Plan Review Details - Permit 02091713
Plan Review Stops For Permit 02091713
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-11 Cont ID  
Sent By btrobaug Date 2002-10-15 Time 07:47 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-10-11 00:00:00*************FAILED**********
  
 1. CONTRACT SHOWS HEAT PUMP; NO HEAT
 PUMP INFO SUBMITTED.( NOT SHOWN ON APPL
 2. CONTRACT SHOWS OWNER AS SCOTT SOMMER
 APPLICATION SHOWS JAMES HACKET; PBC
 SHOWS NEW OWNER 8/02 AS MELISA MALLEY.
 SUBMIT PROOF OF OWNERSHIP & CONTRACT TO
 AGREE.
 3. POOL BARRIER DETAILS PER BFC 2001
 NOT SHOWN ON PLANS. SHOW METHOD OF
 OPENING PROTECTION FROM HOUSE TO POOL
 AREA ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-15 Cont ID  
Sent By kstevens Date 2002-10-11 Time 14:54 Rev Time 0.25
Received By btrobaug Date 2002-10-11 Time 10:34 Sent To B
Notes
2002-10-15 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION
 INDICATING THE SIZE OF THE SERVICE AND
 SHOWING THE TOTAL CONNECTED LOAD AFTER
 THE NEW EQUIPMENT IS INSTALLED.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-11 Cont ID  
Sent By kstevens Date 2002-10-09 Time 15:44 Rev Time 0.00
Received By kstevens Date 2002-10-09 Time 15:43 Sent To E
Notes
2002-10-11 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (PROVIDED DETAIL)
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 4) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 5) PLANS DO NOT CALL OUT POOL HEATER,
 BUT CONTRACT SHOWS HEAT PUMP??
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By sgraham Date 2002-10-07 Time 10:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***