Plan Review Details - Permit 02091693
Plan Review Stops For Permit 02091693
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-07 Cont ID  
Sent By hpiskura Date 2002-11-07 Time 13:25 Rev Time 0.00
Received By hpiskura Date 2002-11-07 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-11 Cont ID  
Sent By hpiskura Date 2002-10-11 Time 10:36 Rev Time 0.00
Received By hpiskura Date 2002-10-11 Time 10:28 Sent To  
Notes
2002-10-11 00:00:00THE PLANS INDICATE A MIXED OCCUPANCY
 USE.PROVIDE THE TWO HOUR FIRE RATED
 SEPARATION FOR THE GROUP M AND S2 USES
 IN ACCORDANCE WITH FBC 704.1 AND INSURE
 THAT THE EXISTING DEMISING WALL IS TWO
 HOUR RATED OR MODIFY AS NECESSARY.
  
 INDICATE ON THE PLANS THE TYPE OF
 BUSINESS AND THE NATURE AND QUANTITY OF
 THE COMMODITIES TO BE STORED ON THE
 PREMISES.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE
 PARTIONS AND THE OPENING PROTECTIVES.
 SEE FBC 701.2.
  
 SHOW A CONNECTION DETAIL FOR THE
 OVERHEAD DOOR TO BE INSTALLED AND
 PROVIDE A NOTICE OF ACCEPTANCE AND/OR
 TEST REPORT FROM A RECOGNIZED AGENCY
 FOR THE OVER HEAD DOOR.SHOW THE WIND
 PRESSURES FOR THE OPENING.
  
 SHEET A-3, SECTION A OPENING THROUGH
 EXISTING WALL, WHERE DOES THIS TAKE
 PLACE? WHAT IS THE HEADER SIZE?

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 07:15 Rev Time 0.25
Received By dpalmer Date 2002-11-13 Time 07:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 06:48 Rev Time 0.50
Received By dpalmer Date 2002-10-31 Time 06:48 Sent To  
Notes
2002-10-31 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, NOTES FROM FIRST
 REVIEW WERE NOT ADDRESSED. PLEASE
 SEE FIRST SET OF REVIEW NOTES AND SUBMIT
 THE ABOVE INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-03 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 16:46 Rev Time 0.50
Received By dpalmer Date 2002-10-03 Time 06:10 Sent To  
Notes
2002-10-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE APPLICATION MENTIONS
 ADDING TWO NEW OFFICES AND PLANS SHOW
 OTHER NEW ELECTRICAL WORK?
 PLEASE CLOUD AREA OF ACTUAL WORK AND
 CLARIFY IF OTHER ELECTRICAL SHOWN IS
 NEW OR EXISTING?
 IF NEW, PLEASE PROVIDE CIRCUITING FOR
 ALL NEW.SUBMIT PANEL SCHEDULE/LOAD CALCS
 215-5
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.700-12
  
 3)NOTE: PLEASE CLARIFY IF THERE IS NEW
 OR EXISTING SHOW WINDOW RECEPTS? 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-31 Cont ID  
Sent By mcarsill Date 2002-10-31 Time 10:19 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-02 Cont ID  
Sent By mcarsill Date 2002-10-02 Time 14:40 Rev Time 0.00
Received By mcarsill Date 2002-10-02 Time 14:40 Sent To  
Notes
2002-10-02 00:00:001) PLEASE INDICATE IF THERE'S ANY FIRE
 SEPARATION BETWEEN THE WAREHOUSE AND
 SHOWROOM.
  
 2) PLEASE EXPLAIN HOW EXITING WORKS FROM
 THE WAREHOUSE AREA.
  
 3) THE ELECTRICAL PLAN DISPLAYS ONLY ONE
 EMERGENCY LIGHT IN THE WAREHOUSE. THERE
 APPEARS TO BE NO EXIT SIGNS IN THE
 WAREHOUSE. PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096, EXT. 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-13 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 06:47 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2002-10-31 00:00:00TO COMM BOARD.
2002-10-30 00:00:00TO DVP./WRT