Plan Review Details - Permit 02091632
Plan Review Stops For Permit 02091632
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-05 Cont ID  
Sent By hpiskura Date 2002-12-05 Time 10:37 Rev Time 0.00
Received By hpiskura Date 2002-12-05 Time 08:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-23 Cont ID  
Sent By jwitmer Date 2002-10-23 Time 08:54 Rev Time 3.00
Received By jwitmer Date 2002-10-23 Time 08:54 Sent To  
Notes
2002-10-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02091632
 ADD: 460 S ROSEMARY/ 180
 CONT:PLAN REVIEW
 "TOSSED"
 CONTACT:LAKOW DEBRA
 TEL: (561)655-6199
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET A-2.2 SECTION @ STOREFRONT
 SHALL INDICATE THE FOLLOWING INFORMATION
 ON THE PLANS:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST. PLANS DO NOT INDICATE
 IF STORM SHUTTERS OR IMPACT GLAZING
 SHALL BE USED.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) 4 UNIT SLIDING GLASS DOOR REPORT
 B) MULLION REPORT SEPERATING DOOR/
 WINDOW & WINDOW / WINDOW.
 C) FIXED GLAZING
 D) EXTERIOR SWING DOORS, GLASS DOOR &
 METAL DOORS.
 E) STORM SHUTTERS/ KEY PLAN / SCHEDULE
  
 4) 4"X6" METAL TUBE (MULLION) SHALL
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 5)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 6)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 7)1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 8)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 9)1707.4.4.2 WINDOW BUCKS TO BE A MINI-
 MUM OF 1 1/2" OR WINDOWS ARE TO BE FAST-
 ENED TO THE STRUCTURAL SUBTRATE.
  
 10) STORM SHUTTERS: REQUIREMENTS FOR
 KEY PLAN AND FOR ANCHORING SCHEDULE:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 11) SHEET A-1 DOOR SCHEDULE DOESN'T
 TIE TO FLOOR PLAN? NO NUMBERS?
  
 12) ADDITIONAL INFORMATION REQUIRED FOR
 ALUMINIUM STOREFRONT FRAME TO EXISTING
 LINTEL, HOW CLOSE TO THE EDGE OF THE
 LINTEL WILL THE FASTENERS OCCUR? SHALL
 A EDGE REDUCTION BE REQUIRED FOR THIS
 TYPE OF FASTENER?
  
 13) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 14)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 15)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 16) 11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 17)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. SEE SIDE ENTRY DOOR 18"
 CLEAR REQUIRED ON THE PULL SIDE.
  
 18) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 19)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 20)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 21)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 22)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-03-03 Cont ID  
Sent By dpalmer Date 2003-03-03 Time 13:51 Rev Time 0.50
Received By dpalmer Date 2003-03-03 Time 13:51 Sent To  
Notes
2003-03-03 00:00:00PLANS STILL HAVE REDLINES FOR SHOW
 WINDOW RECEPTS. 210-62.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2002-11-20 Time 16:00 Rev Time 0.50
Received By dpalmer Date 2002-11-20 Time 16:00 Sent To  
Notes
2002-11-20 00:00:00NOTES ON PLANS.
  
 SHOW WINDOW RECEPTS REQ`D PER 210-62
  
 TAPPED CONDUCTORS FROM TRANSFORMERS TO
 PANELS. PER 240-21.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2002-10-07 Time 18:45 Rev Time 0.50
Received By dpalmer Date 2002-10-07 Time 18:45 Sent To  
Notes
2002-10-07 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SHOW SIGN CIRCUIT REQ`D
 PER 600-5
  
