Plan Review Details - Permit 02091401
Plan Review Stops For Permit 02091401
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-29 Cont ID  
Sent By mcarsill Date 2002-10-29 Time 16:35 Rev Time 1.00
Received By mcarsill Date   Time   Sent To  
Notes
2002-10-29 00:00:00APPROVED BY HAROLD 10/23/02LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-16 Cont ID  
Sent By hpiskura Date 2002-10-16 Time 14:52 Rev Time 0.00
Received By hpiskura Date 2002-10-16 Time 14:21 Sent To  
Notes
2002-10-16 00:00:00SHOW THE DESIGN PRESSURES +/- FOR THE
 STOREFRONT GLAZING TO BE INSTALLED.
 SEE FBC 1606.1.7 #5 AND FBC 3401.7.2.4.
  
 IF TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS FOR THE WINDOW SYSTEM ARE NOT
 INCLUDED WITH THIS APPLICAION A
 SEPARATE PERMIT, PLANS AND FEES WILL BE
 REQUIRED FOR THAT WORK.
  
 THE STORE FRONT MODIFICATION IS SUBJECT
 TO CITY PLACE REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-23 Cont ID  
Sent By dpalmer Date 2002-10-23 Time 05:59 Rev Time 0.25
Received By dpalmer Date 2002-10-23 Time 05:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-26 Cont ID  
Sent By dpalmer Date 2002-09-26 Time 08:04 Rev Time 0.25
Received By dpalmer Date 2002-09-26 Time 08:01 Sent To  
Notes
2002-09-26 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO BE
 STAMPED BY CITY PLACE FOR CONSTRUCTION
 APPROVAL.
  
 2)NOTE: PLEASE CALRIFY CIRCUTIING FOR
 EM/ EXIT LTS PER 700-12
  
 3)NOTE: PLEASE NOTE RECEPTS REQ`D FOR
 SHOW WINDOWS. PER 210-62
 EXISTING?
  
 PLEASE SEE ANY FIRE REVIEW COMMENTS THAT
 MAY AFFECT ELECTRICAL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-29 Cont ID  
Sent By mcarsill Date 2002-10-29 Time 16:37 Rev Time 0.00
Received By mcarsill Date 2002-10-29 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 15:50 Sent To  
Notes
2002-09-24 00:00:001) PLANS DO NOT CONTAIN CITY PLACE
 CONSTRUCTION APPROVAL STAMP.
  
 2) SEPARATE FIRE ALARM PANEL SHOWN
 ON THE PLANS WILL NOT BE ALLOWED TO
 BE INSTALLED. FIRE ALARM EQUIPMENT FOR
 SPACE MUST BE CONNECTED TO THE BASE
 BUILDING'S FIRE ALARM SYSTEM.
  
 3) PLEASE INDICATE ON THE PLANS ANY
 TENANT DEMISING WALLS.
  
 4) FIRE SPRINKLER HEADS ARE REQUIRED
 THROUGHOUT INCLUDING BATHROOM AND
 ENTRY FOYER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-15 Cont ID  
Sent By pkrauss Date 2002-10-15 Time 12:10 Rev Time 0.35
Received By pkrauss Date 2002-10-15 Time 11:47 Sent To  
Notes
2002-10-15 00:00:00PROVISO ON PLAN -
  
 R/A REQUIRED IN "OFFICE" SPACE AS PER
 2001 FBC(M) 601.4.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-05 Cont ID  
Sent By kstevens Date 2002-11-05 Time 14:57 Rev Time 1.00
Received By kstevens Date 2002-11-05 Time 14:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 13:22 Rev Time 0.50
Received By kstevens Date 2002-10-12 Time 13:22 Sent To  
Notes
2002-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-3 DETAIL D, HDCP SINK SHALL BE
 34" MAX PER 11-4.24.2
 2) SHT M-1, PLEASE PROVIDE A WATER RISER
 DIAGRAM. IF WATER HAMMER ARRESTOR IS
 USED, LOCATE NEAR FIXTURE NOT IN CEILING
 AT TOP OF DROP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377