Plan Review Details - Permit 02091641
Plan Review Stops For Permit 02091641
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-06 Cont ID  
Sent By hpiskura Date 2002-11-06 Time 12:56 Rev Time 0.00
Received By hpiskura Date 2002-11-06 Time 12:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-23 Cont ID  
Sent By hpiskura Date 2002-10-23 Time 15:38 Rev Time 0.00
Received By hpiskura Date 2002-10-23 Time 15:29 Sent To  
Notes
2002-10-23 00:00:00SECTION 2/A3.PLEASE PROVIDE A SPECIFIC
 CONSTRUCTION DETAIL FOR THE SUSPENDED
 SOFFIT.INCLUDE FRAMING MEMBERS, SIZE,
 SPACING AND FASTENERS, INCLUDING
 ATTACHMENT TO THE DECK ABOVE.SEE FBC
 104.2.1.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 06:39 Rev Time 0.50
Received By dpalmer Date 2002-10-31 Time 06:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-03 Cont ID  
Sent By dpalmer Date 2002-10-03 Time 06:27 Rev Time 0.25
Received By dpalmer Date 2002-10-03 Time 06:27 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-10-23 Cont ID  
Sent By hpiskura Date 2002-10-23 Time 15:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-29 Cont ID  
Sent By mcarsill Date 2002-10-29 Time 10:26 Rev Time 0.00
Received By mcarsill Date 2002-10-29 Time 10:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-10-01 Cont ID  
Sent By mcarsill Date 2002-10-01 Time 10:46 Rev Time 0.00
Received By mcarsill Date 2002-10-01 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-08 Cont ID  
Sent By dpalmer Date 2002-11-08 Time 10:54 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-30 Cont ID  
Sent By pkrauss Date 2002-10-30 Time 10:36 Rev Time 0.35
Received By pkrauss Date 2002-10-30 Time 10:26 Sent To  
Notes
2002-10-30 00:00:00PROVISO:2ND REQUEST
  
 AS PER COMMENTS DATED 10-15-02 - PLANS
 DO NOT INIDATE RATING OF EXISTING WALLS.
 PLAN SHEET ME-3 HVAC DESIGN INFORMATION,
 THIS SCHEDULE INDICATES FIRE DAMPERS ARE
 "EXISTING".FIRE DAMPERS (NEW OR
 EXISTING) ARE IDENTIFIED ON THE PLAN.
 PROVIDE REVISION TO PLAN SHOULD ANY
 "EXISTING" OR NEW FIRE DAMPERS BE
 BE LOCATED IN THE AREA BEING RENOVATED.
  
 SPOKE WITH KEN WITH ROTELLA TORYAN,
 FIRE DAMPERS ARE ADDRESSED ON THE TENANT
 BUILDOUT PERMIT 02090526.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-15 Cont ID  
Sent By pkrauss Date 2002-10-15 Time 12:51 Rev Time 0.45
Received By pkrauss Date 2002-10-15 Time 12:19 Sent To  
Notes
2002-10-15 00:00:00PROVISO:
  
 PLAN SHEET ME-3 HVAC DESIGN
 INFORMATION, THIS INDICATES FIRE DAMPERS
 ARE "EXISTING".NO FIRE DAMPERS NEW OR
 EXISTING ARE INDICATED ON PLAN.
 PROVIDE REVISION TO PLAN SHOULD ANY
 "EXISTING" OR NEW FIRE DAMPERS BE
 LOCATED IN THE AREA BEING RENOVATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-08 Cont ID  
Sent By kstevens Date 2002-11-08 Time 10:49 Rev Time 1.25
Received By kstevens Date 2002-11-08 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 14:00 Rev Time 0.50
Received By kstevens Date 2002-10-12 Time 14:00 Sent To  
Notes
2002-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT ME-4 GENERAL NOTES #1, CODE IN
 EFFECT IS FBC-2001.
 2) SHT ME-4 PROVIDE MANUFACTURE CUT
 SHEETS FOR INST-HOT.
 3) SHT ME-4 WATER RISER DIAGRAMS, AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROP IN CEILING AS SHOWN PER PDI-WH 201
 AND MANUFACTURE INSTALLATION INSTRUCTION
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-10-23 Cont ID  
Sent By hpiskura Date 2002-10-23 Time 15:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***