 2)NOTE: PLEASE CLARIFY SHOW WINDOW
 OUTLETS PER 210-62
  
 3)NOTE: PLEASESHOW ALL CONTINUOUS LOAD
 -S AT 125%. 215-3/230-42
  
 4)NOTE: PLEASE CLARIFY METHOD OF
 EQUIPMENT GROUDING BETWEEM MAIN DISC AND
 PANEL "B" AND PANEL "B AND PANEL "A".
 EMT? PVC? PLEASE SIZE PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE SEE ANY FIRE REVIEW COMMENTS THAT
 MAY AFFECT ELECTRICAL PLANS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-10-25 Cont ID  
Sent By pkrauss Date 2002-10-25 Time 14:54 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-01-08 Cont ID  
Sent By nmccray Date 2003-01-08 Time 13:02 Rev Time 0.00
Received By nmccray Date 2003-01-08 Time 13:02 Sent To P
Notes
2003-01-08 00:00:001) THE SLIDING GLASS DOORS ARE TO
 REMAIN OPEN DURING BUSINESS HOURS.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-11-15 Cont ID  
Sent By mcarsill Date 2002-11-15 Time 11:13 Rev Time 0.00
Received By mcarsill Date 2002-11-15 Time 11:13 Sent To  
Notes
2002-11-15 00:00:00PREVIOUS PLAN REVIEW COMMENTS BY
 FIRE RESCUE NOT ADDRESSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-02 Cont ID  
Sent By mcarsill Date 2002-10-02 Time 10:53 Rev Time 0.00
Received By mcarsill Date 2002-10-02 Time 10:51 Sent To  
Notes
2002-10-02 00:00:001) EXIT SIGNS ARE DIRECTING PERSONS TO
 THE NEW FOUR TRACK SLIDING GLASS DOORS.
 DURING INCLEMENT WEATHER, WILL THE
 SLIDING DOORS BE OPEN OR CLOSED. IT
 APPEARS, BASED ON THE INTERIOR SEATING
 DIAGRAM, THAT THE BUILDING WILL BE
 CONSIDERED A NEW BUSINESS OCCUPANCY.
 PLEASE EXPLAIN EXITING DESIGN FOR THE
 USE OF THE REQUIRED SECOND MEANS OF
 EGRESS VIA THE TRACK SLIDING DOORS.
  
 2) HOW DOES THE OUTDOOR SEATING EFFECT
 EXITING FROM THE CAFE OR CIRCULATION
 FROM THE LOGGIA?
  
 3) WHAT DOOR HARDWARE WILL BE PROVIDED
 ON RELOCATED GATE AND FENCE.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 5) WILL ANY COOKING OF FOODS THAT
 PRODUCE SMOKE OR GREASE LADEN VAPORS BE
 CONDUCTED ON SITE?
  
 6) PLEASE INDICATE ON PLANS, LOCATIONS
 OF FIRE ALARM EQUIPMENT AND PORTABLE
 FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096 EXT. 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 10:27 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 10:27 Sent To M
Notes
2003-02-27 00:00:00TO MECH INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 17:11 Rev Time 0.00
Received By dpalmer Date 2003-01-07 Time 17:11 Sent To  
Notes
2003-01-07 00:00:00TO COMM BOARD #35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 16:42 Rev Time 0.00
Received By dpalmer Date 2002-11-13 Time 16:42 Sent To  
Notes
2002-11-13 00:00:00TO COMM BOARD #36

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-03-04 Cont ID  
Sent By pkrauss Date 2003-03-04 Time 15:31 Rev Time 0.30
Received By pkrauss Date 2003-03-04 Time 15:31 Sent To  
Notes
2003-03-04 00:00:00PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 10:27 Rev Time 0.30
Received By pkrauss Date 2003-02-04 Time 15:27 Sent To  
Notes
2003-02-04 00:00:00SUBMITTAL / CHANGE EQUIPMENT TO JANITROL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-27 Cont ID  
Sent By pkrauss Date 2002-11-27 Time 09:47 Rev Time 0.40
Received By pkrauss Date 2002-11-27 Time 09:36 Sent To  
Notes
2002-11-27 00:00:00PROVISO:
  
 1. CONDENSATE SHALL BE FULL LINE SIZE
 & TERMINATE INTO STORM DRAIN OR
 AN APPROVED DRYWELL.
  
 2. ADDITIONAL PERMIT REQUIRED FOR HOOD,
 FIRE SUPRESSION OR WALK-IN COOLERS.
 PROVIDE MANUFACTURER SUBMITTAL DATA
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-25 Cont ID  
Sent By pkrauss Date 2002-10-25 Time 14:38 Rev Time 0.40
Received By pkrauss Date 2002-10-25 Time 13:59 Sent To  
Notes
2002-10-25 00:00:00DENIED:
  
 PLEASE PROVIDE ENERGY & MANUAL J CALCS.
  
