| Plan Review Stops For Permit 02091401 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-29 |
Time |
16:35 |
Rev Time |
1.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-29 00:00:00 | APPROVED BY HAROLD 10/23/02LM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-16 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-16 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2002-10-16 00:00:00 | SHOW THE DESIGN PRESSURES +/- FOR THE | | | STOREFRONT GLAZING TO BE INSTALLED. | | | SEE FBC 1606.1.7 #5 AND FBC 3401.7.2.4. | | | | | | IF TEST AND OR NOTICE OF ACCEPTANCE | | | REPORTS FOR THE WINDOW SYSTEM ARE NOT | | | INCLUDED WITH THIS APPLICAION A | | | SEPARATE PERMIT, PLANS AND FEES WILL BE | | | REQUIRED FOR THAT WORK. | | | | | | THE STORE FRONT MODIFICATION IS SUBJECT | | | TO CITY PLACE REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-10-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-23 |
Time |
05:59 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-10-23 |
Time |
05:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-09-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-09-26 |
Time |
08:04 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-09-26 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2002-09-26 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE PLANS NEED TO BE | | | STAMPED BY CITY PLACE FOR CONSTRUCTION | | | APPROVAL. | | | | | | 2)NOTE: PLEASE CALRIFY CIRCUTIING FOR | | | EM/ EXIT LTS PER 700-12 | | | | | | 3)NOTE: PLEASE NOTE RECEPTS REQ`D FOR | | | SHOW WINDOWS. PER 210-62 | | | EXISTING? | | | | | | PLEASE SEE ANY FIRE REVIEW COMMENTS THAT | | | MAY AFFECT ELECTRICAL PLANS. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-29 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-29 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-09-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-09-24 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-24 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2002-09-24 00:00:00 | 1) PLANS DO NOT CONTAIN CITY PLACE | | | CONSTRUCTION APPROVAL STAMP. | | | | | | 2) SEPARATE FIRE ALARM PANEL SHOWN | | | ON THE PLANS WILL NOT BE ALLOWED TO | | | BE INSTALLED. FIRE ALARM EQUIPMENT FOR | | | SPACE MUST BE CONNECTED TO THE BASE | | | BUILDING'S FIRE ALARM SYSTEM. | | | | | | 3) PLEASE INDICATE ON THE PLANS ANY | | | TENANT DEMISING WALLS. | | | | | | 4) FIRE SPRINKLER HEADS ARE REQUIRED | | | THROUGHOUT INCLUDING BATHROOM AND | | | ENTRY FOYER. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-15 |
Time |
12:10 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-10-15 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2002-10-15 00:00:00 | PROVISO ON PLAN - | | | | | | R/A REQUIRED IN "OFFICE" SPACE AS PER | | | 2001 FBC(M) 601.4. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-05 |
Time |
14:57 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-11-05 |
Time |
14:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-10-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-10-12 |
Time |
13:22 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-10-12 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2002-10-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A-3 DETAIL D, HDCP SINK SHALL BE | | | 34" MAX PER 11-4.24.2 | | | 2) SHT M-1, PLEASE PROVIDE A WATER RISER | | | DIAGRAM. IF WATER HAMMER ARRESTOR IS | | | USED, LOCATE NEAR FIXTURE NOT IN CEILING | | | AT TOP OF DROP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|