Plan Review Details - Permit 02091548
Plan Review Stops For Permit 02091548
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-04 Cont ID  
Sent By hpiskura Date 2002-12-04 Time 10:25 Rev Time 0.00
Received By hpiskura Date 2002-12-04 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-17 Cont ID  
Sent By dpalmer Date 2002-12-03 Time 07:58 Rev Time 0.00
Received By hpiskura Date 2002-10-17 Time 11:25 Sent To  
Notes
2002-10-17 00:00:00THIS BUILDING IS SUBJECT TO IMPACT FEES
 COLLECTED BY THE COUNTY.THE PERMIT
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 PLEASE PROVIDE A RECENT SURVEY OF THE
 PROPERTY TO COORDINATE THE LOCATION OF
 THE PROPOSED BUILDING WITH THE SITE
 PLAN.
  
  
 IT APPEARS THE BUILDING WILL BE LOCATED
 IN A LANDSCAPE STRIP.WILL THERE BE ANY
 DRIVEWAYS OR CURBCUTS ASSOCIATED WITH
 THE GARAGE?PLEASE STATE INFORMATION
 ON THE PLANS.SEE FBC 104.2.
  
 WHAT WILL BE STORED IN THE BUILDING RE:
 CHEMICALS OR FUELS?PLEASE NOTE ON
 PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-03 Cont ID  
Sent By dpalmer Date 2002-12-03 Time 07:57 Rev Time 0.50
Received By dpalmer Date 2002-12-03 Time 07:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-07 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 17:57 Rev Time 0.75
Received By dpalmer Date 2002-10-07 Time 08:44 Sent To  
Notes
2002-10-07 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE/CLARIFY EXISTING
 SERVICE SHOWS FEED COMING FROM EXISTING
 100A PANEL GOING THROUGH METER AND THEN
 OUT TO BLDG. PLEASE NOTE MIXING LINE
 AND LOAD IN METER NOT PERMITTED. 215-5
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATION
 FOR EXISTING 100A PANEL. PLEASE SHOW
 SIZE OF OCP TO FEED MAINT BLDG.
 215-5
 3)NOTE: PLEASE NOTE NO INFORMATION SHOWN
 FOR NEW DISC AND PANEL AT DETACHED BLDG.
 215-5
 4)NOTE: PLEASE NOTE NO GROUNDING SYSTEM
 SHOWN AT DETACHED BLDG. 250-31
  
 5)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE W/ A SUBMITTED PANEL
 SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-10-04 Cont ID  
Sent By mcarsill Date 2002-10-04 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2002-10-04 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 17:57 Rev Time 0.00
Received By btrobaug Date 2002-11-26 Time 17:57 Sent To E
Notes
2002-11-26 00:00:00TO DVP./WRT

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-02 Cont ID  
Sent By sgraham Date 2002-10-02 Time 11:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***