 PLAN SHEET M-2 INDICATES CONDENSER UNIT
 STAND AS BEING 30" FROM ROOF SURFACE TO
 THE BOTTOM OF THE SUPPORT RAIL.SEE
 ATTACHED TABLE (1511.7) OF THE FLORIDA
 BUIDLING CODE FOR THE PROPER HEIGHT
 REQUIREMENT.
  
 SEPARATE PERMIT REQUIRED FOR THE
 FOLLOWING:
  
 WALK-IN COOLERS OR FREEZERS
 HOOD & FIRE SUPRESSION (IF APPLICABLE)
 GAS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-01-09 Cont ID  
Sent By kstevens Date 2003-01-09 Time 17:32 Rev Time 0.75
Received By kstevens Date 2003-01-09 Time 17:31 Sent To  
Notes
2003-01-09 00:00:00PASSED/PROVISO
  
 EXPANSION TANK REQUIRED FOR WATER HEATER
 SAMPLE POINT REQUIRED PER R. COMPO
 BIG DIPPER NOT APPROVED - CHECK VALVE
 NOT APPROVED.
 REVISION REQUIRED FOR SHEETS P-1 & P-2
 SHOWING ALL CHANGES SHOWN.

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-01-08 Cont ID  
Sent By kstevens Date 2003-01-08 Time 15:01 Rev Time 1.33
Received By kstevens Date 2003-01-08 Time 15:01 Sent To  
Notes
2003-01-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEWS: PLEASE ROUTE
 PLANS TO THE DEPT. OF BUSINESS REGULAT-
 ION, HOTEL & RESTURANT DIVISION. (954)
 956-5692. PRIOR TO RESUBMITTING FOR PLAN
 REVIEW AT CITY OF WEST PALM BEACH. PLANS
 SHALL BE STAMPED AND WORK SHEET ATTACHED
 2) FROM PREVIOUS REVIEWS: PLEASE CONTACT
 RODNEY COMPO ENVIRONMENTAL COMPLIANCE,
 AT (561) 837-4074. MINIMUM 750 GALLON
 GREASE TRAP REQUIRED. WASTE ORD. #2938-
 96.
 3) FROM PREVIOUS REVIEWS: SHT P-1 & SHT
 P-2 SEPARATE GREASE LINE REQUIRED.
 4) FROM PREVIOUS REVIEWS: THERMAL EXPAN-
 SION CONTROL IS REQUIRED AT WATER HEATER
 DETAIL SHT P-2. SEC 607.3.2- AN EXPAN-
 SION TANK IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-10 Cont ID  
Sent By nmccray Date 2003-01-08 Time 13:02 Rev Time 1.00
Received By kstevens Date 2002-12-10 Time 13:11 Sent To  
Notes
2002-12-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, PLEASE ROUTE
 PLANS TO THE DEPT. OF BUSINESS REGULAT-
 ION, HOTEL & RESTURANT DIVISION (954)
 956-5692 PRIOR TO RE-SUBMITTING FOR PLAN
 REVIEW AT THE CITY OF WPB.
 2) FROM PREVIOUS REVIEW, PLEASE CONTACT
 RODNEY COMPO ENVIRONMENTAL COMPLIANCE
 MANAGER FOR SIZING OF GREASE TRAP.
 3) FROM PREVIOUS REVIEW, SHT P-1 MINIMUM
 FACILITIES TABLE 403.1 REQUIRE A DRINK-
 ING FOUNTAIN.
 4) FROM PREVIOUS REVIEW, SHT P-1 WATER
 FILTER SHALL BE NSF APPROVED. PLEASE
 SUBMIT MANUF. INFO.
 5) FROM PREVIOUS REVIEW, SHT P-1 PLUMB-
 ING NOTES #5, AIR CHAMBERS ARE NOT APP-
 ROVED. PLEASE DELETE REFERENCE FROM NOTE
 6) FROM PREVIOUS REVIEW, SHT P-1 SEPAR-
 ATE GREASE LINE REQUIRED.
 7) FROM PREVIOUS REVIEW, SHT P-1 BACK-
 FLOW IS REQUIRED FOR WATER SERVICE. MAX-
 IMUM 4' FINISHED FLOOR. ALSO SHOW ON
 RISER DIAGRAM SHT P-2.
 8) FROM PREVIOUS REVIEW, THERMAL EXPAN-
 SIONCONTROL IS REQUIRED AT WATER HEATER
 DETAIL SHT P-2. SEC 607.3.2
 9) FROM PREVIOUS REVIEW, SHT P-2 SANIT-
 ARY - GREASE WASTE RISER DIAGRAM, SEPAR-
 ATE GREASE LINE REQUIRED.
 10) NEW NOTE: WHEN ADDRESSING PLAN RE-
 VIEW COMMENTS, A TRANSMITTAL LETTER
 LISTING ORIGINAL REVIEW COMMENT NUMBER
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OF SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND.
 THIS WILL HELP EXPEDITE YOUR PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-15 Cont ID  
Sent By kstevens Date 2002-10-15 Time 11:03 Rev Time 0.00
Received By kstevens Date 2002-10-15 Time 11:03 Sent To  
Notes
2002-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING.
  
