |
| | 8) KITCHEN HOOD SYSTEM SHALL BE |
| | CONNECTED TO THE FIRE ALARM SYSTEM. |
| | |
| | 9) SPEAKER STROBE LOCATED IN VALET |
| | RAMP. PLEASE ADVISE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |