Plan Review Details - Permit 02091693
| Plan Review Stops For Permit 02091693 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-11-07 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-11-07 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-11-07 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-11 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-11 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-11 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2002-10-11 00:00:00 | THE PLANS INDICATE A MIXED OCCUPANCY | | | USE.PROVIDE THE TWO HOUR FIRE RATED | | | SEPARATION FOR THE GROUP M AND S2 USES | | | IN ACCORDANCE WITH FBC 704.1 AND INSURE | | | THAT THE EXISTING DEMISING WALL IS TWO | | | HOUR RATED OR MODIFY AS NECESSARY. | | | | | | INDICATE ON THE PLANS THE TYPE OF | | | BUSINESS AND THE NATURE AND QUANTITY OF | | | THE COMMODITIES TO BE STORED ON THE | | | PREMISES. | | | | | | SHOW THE FIRE DESIGN NUMBER FOR THE | | | PARTIONS AND THE OPENING PROTECTIVES. | | | SEE FBC 701.2. | | | | | | SHOW A CONNECTION DETAIL FOR THE | | | OVERHEAD DOOR TO BE INSTALLED AND | | | PROVIDE A NOTICE OF ACCEPTANCE AND/OR | | | TEST REPORT FROM A RECOGNIZED AGENCY | | | FOR THE OVER HEAD DOOR.SHOW THE WIND | | | PRESSURES FOR THE OPENING. | | | | | | SHEET A-3, SECTION A OPENING THROUGH | | | EXISTING WALL, WHERE DOES THIS TAKE | | | PLACE? WHAT IS THE HEADER SIZE? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-11-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-13 |
Time |
07:15 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-11-13 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-31 |
Time |
06:48 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-10-31 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE, NOTES FROM FIRST | | | REVIEW WERE NOT ADDRESSED. PLEASE | | | SEE FIRST SET OF REVIEW NOTES AND SUBMIT | | | THE ABOVE INFORMATION FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-10-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-30 |
Time |
16:46 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-10-03 |
Time |
06:10 |
Sent To |
|
|
| Notes |
| 2002-10-03 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE APPLICATION MENTIONS | | | ADDING TWO NEW OFFICES AND PLANS SHOW | | | OTHER NEW ELECTRICAL WORK? | | | PLEASE CLOUD AREA OF ACTUAL WORK AND | | | CLARIFY IF OTHER ELECTRICAL SHOWN IS | | | NEW OR EXISTING? | | | IF NEW, PLEASE PROVIDE CIRCUITING FOR | | | ALL NEW.SUBMIT PANEL SCHEDULE/LOAD CALCS | | | 215-5 | | | 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | THAT MAY AFFECT ELECTRICAL PLANS.700-12 | | | | | | 3)NOTE: PLEASE CLARIFY IF THERE IS NEW | | | OR EXISTING SHOW WINDOW RECEPTS? 210-62 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-31 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-31 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-10-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-02 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-02 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2002-10-02 00:00:00 | 1) PLEASE INDICATE IF THERE'S ANY FIRE | | | SEPARATION BETWEEN THE WAREHOUSE AND | | | SHOWROOM. | | | | | | 2) PLEASE EXPLAIN HOW EXITING WORKS FROM | | | THE WAREHOUSE AREA. | | | | | | 3) THE ELECTRICAL PLAN DISPLAYS ONLY ONE | | | EMERGENCY LIGHT IN THE WAREHOUSE. THERE | | | APPEARS TO BE NO EXIT SIGNS IN THE | | | WAREHOUSE. PLEASE ADVISE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096, EXT. 8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-31 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | TO COMM BOARD. | | 2002-10-30 00:00:00 | TO DVP./WRT |
|
|
|