 1) PLEASE ROUTE PLANS TO THE DEPT. OF
 BUSINESS REGULATION, HOTEL & RESTURANT
 DIVISION (954) 956-5692 PRIOR TO RE-SUB-
 MITTING FOR PLAN REVIEW AT CITY WPB.
 2) PLEASE CONTACT RODNEY COMPO ENVIRON-
 MENTAL COMPLIANCE MANAGER FOR SIZING OF
 GREASE TRAP.
 3) SHT P-1 MINIMUM FACILITIES TABLE
 407.3.1 REQUIRES A DRINKING FOUNTAIN.
 4) SHT P-1, WATER FILTER SHALL BE NSF
 APPROVED. PLEASE PROVIDE MANUF. INFO.
 5) SHT P-1 DOMESTIC WATER PIPING CALLS
 FOR GALVANIZED PIPE. ENGINEER SAYS THAT
 COPPER WILL BE USED. (SEE NOTE #3 UNDER
 PIPING MATERIALS). PLEASE CHANGE NOTES
 #1 & #2 FROM GALV. TO COPPER.
 6) SHT P-1 PLUMBING NOTES #5, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE REF-
 ERENCE FROM NOTES.
 7) SHT P-1 SEPARATE GREASE LINE REQUIRED
 8) SHT P-1 BACKFLOW IS REQUIRED FOR
 WATER SERVICE. MAXIMUM 4' ABOVE FINISHED
 FLOOR. ALSO SHOW ON WATER RISER DIAGRAM
 SHT P-2.
 9) SHT P-2 WATER HEATER DETAIL, PAN
 DRAIN/RELIEF VALVE DRAIN (T/P) SHALL
 DRAIN INTO A FLOOR SINK. FLOOR DRAIN NOT
 AN INDIRECT WASTE RECEPTOR. - THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION
 607.3.2
 10) SHT P-2 SANITARY - GREASE WASTE
 RISER DIAGRAM, SEPARATE GREASE LINE
 REQUIRED.
 11) HEALTH DEPT. REQUIREMENT - 140 DEGR-
 EE WATER REQUIRED FOR 3 COMPARTMENT SINK
 AND JANITOR SINK. - MIXING VALVE REQ-
 UIRED FOR 110 DEGREE WATER FOR OTHER
 FIXTURES REQUIRING HOT WATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-10-25 Cont ID  
Sent By pkrauss Date 2002-10-25 Time 14:55 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***